SIEMENS SENTRON Miniature Circuit Breaker

Data Sheet: 5SY4603-5

General Technical Data

Number of poles4
Design of pole3P+N
Tripping characteristic classA
Mechanical service life (operating cycles) typical10,000
Overvoltage categoryIII
Degree of pollution3

Voltage

Type of voltage of the operating voltageAC
Insulation voltage (Ui)440 V
Supply voltage with single-phase operation at AC rated value230 V

Operational Current

Supply Voltage

Supply voltage at AC400 V
Supply voltage at DC rated value60 V
Value range of the supply voltage frequency50/60 Hz
Operating voltage at DC rated value maximum72 V

Protection Class

Protection class IP: IP20, with connected conductors

Breaking Capacity

Switching capacity current at DC according to IEC 60947-2 rated value15 kA
Switching capacity current according to EN 60898 rated value10 kA
Switching capacity current according to IEC 60947-2 rated value35 kA

Dissipation

Power loss [W] for rated value of the current at AC in hot operating state per pole1.9 W
Suitability for operationInfrastructure / Industry

Product Details

Product Function

Set values setting current (Ii) for I-tripping2.5 A
Reference value setting current (Ii) for I-trippingx In

Short Circuit

Short-circuit current breaking capacity (Icn) at AC according to UL 1077 and CSA C22.2 No.2355 kA

Connections

Connectable Conductor Cross-Section

TypeMinimumMaximum
Solid0.75 mm²35 mm²
Stranded0.75 mm²35 mm²
Finely stranded with core end processing0.75 mm²25 mm²

AWG Number

Minimum18
Maximum4

Tightening Torque

With Screw-Type Terminals [lbf·in]22 - 31 lbf·in
With Screw-Type Terminals [N·m]2.5 - 3.5 N·m

Mechanical Design

Height90 mm
Width72 mm
Depth76 mm
Installation depth70 mm
Number of modular width units4
Fastening methodDIN rail
Mounting positionAny
Net weight655 g

Environmental Conditions

Influence of the surrounding temperaturemax. 95% RH up to 55°C, max. 55% RH up to 70°C, max. 35% RH up to 75°C
StandardIEC / EN 60898-1, IEC / EN 60947-2 / UL1077
Vibration resistance according to IEC 60068-2-6±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz
Ambient temperature during operation (minimum)-40 °C
Ambient temperature during operation (maximum)70 °C
Ambient temperature during storage (minimum)-40 °C
Ambient temperature during storage (maximum)75 °C
Number of test cycles for environmental testing according to IEC 60068-2-306

Diagrams and Dimensions

The document includes diagrams illustrating the physical dimensions and internal schematic of the miniature circuit breaker.

Physical Dimensions

One diagram shows the front and side profiles, indicating:

Another view shows the top profile.

Circuit Schematic

A circuit diagram represents the internal connections for a 3+N pole configuration. It shows terminals numbered 1 through 8, with terminals 7 and 8 designated for the neutral conductor ('N'). Each pole (1-2, 3-4, 5-6) is depicted with a switch symbol representing the circuit breaker contacts. The schematic includes a symbol for the tripping mechanism and indicates connections related to neutral conductor switching.

Approvals and Certificates

The product has received various general product approvals, test certificates, and maritime/railway/environmental certifications, including:

Further Information

PDF preview unavailable. Download the PDF instead.

A700000014403345 Conplement Ag

Related Documents

Preview Siemens SENTRON Miniature Circuit Breaker 5SY4204-5 Datasheet
Technical datasheet for the Siemens SENTRON 5SY4204-5 miniature circuit breaker. Details include electrical specifications, breaking capacity, connections, mechanical design, and environmental conditions.
Preview Siemens SENTRON 5SJ4113-7HG41 Miniature Circuit Breaker Datasheet
Comprehensive datasheet for the Siemens SENTRON 5SJ4113-7HG41 miniature circuit breaker. Details include electrical specifications (voltage, current, breaking capacity), mechanical dimensions, environmental conditions, product features, and relevant approvals.
Preview Siemens SENTRON 3VA4 Molded-Case Circuit Breaker Datasheet
Technical datasheet for the Siemens SENTRON 3VA4 series molded-case circuit breaker, model 3VA4130-5ED34-0AA0. This 3-pole breaker offers 30A operational current, 35kA breaking capacity at 480V, TM210 line protection, and is designed for system protection.
Preview Siemens WL Circuit Breakers: Selection and Application Guide
Comprehensive guide to Siemens WL Low Voltage Circuit Breakers, covering selection, application, features, specifications, and accessories for UL489 and UL1066 listed products.
Preview Siemens 3VA and 3VM Molded Case Circuit Breakers: Technical Specifications and Product Overview
Explore the Siemens 3VA and 3VM series of molded case circuit breakers (MCCBs). This document details their advanced features, technical specifications, trip units, accessories, and applications for reliable power distribution and protection in industrial and building environments.
Preview Siemens 3VA5110-4EC31-0AA0 Molded-Case Circuit Breaker Data Sheet
Detailed technical data sheet for the Siemens SENTRON 3VA5110-4EC31-0AA0 molded-case circuit breaker, covering electrical specifications, switching capacity, mechanical design, and certifications.
Preview Siemens 3VA9908-0BB23 Undervoltage Release - Technical Data Sheet
Detailed technical specifications for the Siemens SENTRON 3VA9908-0BB23 undervoltage release accessory. Includes electrical, mechanical, connection data, certifications, and dimensions for 3VA1 and 3VA20-26 circuit breakers.
Preview Siemens PM6 and PMK Circuit Breaker Installation Instructions
Comprehensive installation guide for Siemens PM6 and PMK Thermal Magnetic Trip Circuit Breakers, covering safety precautions, preparation, mounting procedures, and field testing requirements.