PolyGard®2 DT6 Digital Gas Transmitters

User Manual

Serial No. SB-03

Version February 2020

Intended Use

The PolyGard®2 DT6 are designed for the detection of toxic, combustible or dangerous atmosphere in many commercial and industrial applications in connection with the Gas Controller System DGC6. The intended sites are all areas being directly connected to the public low voltage supply, e.g. residential, commercial and industrial environments as well as small enterprises (according to EN 50 082). The PolyGard®2 Series must not be used in potentially explosive atmospheres. The sensor must only be employed in areas within the environmental conditions specified in the Technical Data.

1 Functional Description

1.1 General

The Sensor consists of the two components DT6 Basic Sensor Board (BSB) and SC2 Sensor Cartridge (SC). The Sensor Cartridge contains a µController for signal processing besides the sensor element and the measuring amplifier. All data and measured values of the sensor element are stored fail-safe in the µController and transferred digitally via the local bus to the DT6 Basic Sensor Board. The calibration management is also integrated in the µController of the SC2 Sensor Cartridge.

The DT6 Basic Sensor Board has got three local bus interfaces for connection of up to three Sensor Cartridges and a field bus interface (RS-485) for communication with the DGC6 Gas Controller. The DT6 Basic Sensor Board is integrated in the system as a slave with its basic address. The addressing on the field bus level as well as the registration and assignment of the Sensor Cartridge on the local bus level is done via the STL6 Service Tool or with the DPT6 EasyConfig Software, which is directly connected to the BSB.

The cable topology for the RS-485 field bus can be taken from the “Guidelines for wiring and commissioning of the DGC6 hardware".

1.2 Measuring Mode

The sensor element continuously monitors the ambient air to detect an existing gas concentration and transmits a measurement signal which is proportional to the gas concentration via the amplifier directly to the AD converter of the µController. The µController checks the measurement signal for plausibility (within defined measuring, temperature and voltage ranges, etc.), calculates the average and sends both values with the attributes gas type and unit via the local bus to the µController of the DT6 Basic Sensor Board. The BSB (slave) sends the data of the registered Sensor Cartridge upon polling request to the DGC6 Controller (master).

1.3 Special Mode

If a fault occurs (measurement signal, temperature or operating voltage outside the defined range, communication error on local bus) or when the DT6 Basic Sensor Board is in the maintenance/calibration mode, the measurement operation is interrupted and the status of "special mode" is sent to the DGC6 Controller.

The integrated measuring amplifier converts this change in resistance into a linear output signal. The continuous combustion leads by-and-by to a loss of sensitivity that can be compensated by performing regular calibration of zero and gain. See section 4.4.

2 Installation

Electronics can be destroyed by electrostatic discharge (ESD). Therefore, the installation work should be done only by persons connected to ground, e. g. with a wrist strap connected to ground or by standing on a conductive floor (acc. to DIN EN 100015).

2.1 Mounting Instructions

The housing with the Basic or Remote Sensor Board comes in closed state. Therefore, before mounting, break out the pre-embossed knockouts to insert the cable entries and the Sensor Cartridge(s). The housing offers different mounting options by a variety of knockout openings depending on the number and types of Sensor Cartridge(s).

Prior to breaking out the knockouts it is essential to determine the exact position and size of the Sensor Cartridge(s) and cable entries with reference to the drawings "mounting options and knockouts in the enclosure", fig. 3 and 4.

When choosing the mounting site please pay attention to the following:

2.2 Installation Work

3 Electrical Connection

3.1 Wire Connection

Connecting the 24 V field bus voltage to the local bus terminal X7 can destroy the DT6 Basic Sensor Board completely!

4 Commissioning

Only trained technicians should perform the following when commissioning:

Required instruments for commissioning (calibration):

4.1 Installation of Sensor Cartridge

The Sensor Cartridge is supplied in a separate package and should be installed on the housing only during commissioning to protect it against dirt and damage.

4.2 Addressing

A basic communication address is assigned to the DT6 board with the help of the STL6 Service Tool or the DPT6 EasyConfig Software. Using this basic address, the data of the Sensor Cartridge assigned to input 1 are sent via the field bus to the gas controller. Any further SC connected / registered on the printed circuit board automatically gets the next address.

4.3 Registration / Assignment of the Sensor Cartridge(s) (SC)

The DT6 recognizes automatically the SC(s) physically connected to it (unimportant whether directly on the DT6 or on the remote DR6) via the gas type and the measuring range which are factory-integrated in the SC address bit. By selecting the signal type, analog or bus, the input is activated. In the second step by assigning the gas type and defining the measurement range, the SC is connected to the input.

Up to two different SC can be connected at the DT6, with a third to an attached remote DR6. The physical position of the SC does not have to agree with the input in the menu.

Example: DT6 with three SCs for CO, NO2 and C3H4 with basic address 09

Input Mode Field Bus Address Gas Type Measuring Range Result
1 SC DP 09 CO 300 ppm CO SC assigned to input 1 und thus field bus address DP09
2 SC DP 10 NO2 30 ppm NO2 SC assigned to input 2 und thus field bus address DP10
3 SC DP 11 C3H4 100% UEG C3H4 SC assigned to input 3 und thus field bus address DP11

Only the parameters with blue background have to be worked on for the BSB addressing and the SC registration.

