Lochinvar Amicus Aquastore Installation Planning Guide

Contact: info@lochinvar.ltd.uk | www.lochinvar.ltd.uk

Document Control

Article Language Version Modified by
Amicus Aquastore Planning guide English V1.3 July 2025 S Hunt

Introduction

This document provides essential information for the Design team from stage 2 to stage 5 of a project. The Amicus Aquastore is a packaged heat pump water heater designed for indoor plantroom installation, capable of providing Domestic Hot Water (DHW) at temperatures up to 65°C. The range includes three models, each with an 8 kW heat pump and immersion backup options from 6 kW to 12 kW.

The Aquastore offers three operating modes:

Standard features include:

Sizing

The Aquastore can be sized for Efficiency or Hybrid mode using the provided tables. The tables illustrate typical one-hour peak supply utilizing stored water and recovery. Sizing requires careful consideration of hot water load and peak demand periods. Lochinvar offers sizing assistance; contact your local area sales manager or email info@lochinvar.ltd.uk.

Operational Limits (Heat Pump Only): The Amicus Aquastore can deliver DHW up to 65°C in Hybrid mode and 85°C in Power mode (using electric elements only). The operational limits diagram shows the heat pump's performance range. Outside these limits, immersion heaters will activate to reach the 65°C setpoint.

Diagram Description: A line graph showing the operational limits of the heat pump. The Y-axis represents 'Outside air temperature' (°C) from 0 to 25. The X-axis represents 'Maximum flow temperature (Heat pump only)' (°C) from 35 to 65. The operational area is a red rectangle indicating that the heat pump can operate within specific air and flow temperature ranges.

Table 1: Sizing Capacity (litres)
Efficiency Mode Hybrid Mode
Tcold = 10°C / Tset = 65°C
Draw capacity direct ΔT=28 K 590 ltr 590 ltr 590 ltr 590 ltr 590 ltr 590 ltr
30 min. ΔT=28 K 690 ltr 710 ltr 730 ltr 750 ltr 780 ltr 810 ltr
60 min. ΔT=28 K 800 ltr 830 ltr 860 ltr 1000 ltr 1040 ltr 1070 ltr
90 min. ΔT=28 K 910 ltr 950 ltr 990 ltr 1250 ltr 1300 ltr 1340 ltr
120 min. ΔT=28 K 1020 ltr 1070 ltr 1130 ltr 1510 ltr 1570 ltr 1600 ltr
Tcold = 10°C / Tset = 65°C
Draw capacity direct ΔT=50 K 260 ltr 260 ltr 260 ltr 260 ltr 260 ltr 260 ltr
30 min. ΔT=50 K 300 ltr 300 ltr 300 ltr 330 ltr 340 ltr 350 ltr
60 min. ΔT=50 K 350 ltr 350 ltr 360 ltr 460 ltr 480 ltr 490 ltr
90 min. ΔT=50 K 390 ltr 400 ltr 410 ltr 600 ltr 620 ltr 630 ltr
120 min. ΔT=50 K 430 ltr 450 ltr 470 ltr 730 ltr 760 ltr 780 ltr

General

The Amicus Aquastore should be installed in a plantroom that can support its weight, provides adequate space for maintenance, does not cause noise nuisance, and has sufficient ventilation.

Operational limits

The unit can provide DHW up to 65°C in Hybrid mode and 85°C in Electric mode (for pasteurization). The diagram below illustrates the heat pump's general working limits. Outside these parameters, immersion heaters will be used to achieve the 65°C setpoint.

Diagram Description: A line graph titled 'Drawing 1 operational limits'. The Y-axis is 'Outside air temperature' (°C) ranging from 0 to 25. The X-axis is 'Maximum flow temperature (Heat pump only)' (°C) ranging from 35 to 65. A red boundary defines the operational zone for the heat pump.

