Product Overview
Product brand name: SIRIUS
Product designation: Circuit breaker
Product type designation: 3RV2
Description: Circuit breaker size S00 for starter combination, rated current 4 A, N release 52 A, screw terminal, standard switching capacity.
General Technical Data
Parameter | Value |
---|---|
Size of the circuit-breaker | S00 |
Size of contactor can be combined | S00, S0 |
Product extension: auxiliary switch | Yes |
Power loss [W] for rated value of the current at AC in hot operating state | 7.25 W |
Power loss [W] per pole at AC in hot operating state | 2.4 W |
Insulation voltage with degree of pollution 3 at AC rated value | 690 V |
Surge voltage resistance rated value | 6 kV |
Shock resistance according to IEC 60068-2-27 | 25g / 11 ms |
Mechanical service life (operating cycles) of the main contacts typical | 100,000 |
Mechanical service life (operating cycles) of auxiliary contacts typical | 100,000 |
Electrical endurance (operating cycles) typical | 100,000 |
Reference code according to IEC 81346-2 | Q |
Substance Prohibitance (Date) | 10/01/2009 |
SVHC substance name | Lead - 7439-92-1 |
Weight | 0.342 kg |
Ambient Conditions
Parameter | Value |
---|---|
Installation altitude at height above sea level maximum | 2,000 m |
Ambient temperature during operation | -20 ... +60 °C |
Ambient temperature during storage | -50 ... +80 °C |
Ambient temperature during transport | -50 ... +80 °C |
Relative humidity during operation | 10 ... 95 % |
Environmental footprint | Siemens EcoTech |
Main Circuit
Parameter | Value |
---|---|
Number of poles for main current circuit | 3 |
Type of voltage for main current circuit | AC |
Operating voltage rated value | 20 ... 690 V |
Operating voltage at AC-3 rated value maximum | 690 V |
Operating voltage at AC-3e rated value maximum | 690 V |
Operating frequency rated value | 50 ... 60 Hz |
Operational current rated value | 4 A |
Operational current at AC-3 at 400 V rated value | 4 A |
Operational current at AC-3e at 400 V rated value | 4 A |
Operating power at AC-3 at 230 V rated value | 0.8 kW |
Operating power at AC-3 at 400 V rated value | 1.5 kW |
Operating power at AC-3 at 500 V rated value | 2.2 kW |
Operating power at AC-3 at 690 V rated value | 3 kW |
Operating power at AC-3e at 230 V rated value | 0.8 kW |
Operating power at AC-3e at 400 V rated value | 1.5 kW |
Operating power at AC-3e at 500 V rated value | 2.2 kW |
Operating power at AC-3e at 690 V rated value | 3 kW |
Operating frequency at AC-3 maximum | 15 1/h |
Operating frequency at AC-3e maximum | 15 1/h |
Auxiliary Circuit
Parameter | Value |
---|---|
Type of voltage for auxiliary and control circuit | AC/DC |
Number of NC contacts for auxiliary contacts | 0 |
Number of NO contacts for auxiliary contacts | 0 |
Number of CO contacts for auxiliary contacts | 0 |
Protective and Monitoring Functions
Parameter | Value |
---|---|
Product function: ground fault detection | No |
Product function: phase failure detection | No |
Maximum short-circuit current breaking capacity (Icu) at AC at 240 V rated value | 100 kA |
Maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value | 100 kA |
Maximum short-circuit current breaking capacity (Icu) at AC at 500 V rated value | 100 kA |
Maximum short-circuit current breaking capacity (Icu) at AC at 690 V rated value | 6 kA |
Operating short-circuit current breaking capacity (Ics) at AC at 240 V rated value | 100 kA |
Operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value | 100 kA |
Operating short-circuit current breaking capacity (Ics) at AC at 500 V rated value | 100 kA |
Operating short-circuit current breaking capacity (Ics) at AC at 690 V rated value | 4 kA |
Response value current of instantaneous short-circuit trip unit | 52 A |
UL/CSA Ratings
Parameter | Value |
---|---|
Full-load current (FLA) for 3-phase AC motor at 480 V rated value | 4 A |
Full-load current (FLA) for 3-phase AC motor at 600 V rated value | 4 A |
Yielded mechanical performance [hp] for single-phase AC motor at 110/120 V rated value | 0.13 hp |
Yielded mechanical performance [hp] for single-phase AC motor at 230 V rated value | 0.33 hp |
Yielded mechanical performance [hp] for 3-phase AC motor at 200/208 V rated value | 0.8 hp |
Yielded mechanical performance [hp] for 3-phase AC motor at 220/230 V rated value | 0.75 hp |
Yielded mechanical performance [hp] for 3-phase AC motor at 460/480 V rated value | 2 hp |
Yielded mechanical performance [hp] for 3-phase AC motor at 575/600 V rated value | 3 hp |
Short-Circuit Protection
Parameter | Value |
---|---|
Product function short circuit protection | Yes |
Design of the short-circuit trip | Magnetic |
Design of the fuse link for IT network for short-circuit protection of the main circuit at 400 V | gL/gG 32 A |
Design of the fuse link for IT network for short-circuit protection of the main circuit at 500 V | gL/gG 32 A |
Design of the fuse link for IT network for short-circuit protection of the main circuit at 690 V | gL/gG 25 A |
Installation/ Mounting/ Dimensions
Parameter | Value |
---|---|
Mounting position | Any |
Fastening method | Screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
Height | 97 mm |
Width | 45 mm |
Depth | 97 mm |
Required spacing with side-by-side mounting at the side | 0 mm |
Required spacing for grounded parts at 400 V - downwards | 30 mm |
Required spacing for grounded parts at 400 V - upwards | 30 mm |
Required spacing for grounded parts at 400 V - at the side | 9 mm |
Required spacing for live parts at 400 V - downwards | 30 mm |
Required spacing for live parts at 400 V - upwards | 30 mm |
