SHARP

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR SPLIT-TYPE AIR CONDITIONER

Installation Manual

Indoor unit:
-AH-XC9XV
-AH-XC12XV

Outdoor unit:
-AU-X3M21XV
-AU-X4M28XV

IMPORTANT NOTE:

Table of Contents

  1. Safety Precautions
  2. Accessories
  3. Installation Overview
  4. Installation Diagram
  5. Specifications
  6. Outdoor Unit Installation
  7. Refrigerant Piping Connection
  8. Wiring
  9. Air Evacuation
  10. Test Run
  11. Function of Automatic Wiring/Piping Correction

1 Safety Precautions

Read Safety Precautions Before Installation

Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.

WARNING: Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations.

CAUTION: Failure to observe a caution may result in injury or equipment damage.

This symbol indicates that you must never perform the action indicated.

WARNING

  1. Carefully read the Safety Precautions before installation.
  2. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
  3. Only trained and certified technicians should install, repair and service this air conditioning unit.
  4. Improper installation may result in electrical shock, short circuit, leaks, fire or other damage to the equipment and personal property. (In North America, installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.)
  5. Strictly follow the installation instructions set forth in this manual.
  6. Before you install the unit, consider strong winds, typhoons and earthquakes that might affect your unit and locate it accordingly. Failure to do so could cause the equipment to fail.
  7. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
  8. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
  9. This appliance is not intended for use by persons(including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  10. Children should be supervised to ensure that they do not play with the appliance. (IEC Standard requirement)
  11. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
  12. The appliance shall be installed in accordance with national wiring regulations.
  13. An all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
  14. The appliance disconnection must be incorporated with an all-pole disconnection device in the fixed wiring in accordance with the wiring rules.
  15. Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.
  16. Servicing shall only be performed as recommended by the equipment manufacturer.
  17. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
  18. The appliance shall be stored so as to prevent mechanical damage from occurring.
  19. Keep ventilation openings clear of obstruction.
  20. Do not turn on the power until all work has been completed.
  21. When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit.
  22. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.
  23. Removal of the plug has to be such that an operator can check from any of the points to which he has access that the plug remains removed.
  24. If this is not possible, due to the construction of the appliance or its installation, a disconnection with a locking system in the isolated position shall be provided.

CAUTION

Note about Fluorinated Gasses

  1. Installation, service, maintenance and repair of this unit must be performed by a certified technician.
  2. Product uninstallation and recycling must be performed by a certified technician.
  3. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more, but of less than 50 tonnes of CO2 equivalent, If the system has a leak-detection system installed, it must be checked for leaks at least every 24 months.
  4. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.

2 Accessories

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure.

Name Shape Quantity
Installation plate 1
Plastic expansion sheath 5-8 (depending on models)
Self-Tapping Screw A ST3.9X25 5-8 (depending on models)
Drain joint (some models) 1
Seal ring (some models) 1
Connecting pipe assembly Liquid side: Ø6.35
Ø9.52
Gas side: Ø9.52
Ø12.7
Ø15.9
Parts you must purchase. Consult a technician for the proper size.
Owner's manual 1
Installation manual 1
Transfer connector (packed with the indoor or outdoor unit, depending on models) Φ9.52-12.7:1 pcs

NOTE: Pipe size may differ from appliance to appliance. To meet different pipe size requirements, sometimes the pipe connections need a transfer connector installed on the outdoor unit.

Optional Accessories

There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller.

3 Installation Overview

INSTALLATION ORDER

  1. Install the outdoor unit (Page 10)
  2. Connect the refrigerant pipes (Page 14)
  3. Connect the wires (Page 18)
  4. Evacuate the refrigeration system and pipe insulation (Page 24)
  5. Perform a test run (Page 27)

4 Installation Diagram

Safety Precautions

CAUTION

NOTE: The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas.

5 Specifications

Table 5.1

Connected units
Number of units that can be used together - AU-X3M28XV = 3 units (Max)
- AU-X4M28XV = 4 units (Max)
Compressor stop/start frequency Stop time: 3 min or more
Power source voltage voltage fluctuation: within ±10% of rated voltage
voltage drop during start: within ±15% of rated voltage
interval unbalance: within ±3% of rated voltage

Table 5.2

1 drive 2 1 drive 3 1 drive 4
Max. length for all rooms 40/131 60/197 80/262
Max. length for one indoor unit 25/82 30/98 35/115
Max. height different between indoor and outdoor unit 15/49 15/49 15/49
Max. height different between indoor units 10/33 10/33 10/33

When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements illustrated in the following diagram:

Outdoor unit

Indoor unit Max.Height difference

Indoor unit 15m(49ft)

10m(32.8ft)

Indoor unit 15m(49ft)

6 Outdoor Unit Installation

Outdoor Unit Installation Instructions

Step 1: Select installation location.