Technical Details

Table 1: Technical details
Model LAAS8-455-6 LAAS8-455-9 LAAS8-455-12
Input power heat pump operation kW 2.22 2.22 2.22
Heating capacity heat pump (EN 16147 - A15) kW 8 8 8
Efficiency COP 3.2 3.2 3.2
Heating capacity electric elements kW 6 9 12
Power supply 400Vac/3N 400Vac/3N 400Vac/3N
Total heating capacity kW 14 17 20
Peak current A 39.5 50.8 65.7
Maximum current (L1) - heat pump A 9.6 9.6 9.6
Maximum input (L2) - back up element 1 + controls + fans A 16.9 22.5 30
Maximum current (L3) - back up element 2 A 13 18.7 26.1
Refrigerant (weight.CO2 equivalent) (kg/ton) R134 (1.85/2.646) R134 (1.85/2.646) R134 (1.85/2.646)
Tank volume Ltr 445 445 445
Max Water Temperature Efficiency or Hybrid mode °C 65 65 65
Max Water Temperature Immersion heaters only °C 85 85 85
Operating range °C -7-43 -7-43 -7-43
Shipping weight kg 226 226 226
Weight when full kg 684 684 684
Sound Power-Indoors dB 59 59 59
Table 2: Dimensions
Device height Device width Device depth Height cold water supply connection Height hot water outlet connection Height drain valve connection Height T&P-valve connection Height condensate drain connection Cold water supply connection (female) Hot water outlet connection (female) Drain valve connection (female) T&P-valve connection (female)
mm mm mm mm mm mm mm mm NPT NPT NPT NPT
LAAS8-455-6 1770 785 995 165 1470 165 1470 15 3/4" 3/4" 3/4" 3/4"
LAAS8-455-9 1770 785 995 165 1470 165 1470 15 3/4" 3/4" 3/4" 3/4"
LAAS8-455-12 1770 785 995 165 1470 165 1470 15 3/4" 3/4" 3/4" 3/4"

Diagram Description: 'Drawing 2 Dimensions' shows front and top views of the Amicus Aquastore unit with various dimensions labeled (A, D, E, M, B, R, S, W) and connection points numbered (1, 2, 4, 5).

Position on Site

The Amicus Aquastore is designed for indoor plantroom installation only. The plantroom must be sufficiently large to prevent excessive cooling during unit operation. The required size depends on the heat pump's usage patterns, with larger peak demands necessitating larger plantrooms.

If the plantroom contains appliances with open flues, ensure the Aquastore does not affect their combustion. A qualified gas engineer should assess the installation. Minimum clearances are required around the unit for maintenance.

Diagram Description: 'Drawing 3 clearances single unit' illustrates the required clearances for a single unit. The front view shows a 1000mm clearance. The top view shows 610mm clearances on both sides. A 1000mm clearance is indicated below the unit for the condensate drain.

A minimum clearance of 1000 mm must be maintained at the front to ensure unobstructed airflow from the exhaust fans. Side clearances are necessary for maintenance, such as removing immersion heaters. The unit should be placed on a base of at least 100 mm, with a suitable metal base available from Lochinvar (item number LV337941).

Airflow

The Amicus Aquastore requires a continuous airflow of 2275 m³/h across the evaporator. Insufficient airflow, indicated by the plantroom air temperature dropping by more than 8°C, requires increased ventilation. Drawing air from an indoor space enhances seasonal efficiency. If the unit is in a plantroom, ventilation should be calculated as per Table 3, with inlet and exhaust air louvers provided as shown in 'Drawing 4 airflow requirements'.

Diagram Description: 'Drawing 4 airflow requirements' depicts a plantroom with louvred doors, illustrating the need for air intake and exhaust.

Diagram Description: A photograph shows a Lochinvar Amicus Aquastore unit installed in a plantroom, connected to plumbing.

Table 3: Airflow calculations based on an ambient air temperature of 10°C
V (room volume in m³) Ventilation required [m³/h] Minimum plant room temperature (°C)
10 ~250 0
50 ~750 0
100 ~1500 0
200 ~2000 5
300 ~2500 5
500 ~2500 6
1000 ~2500 7

Key to chart: V = room volume in m³. Bottom numbers indicate minimum plant room temperature. Left-hand numbers indicate ventilation required in m³/hr.

Example airflow calculation 1: For a plantroom of 7m x 6m x 2.5m (105 m³), if the temperature should not drop below 5°C, 2000 m³/hr of air into and exhaust from the plant room is required.

Example airflow calculation 2: For a warehouse space of 40m x 25m x 6m (6000 m³), additional ventilation is not required.

Positioning Multiple Units

When installing multiple units, observe minimum distances as per Drawing 3. Airflow requirements will increase. Contact Lochinvar technical support for guidance.