Mode: Not active: = SC assignment to input not possible; SC: = SC assignment possible; Analog: = Input with 4-20 mA signal, assignment possible

Gas type and meas. range: Selection of gas type and measuring range of the SC connected to the input or of the analog sensor

The registration is only accepted if the assigned gas type/measuring range are identic in the BSB and in the SC. Gas type and measuring range of the BSB are checked for identity by the GC Controller, too.

Only one SC per gas type must be connected to the same DT6 Basic Sensor Board. Two SC2 sensor heads of the same gas group (Freons) must not be connected.

4.4 Calibration

The STL6 service tool or DPT6 EasyConfig Software are available for convenient on-site calibration. There is also the possibility to exchange the SC against a calibrated SC on site. The used SC can then be calibrated directly in the office or at INTEC Controls and then reused.

Prior to calibration the Sensor Cartridge must be supplied with power voltage without interruption for warm-up and stabilisation. The warm-up time depends on the sensor element and is shown in the following table for Example: See also User Manual for Sensor Cartridge.

Sensor Cartridge Warm-up for calibration (h) Stabilization time to specification (min) Flow rate (ml/min)
CO 24 60 500
NO2 24 60 500
LPG (C3H4) 24 60 150

Table Calibration

Please observe proper handling procedures for compressed gas and test gas bottles (regulations TRGS 220)! Test gas can be toxic, so never inhale it! Symptoms: Dizziness, headache and nausea. Procedure if exposed: Remove victim to fresh air, seek medical attention.

4.5 Calibration with DPT6 EasyConfig Software

Zero calibration

With a zero reading> 10% of measuring range during the zero calibration, zero calibration is not possible.

Gain calibration

By limiting the gain factor, calibration will not be possible anymore when the sensitivity of the sensor reaches a residual sensitivity of 40 %. Then the Sensor Cartridge has to be replaced. For more information, see the user manual of the DPT6 EasyConfig Software.

4.6 Exchange of Sensor Cartridge

Instead of the on-site calibration, the used SC can be easily and conveniently replaced by a calibrated one.

The local bus communication is automatically established and tested. At the same time the gas type and the measuring range of the "new" SC are compared with the data stored in the BSB. If they match and the communication is correct, the error message will be automatically acknowledged at the Gas Controller.

The yellow LED of the BSB flashes with a pulse duration of 1 sec., while the SC connector is disconnected (communication error). After the local bus communication has been re-established and the conformity test has been successful, the LED will go into flashing mode with 3 sec. pulse duration.

The sensor element is treated with a defined gas concentration with the help of the gas generator. As a result the measurement signal acknowledges the LED when an internal switching threshold is reached. With this test, the complete function chain “Sensor Element > Sensor Cartridge> Local Bus> BSB> Field Bus> GC Controller" is tested.

5 Inspection and Service

Regular maintenance and calibration of the sensors by trained technicians is recommend. See SC2 datasheet for requirements.

According to EN 45544-4, inspection and service has to be executed at regular intervals. The maximum intervals have to be determined and observed by the person responsible for the gas warning system according to the legal requirements. Inspection and maintenance intervals as prescribed in the general regulations of the gas measuring technique like VDI-2053, EN 60079-29-1 etc. The inspection interval normally is three months. The recommended service intervals are depended from the connected Sensor Cartridges. If different intervals are valid, always consider the shortest one.

Inspections and services must be documented. The date for the next maintenance has to be affixed to the sensor.

5.1 Inspection

Gas sensors should be controlled regularly by a competent person according to EN 45544-4. The following has to be checked in particular:

5.2 Service and Calibration

When performing the maintenance, you have to do the calibration and the functional test in addition to the inspection. See section 4.

6 Troubleshooting

6.1 DT6 Basic Sensor Board

Trouble Cause Solution
Green LED isn't on. Power voltage not applied Measure tension at X4: (16-28 V DC) Pin 1 (+) and 2 (-) Connect correctly.
Polarity not correct at X4 Check the plug.
Connector X4 not plugged in Check the wiring.
Wire breakage Check BSB address, address correctly.
Green LED doesn't flash. BSB hasn't got any address. Check field bus wiring, topology and termination.
BSB: no field bus communication Check SC plug.
SC not or wrongly plugged in Register SC.
SC not registered Check SC data<> registration data for conformity.
No measured value at the Tool or Controller SC gas type/measuring range doesn't match with registered ones. Replace BSB.
Message at the Tool / Controller: 24 V DC voltage <range> 5 V DC voltage <range> Temp. <range> WatchDog triggered Internal error Replace SC.