The outdoor unit should be installed in the location that meets the following requirements:

Step 2: Install outdoor unit.

Fix the outdoor unit with anchor bolts (M10)

CAUTION

Split Type Outdoor Unit

(Refer to Fig 6.4, 6.5, 6.6, 6.10 and Table 6.1)

Table 6.1: Length Specifications of Split Type Outdoor Unit (unit: mm/inch)

Outdoor Unit Dimensions W x H x D Mounting Dimensions
Distance A Distance B
845x702x363 (33.27x27.6x14.3) 540 (21.26) 350 (13.8)

Table 6.2 The relations between H, A and L are as follows.

L A
L ≤ 1/2H 25 cm / 9.8" or more
1/2H < L ≤ H 30 cm/11.8" or more
L > H Can not be installed

Notes On Drilling Hole In Wall

You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.

  1. Determine the location of the wall hole based on the location of the outdoor unit.
  2. Using a 65-mm (2.5") core drill, drill a hole in the wall.

NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

  1. Place the protective wall cuff in the hole. This protects the edges of the hole and helps seal it when you finish the installation process.

Table 6.3: Connective pipe size of an A and B system (unit: inch)

Indoor Unit capacity (Btu/h) Liquid Gas
9K/12K 1/4 3/8

Drain Joint Installation

If the drain joint comes with a rubber seal (see Fig. 6.9 - A ), do the following:

  1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
  2. Insert the drain joint into the hole in the base pan of the unit.
  3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
  4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

If the drain joint doesn't come with a rubber seal (see Fig. 6.9 - B), do the following:

  1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
  2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

NOTE: Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard.

7 Refrigerant Piping Connection

Safety Precautions

WARNING

Refrigerant Piping Connection Instructions

CAUTION

Step1: Cut pipes

When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.

  1. Measure the distance between the indoor and outdoor units.
  2. Using a pipe cutter, cut the pipe a little longer than the measured distance.

CAUTION

DO NOT deform pipe while cutting. Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.

  1. Make sure that the pipe is cut at a perfect 90° angle. Refer to Fig. 7.1 for examples of bad cuts.

Step 2: Remove burrs.

Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.

  1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
  2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight seal.

  1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
  2. Sheath the pipe with insulating material.
  3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can't put them on or change their direction after flaring. See Fig. 7.3
  4. Remove PVC tape from ends of pipe when ready to perform flaring work.
  5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
  6. Place flaring tool onto the form.
  7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 7.1.
  8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.

Table 7.1: PIPING EXTENSION BEYOND FLARE FORM

Pipe gauge Tightening torque Flare dimension (A) (Unit: mm/Inch) Flare shape
Ø 6.4 18-20 N.m (183-204 kgf.cm) Min. 8.4/0.33 Max. 8.7/0.34 90 ±4
Ø 9.5 Min. 13.2/0.52 Max. 13.5/0.53
Ø12.7 Min. 16.2/0.64 Max. 16.5/0.65
Ø 15.9 25-26 N.m (255-265 kgf.cm) Min. 19.2/0.76 Max. 19.7/0.78
Ø 19.1 35-36 N.m (357-367 kgf.cm) Min. 23.2/0.91 Max. 23.7/0.93 R0.4~0.8
Ø 22 45-47 N.m (459-480 kgf.cm) Min. 26.4/1.04 Max. 26.9/1.06

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high-pressure pipe.

  1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
  2. Align the center of the two pipes that you will connect.
  3. Tighten the flare nut as tightly as possible by hand.
  4. Using a spanner, grip the nut on the unit tubing.
  5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in table 7.1.

CAUTION

NOTE ON MINIMUM BEND RADIUS

Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.

NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.

  1. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.

NOTE: DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.

  1. Thread this pipeline through the wall and connect it to the outdoor unit.
  2. Insulate all the piping, including the valves of the outdoor unit.
  3. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.

CAUTION

Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).

8 Wiring

Safety Precautions

CAUTION

Follow these instructions to prevent distortion when the compressor starts:

TAKE NOTE OF FUSE SPECIFICATIONS

The air conditioner's circuit board(PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board, such as:

Outdoor unit: T20A/250VAC(for <24000Btu/h unit), T30A/250VAC(for >24000Btu/h unit)

NOTE: The fuse is made of ceramic.

Outdoor Unit Wiring

WARNING

Before performing any electrical or wiring work, turn off the main power to the system.

  1. Prepare the cable for connection
    1. You must first choose the right cable size before preparing it for connection. Be sure to use H07RN-F cables.