Diagram Description: A graph titled 'Ventilation need [m³/h]' on the Y-axis and a scale from 0 to 18 on the X-axis. Multiple colored lines represent different room volumes (V=10 m³ to V=1000 m³), showing ventilation requirements based on room size.

Installation

Amicus Aquastore units can be installed individually or in multiples. For applications with large peak loads followed by periods of limited demand (e.g., sports facilities), a buffer vessel can be used with the Aquastore to reduce capital costs and maintain efficient hot water production without excessive use of immersion heaters. See 'Drawing 7-Aquastore with buffer vessel'.

Diagram Description: 'Drawing 5- Single Aquastore on an unvented system' shows a schematic of a single Aquastore unit connected to a DHW flow line, with cold feed and building flow lines. It includes various components like isolation valves, pumps, expansion vessels, and a T&P relief valve.

Diagram Description: 'Drawing 6- Multiple Aquastore on an unvented system' shows a schematic of two Aquastore units connected in parallel to a DHW flow line, with cold feed and building flow lines. It includes similar components as the single unit diagram.

Diagram Description: 'Drawing 7-Aquastore with buffer vessel' shows a schematic of an Aquastore unit connected to a buffer vessel, with cold feed and building flow lines, and a DHW flow line.

Drawings Master Key
Number Description
1 Isolation Valve
2 Pressure Reducing Valve
3 Non-Return Valve
4 Lockshield Valve
5 Expansion Vessel
6 Tundish
7 Expansion Valve
8 Temperature & Pressure Relief Valve
9 Pump
10 Drain Valve
11 Tank Temperature Sensor
12 Air Separator
13 Dirt Separator
14 Plate System Separator
15 Double Check Valve
16 Automatic Air Vent
17 3 Port Valve
18 Temporary Fill Loop
19 Anti-Vibration Coupling
20 Flow Regulator/Commissioning Set
21 Plate Heat Exchanger
22 Hydraulic Kit
23 Heat Meter
24 Grundfos Flow Sensor
25 2 Port Valve
26 Solar Expansion Vessel
27 Solar Collector Sensor
28 Solar Vessel Sensor
29 High Limit Stat
30 Solar Pump Station

A suitable unvented systems kit (item number WH15A-RF) is available from Lochinvar, including a 22 mm monoblock with pressure reducing valve, non-return valve, 6 bar pressure relief valve, a 3/4" temperature and pressure relief valve, a 22 mm tundish, and a 25-litre flow-through expansion vessel with a flow-through valve.

To improve stratification, a de-stratification pump kit (item number WH9) is available from Lochinvar. This kit includes a bronze pump, gate valves, and an NRV.

Pump Specifications
Pump Type Potable
Motor Electric with integrated motor protection
Electrical Requirements 230 V / 1 Ph / 50 Hz
Enclosure Rating IP44
Thermal Class F
Temperature Class TP 110
Enclosure class IP44
Bearings Product lubricated special plain bearing
Operating Modes 3 fixed speed levels
GENERAL DATA
Pump housing Stainless steel
Impeller Composite PES/PP
Connection Type Screw end
Connection Size R1/4 inch
Maximum Pressure 10 bar
Maximum Temperature 110 °C
Weight 2.9 kg
Power Consumption speed 1 / 2 / 3 35 / 45 / 50 W
Current Draw speed 1 / 2 / 3 0.16 / 0.2 / 0.23 A
Approvals CE WEEE WRA5
DIMENSIONS
Port to port length 130 mm

Diagram Description: Two views (side and top) of a pump, showing dimensions like 75, 51, 130, 32, 102.

Electrical Connections

All models require a 3-phase supply with the following electrical requirements:

Table 4: Electrical requirements
Electric data
Power supply VAC / Ph / Hz 400 / 3 / 50
Electric input (Peak) kW 9.1 11.7 15.1
Number of backup elements - 2 2 2
Back up element power (each) kW 3 4.3 6
Backup element power (total) kW 6 8.6 12
Maximum current (L1) - heat pump A 9.6 9.6 9.6
Maximum input (L2) - back up element 1 + controls + fans A 16.9 22.5 30.0
Maximum current (L3) - back up element 2 A 13.0 18.7 26.1
Peak current A 39.5 50.8 65.7
IP-class - IPx4

A lockable isolator should be fitted near the heat pump for local isolation. A 230v plug socket should also be installed nearby for commissioning and maintenance.