Required spacing for live parts at 400 V - at the side | 9 mm |
Required spacing for grounded parts at 500 V - downwards | 30 mm |
Required spacing for grounded parts at 500 V - upwards | 30 mm |
Required spacing for grounded parts at 500 V - at the side | 9 mm |
Required spacing for live parts at 500 V - downwards | 30 mm |
Required spacing for live parts at 500 V - upwards | 30 mm |
Required spacing for live parts at 500 V - at the side | 9 mm |
Required spacing for grounded parts at 690 V - downwards | 50 mm |
Required spacing for grounded parts at 690 V - upwards | 50 mm |
Required spacing for grounded parts at 690 V - backwards | 0 mm |
Required spacing for grounded parts at 690 V - at the side | 30 mm |
Required spacing for grounded parts at 690 V - forwards | 0 mm |
Required spacing for live parts at 690 V - downwards | 50 mm |
Required spacing for live parts at 690 V - upwards | 50 mm |
Required spacing for live parts at 690 V - backwards | 0 mm |
Required spacing for live parts at 690 V - at the side | 30 mm |
Required spacing for live parts at 690 V - forwards | 0 mm |
Connections/ Terminals
Parameter | Value |
---|---|
Type of electrical connection for main current circuit | Screw-type terminals |
Arrangement of electrical connectors for main current circuit | Top and bottom |
Type of connectable conductor cross-sections for main contacts - solid or stranded | 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
Type of connectable conductor cross-sections for main contacts - finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
Type of connectable conductor cross-sections for AWG cables for main contacts | 2x (18 ... 14), 2x 12 |
Tightening torque for main contacts with screw-type terminals | 0.8 ... 1.2 N·m |
Design of screwdriver shaft | Diameter 5 to 6 mm |
Size of the screwdriver tip | Pozidriv size 2 |
Design of the thread of the connection screw for main contacts | M3 |
Safety Related Data
Parameter | Value |
---|---|
Product function suitable for safety function | Yes |
Suitability for use: safety-related switching on | No |
Suitability for use: safety-related switching OFF | Yes |
Service life maximum | 10 a |
Test wear-related service life necessary | Yes |
Proportion of dangerous failures with low demand rate according to SN 31920 | 40 % |
Proportion of dangerous failures with high demand rate according to SN 31920 | 50 % |
B10 value with high demand rate according to SN 31920 | 5,000 |
Failure rate [FIT] with low demand rate according to SN 31920 | 50 FIT |
Device type according to ISO 13849-1 | 3 |
Overdimensioning according to ISO 13849-2 necessary | Yes |
Safety device type according to IEC 61508-2 | Type A |
T1 value for proof test interval or service life according to IEC 61508 | 10 a |
Electrical Safety
Parameter | Value |
---|---|
Protection class IP on the front according to IEC 60529 | IP20 |
Touch protection on the front according to IEC 60529 | Finger-safe, for vertical contact from the front |
Display
Parameter | Value |
---|---|
Display version for switching status | Handle |
Approvals and Certificates
General Product Approval
Logos for CCC, EG-Konf., UKCA, UL, EAC, S represent various certifications and compliance standards.
Test Certificates
Includes Type Test Certificates/Test Report and Special Test Certificates for various applications like Maritime and Railway.
Maritime Application
Certifications from ABS, BUREAU VERITAS, DNV, LRS, PRS, RINA are listed.
Other
Miscellaneous certifications including QC PASS and VDE.
Environment
Environmental Confirmations and Siemens EcoTech information.
Diagrams and Visuals
Device Dimensions and Views
The device has a front view and a side view. The front view shows the main terminals labeled 1/L1, 3/L2, 5/L3 at the top and 2/T1, 4/T2, 6/T3 at the bottom. It features a central operating lever with positions for ON, OFF, and TRIPPED, and the branding "SIEMENS" and "3RV2". Dimensions indicated are 97 mm height, 45 mm width, and 97 mm depth. The side view shows a depth of 96.9 mm and a height of 49 mm from the mounting rail interface, with a 5 mm projection at the bottom.
Circuit Diagram
The schematic shows a three-pole circuit breaker. The input terminals are labeled 1/L1, 3/L2, and 5/L3. The output terminals are labeled 2/T1, 4/T2, and 6/T3. Each pole contains a symbol representing a current-limiting device (I>) indicating short-circuit protection. A symbol labeled "-F" is shown, likely representing a fault detection or protection function.
Further Information
- Information on the packaging: https://support.industry.siemens.com/cs/ww/en/view/109813875
- Information- and Downloadcenter (Catalogs, Brochures,...): https://www.siemens.com/ic10
- Industry Mall (Online ordering system): https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2311-1EC10
- Cax online generator: http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2311-1EC10
- Service&Support (Manuals, Certificates, Characteristics, FAQs,...): https://support.industry.siemens.com/cs/ww/en/ps/3RV2311-1EC10
- Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...): http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2311-1EC10&lang=en
- Characteristic: Tripping characteristics, I²t, Let-through current: https://support.industry.siemens.com/cs/ww/en/ps/3RV2311-1EC10/char
- Further characteristics (e.g. electrical endurance, switching frequency): http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2311-1EC10&objecttype=14&gridview=view1
Document version: 3RV23111EC10, Page 4/6, Last modified: 5/17/2025. Subject to change without notice. © Copyright Siemens.