Table 8.1: Minimum Cross-Sectional Area of Power and Signal Cables North America

Rated Current of Appliance (A) AWG
≤7 18
7 - 13 16
13 - 18 14
18 - 25 12
25 - 30 10

Table 8.2: Other Regions

Rated Current of Appliance (A) Nominal Cross-Sectional Area (mm²)
≤6 0.75
6 - 10 1
10 - 16 1.5
16 - 25 2.5
25 - 32 4
32 - 45 6
  1. Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts.
  2. Reinstall the cover of the electric control box.

Wiring Figure

CAUTION

Connect the connective cables to the terminals, as identified, with their matching numbers on the terminal block of the indoor and outdoor units. For example, in the US models shown in the following diagram, Terminal L1(A) of the outdoor unit must connect with terminal L1 on the indoor unit.

NOTE: Refer to the following figures if end users wish to perform their own wiring. Run the main power cord through the lower line-outlet of the cord clamp. This symbol indicates field wiring.

One-three models:

One-four models:

CAUTION

After confirmation of the above conditions, follow these guidelines when performing wiring:

NOTE: To satisfy the EMC compulsory regulations, which is required by the international standard CISPR 14-1:2005/A2:2011 in specific countries or districts, please make sure you apply the correct magnetic rings on your equipment according to the wiring diagram that adhere to the your equipment. Please contact your distributor or installer to get further information and purchase magnetic rings (The supplier of magnetic ring is TDK (model ZCAT3035-1330) or similar).

9 Air Evacuation

Safety Precautions

CAUTION

Evacuation Instructions

Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know how to use them properly.

OPEN VALVE STEMS GENTLY

When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT try to force the valve to open further.

  1. Connect the manifold gauge's charge hose to the service port on the outdoor unit's low pressure valve.
  2. Connect the middle charge hose of manifold gauge to the vacuum pump.
  3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.
  4. Turn on the vacuum pump to evacuate the system.

NOTE: If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.

  1. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system, then close the valve after 5 seconds.
  1. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. It should read slightly higher than the atmospheric pressure.
  2. Remove the charge hose from the service port.
  3. Using hexagonal wrench, fully open both the high pressure and low pressure valves.
  4. Tighten valve caps by hand, then tighten it using the proper tool.
  5. If the outdoor unit uses all vacuum valves, and the vacuum position is at the main valve, the system is not connected with the indoor unit. The valve must be tightened with a screw nut. Check for gas leaks before operation to prevent leakage.

Note On Adding Refrigerant

CAUTION

N=2(one-twin models), N=3(one-three models), N=4(one-four models), N=5(one-five models). Depending on the length of connective piping or the pressure of the evacuated system, you made need to add refrigerant. Refer to table below for refrigerant amounts to be added:

ADDITIONAL REFRIGERANT PER PIPE LENGTH

Connective Pipe Length(m) Air Purging Method Additional Refrigerant
Pre-charge pipe length (ft/m) (pre-charge pipe length xN) Vacuum Pump N/A
More than (pre-charge pipe length xN) ft/m Vacuum Pump Liquid Side: Ø 6.35 (Ø 1/4") R410A (Total pipe length - pre-charge pipe length xN) x15g/m (Total pipe length - pre-charge pipe length xN) x0.16oZ/ft Liquid Side: Ø 9.52 (Ø 3/8") R410A (Total pipe length - pre-charge pipe length xN) x35g/m (Total pipe length - pre-charge pipe length xN) x0.32oZ/ft

Note: The pre-charge pipe length is 7.5m (24.6′).

Safety And Leakage Check

Electrical safety check

Perform the electrical safety check after completing installation. Cover the following areas:

  1. Insulated resistance: The insulated resistance must be more than 2M.
  2. Grounding work: After finishing grounding work, measure the grounding resistance by visual detection and using the grounding resistance tester. Make sure the grounding resistance is less than 4.
  3. Electrical leakage check (performing during test while unit is on): During a test operation after completed installation, use the electroprobe and multimeter to perform an electrical leakage check. Turn off the unit immediately if leakage happens. Try and evaluate different solutions until the unit operates properly.

Gas leak check

  1. Soap water method: Apply a soap-water solution or a liquid neutral detergent on the indoor unit connection or outdoor unit connections with a soft brush to check for leakage of the connecting points of the piping. If bubbles emerge, the pipes are experiencing leakage.
  2. Leak detector: Use the leak detector to check for leakage.

NOTE: The illustration is for example purposes only. The actual order of A, B, C, D, and E on the machine may be slightly different from the unit you purchased but the general shape will remain the same.

10 Test Run

Before Test Run

A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:

CAUTION

Failure to perform the test run may result in unit damage, property damage or personal injury.