Diagram Description: A table showing electrical connection phases L1, L2, L3, N, and PE (Earth).

Installation Assistance

Lochinvar offers expert assistance to designers and installers. Correct calculation of plantroom size and ventilation is crucial before commissioning. Refer to the 'Position on site' section for details.

Frequently Asked Questions

Q1: Can Aquastore be fitted outside?
A1: No, the Aquastore is not rated for outdoor installation and must be installed inside a plantroom or suitable space.
Q2: Does the Aquastore have BMS Connectivity?
A2: No, the Aquastore is a plug-and-play water heater and does not feature BMS connectivity.
Q3: What is the maximum working temperature of Aquastore?
A3: In Efficiency or Hybrid mode, the maximum water temperature is 65°C. In Power mode, using only immersion heaters, the maximum working temperature is 85°C.
Q4: Why are the clearances around the unit so large?
A4: The clearances ensure adequate airflow for operation and are essential for service and maintenance access to internal components.
Q5: Why is the Amps per phase not balanced?
A5: The Aquastore is a single-phase unit that requires a three-phase supply due to its high power demand. Each phase supplies a 230V to different parts of the heat pump, as detailed in Table 4.
Models: LAAS8-455-6, LAAS8-455-9, LAAS8-455-12, LAAS8 Series Amicus Aquastore Largest Heat Pump Water, LAAS8 Series, Amicus Aquastore Largest Heat Pump Water, Aquastore Largest Heat Pump Water, Largest Heat Pump Water, Heat Pump Water, Pump Water

File Info : application/pdf, 16 Pages, 1.60MB

PDF preview unavailable. Download the PDF instead.

Amicus Aquastore Planning guide

References

Microsoft Word for Microsoft 365

Related Documents

Preview Amicus LAHP-902WW Heat Pump Product Fiche
Product fiche detailing the technical specifications and performance data for the Amicus LAHP-902WW water-to-water heat pump, including energy efficiency, heat output, and consumption under various temperature conditions.
Preview Lochinvar WHP185R Water Source Heat Pump Water Heater Installation Manual
Comprehensive installation manual for the Lochinvar WHP185R Water Source Heat Pump Water Heater, covering safety, specifications, installation procedures, and troubleshooting for efficient commercial hot water solutions.
Preview Lochinvar Veritus Air Source Heat Pump Water Heater VAHP-Sub-02 Specifications & Features
Detailed submittal sheet and specifications for the Lochinvar Veritus Air Source Heat Pump Water Heater, including features, dimensions, performance data, and optional equipment.
Preview Lochinvar WHP125R Water Source Heat Pump Installation Manual
Installation manual for the Lochinvar WHP125R Water Source Heat Pump Water Heater, detailing specifications, installation procedures, safety guidelines, and troubleshooting for commercial applications.
Preview Lochinvar Commercial Heat Pump Water Heater 1-Year Limited Warranty
This document outlines the 1-Year Limited Warranty for Lochinvar Commercial Heat Pump Water Heaters. It details coverage, exclusions, owner responsibilities, warranty limitations, and the claim procedure. Learn about the terms and conditions to ensure proper warranty service for your Lochinvar water heater.
Preview Lochinvar Smart Electric Heat Pump Water Heater Submittal Sheet & Specifications
Technical specifications, features, and dimensions for Lochinvar Smart Electric Heat Pump Hybrid Water Heaters, including model numbers HPSA050KD DAK, HPSA065KD DAK, and HPSA080KD DAK. This document provides essential data for product selection and installation.
Preview Lochinvar Cavalier Eco Electric Storage Water Heaters: Features and Specifications
Discover the Lochinvar Cavalier Eco series of electric storage water heaters, featuring renewable technology compatibility, custom efficiency programming, zero on-site emissions, and high recovery rates for commercial and industrial use. Includes technical specifications and installation details.
Preview Lochinvar Imperium System Controller Installer Quick Guide
A comprehensive quick guide for installers on setting up and connecting the Lochinvar Imperium System Controller. This guide covers system configurations, screen navigation, safety warnings, and error codes for efficient operation of heat pump systems.