Test Run Instructions

  1. Open both the liquid and gas stop valves.
  2. Turn on the main power switch and allow the unit to warm up.
  3. Set the air conditioner to COOL mode.
  4. For the Indoor Unit
    1. Ensure the remote control and its buttons work properly.
    2. Ensure the louvers move properly and can be changed using the remote control.
    3. Double check to see if the room temperature is being registered correctly.
    4. Ensure the indicators on the remote control and the display panel on the indoor unit work properly.
    5. Ensure the manual buttons on the indoor unit works properly.
    6. Check to see that the drainage system is unimpeded and draining smoothly.
    7. Ensure there is no vibration or abnormal noise during operation.
  5. For the Outdoor Unit
    1. Check to see if the refrigeration system is leaking.
    2. Make sure there is no vibration or abnormal noise during operation.
    3. Ensure the wind, noise, and water generated by the unit do not disturb your neighbors or pose a safety hazard.

NOTE: If the unit malfunctions or does not operate according to your expectations, please refer to the Troubleshooting section of the Owner's Manual before calling customer service.

11 Function of Automatic Wiring/Piping Correction

Automatic Wiring/Piping Correction Function

More recent models now feature automatic correction of wiring/piping errors. Press the "check switch" on the outdoor unit PCB board for 5 seconds until the LED displays "CE", indicating that this function is working. Approximately 5-10 minutes after the switch is pressed, the "CE" disappears, meaning that the wiring/piping error is corrected and all wiring/piping is properly connected.

How To Activate This Function

  1. Check that outside temperature is above 5 ℃. (This function does not work when outside temperature is not above 5 °C)
  2. Check that the stop valves of the liquid pipe and gas pipe are open.
  3. Turn on the breaker and wait at least 2 minutes.
  4. Press the check switch on the outdoor PCB board unit LED display "C E".

SHARP CORPORATION

The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details. Any updates to the manual will be uploaded to the service website, please check for the latest version.

Models: Air Conditioner, AH-XC9XV, AU-X3M21XV, AH-XC12XV, AU-X4M28XV

File Info : application/pdf, 27 Pages, 9.17MB

PDF preview unavailable. Download the PDF instead.

ODU - Installation Manual Adobe PDF library 10.01 Adobe Illustrator CS6 (Windows)

Related Documents

Preview Sharp Air Conditioner Owner's Manual - AH-XC9XV, AH-XC12XV, AU-X3M21XV, AU-X4M28XV
Owner's manual for Sharp Inverter One-Two/One-Three/One-Four Split-Type Air Conditioners, covering safety precautions, unit parts, functions, operation, maintenance, and troubleshooting for models AH-XC9XV, AH-XC12XV, AU-X3M21XV, and AU-X4M28XV.
Preview Sharp Air Conditioner Remote Controller Manual
A comprehensive guide to the Sharp air conditioner remote controller, detailing its functions, indicators, and operation for various modes like COOL, AUTO, DRY, and FAN. Includes instructions for advanced features such as SLEEP, TURBO, SELF CLEAN, LOCK, FOLLOW ME, SILENCE, and TIMER functions.
Preview Sharp Room Air Conditioner User Manual
This user manual provides instructions for the Sharp Room Air Conditioner models AC-225FD, AC-255FD, and AC-285FD. It covers installation, operation, maintenance, troubleshooting, and safety precautions.
Preview Sharp AE-X3M24BU Split Type Air Conditioner Outdoor Unit Installation Manual
Installation manual for the Sharp AE-X3M24BU split type air conditioner outdoor unit, detailing safety precautions, piping, electrical connections, and operational checks.
Preview Sharp Split Type Air Conditioner Owner's Manual & Installation Guide
Comprehensive guide for Sharp Split Type Air Conditioners (Models AY-X9XEJ, AE-X9XEJ, AY-X12XEJ, AE-X12XEJ) covering operation, installation, maintenance, and troubleshooting.
Preview Sharp Air Conditioner Maintenance Guide
A comprehensive guide to maintaining your Sharp air conditioner, including cleaning the air filter, the unit, and the remote control, with seasonal maintenance tips.
Preview Sharp Room Air Conditioner Installation and Operation Manual (AF-S60RX, AF-S80RX, AF-S85RX)
This manual provides comprehensive instructions for the installation, operation, and maintenance of Sharp Room Air Conditioners, models AF-S60RX, AF-S80RX, and AF-S85RX. It covers safety precautions, installation steps, operating modes, remote control usage, cleaning procedures, and troubleshooting tips.
Preview Sharp FP-J30J Air Purifier Operation Manual
Comprehensive operation manual for the Sharp FP-J30J Air Purifier, detailing its features, installation, operation, maintenance, troubleshooting, specifications, and warranty information.