6.2 Sensor Cartridge (Messages at the Tool/Controller)

Measuring signal <range> 5 V DC voltage < range > Temp. < range > WatchDog triggered. Cause Solution
Internal error Replace SC.
SC Input 1 ≠ stored type Wrong SC type at input 1 Check SC at input 1, replace it.
SC Input 2 ≠ stored type Wrong SC type at input 2 Check SC at input 2, replace it.
SC Input 3 ≠ stored type Wrong SC type at input 3 Check SC at input 3, replace it.

7 Technical Data

Electrical

Sensors

Serial interface

Physical

Dimensions (H x W x D)

Certified to

UL 2075 Listed, NRTL performance tested for models DT6-E1110-E-02, DT6-E1110-E-E1130-B-02, DT6-E1110-E-E1130-B-32

Note: SC2 infrared sensors are incompatible with the DR6 module

Conforms to

EMC Directive 2014/30/EU CE EN 50271, EN 61010-1:2010 ANSI/UL 61010-1 CAN/CSA-C22.2 No. 61010-1 City of Los Angeles

Warranty

Two years material and workmanship, 12 months normal exposure for sensor element

OPTIONS & ACCESSORIES

Horn & Status LED

Configurable to local thresholds set at this unit > 85 dB (A) (dist. 0.1 m / 0.3 ft) 2300 Hz NEMA 4X (IP65)

Red = Alarm NEMA 4X (IP65)

PG2-DUCTKIT

Min. 3.1 mph (5000 m/h), max. 12.4 mph (20,000 m/h) Min. 3.94 in. (0.1 m), max. 39.37 in. (1.0 m) 9.84 in. (250 mm), adaptable 2 x 39.37 in. (1000 mm)

Calibration Kits

8 Figures

Fig 1: Electrical connection of field bus and optional local bus

Diagram showing the electrical connections for the field bus and optional local bus for the DT6 Basic Sensor Board and DR6 Remote Sensor Board.

Fig 2: Basic Sensor Board with Sensor Cartridge and with option Remote Sensor Board

Diagram illustrating the physical connection of the Basic Sensor Board with a Sensor Cartridge and an optional Remote Sensor Board.

Fig 3: Mounting possibilities

Diagrams showing various mounting configurations for the Basic Sensor Board and Remote Sensor Board with different cable entries (M12, M20, M25).

Fig. 4 Housing knockouts

Diagram illustrating the knockout openings on the housing for cable entries.

Fig. 5 Housing dimensions

Diagram showing the dimensions of the DT6 housing, including mounting points and cable entry locations.

Fig. 6 Calibration adapter

Image of a calibration adapter used for the sensor calibration process.

9 Part Disposal

Since August 2005 there are EC-wide directives defined in the EC Directive 2002/96/EC and in national codes concerning the waste electrical and electronic equipment also regarding this device.

For private households there are special collecting and recycling possibilities. For this device isn't registered for the use in private households, it mustn't be disposed this way. You can send it back to your national sales organisation for disposal. If there are any questions concerning disposal, please contact your national sales organisation.

Outside the EC, you have to consider the corresponding directives.

10 Notes and General Information

It is important to read this user manual thoroughly and clearly in order to understand the information and instructions. The PolyGard®2 devices must be used within product specification capabilities. The appropriate operating and maintenance instructions and recommendations must be followed.

Due to on-going product development, INTEC Controls and MSR-Electronic GmbH reserves the right to change specifications without notice. The information contained herein is based upon data considered to be accurate. However, no guarantee is expressed or implied regarding the accuracy of these data.

10.1 Intended Product Application

The PolyGard®2 devices are designed and manufactured for control applications and air quality compliance in commercial buildings and manufacturing plants.

10.2 Installers' Responsibilities

It is the installer's responsibility to ensure that all PolyGard®2 devices are installed in compliance with all national and local codes and OSHA requirements. Installation should be implemented only by technicians familiar with proper installation techniques and with codes, standards and proper safety procedures for control installations and the latest edition of the National Electrical Code (ANSI/NFPA70).

The equipotential bonding required (also e.g. secondary potential to earth) or grounding measures must be carried out in accordance with the respective project requirements. It is important to ensure that no ground loops are formed to avoid unwanted interference in the electronic measuring equipment.

It is also essential to follow strictly all instructions as provided in the user manual.

10.3 Maintenance

It is recommended checking the PolyGard®2 device regularly. Due to regular maintenance any performance deviations may easily be corrected. Re-calibration and part replacement in the field may be implemented by a qualified technician and with the appropriate tools. Alternatively, the easily removable plug-in Sensor Cartridge with the sensor element may be returned for service to INTEC Controls.

10.4 Limited Warranty

INTEC Controls and MSR-Electronic GmbH warrants the PolyGard®2 devices for a period of two (2) year from the date of shipment against defects in material or workmanship; 12 months for sensor elements operating within normal exposures. Should any evidence of defects in material or workmanship occur during the warranty period, INTEC Controls will repair or replace the product at their own discretion, without charge. A preauthorized RMA number is required for returns.

This warranty does not apply to units that have been altered, had attempted repair, or been subject to abuse, accidental or otherwise. The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned. The above warranty is in lieu of all other express warranties, obligations or liabilities.

This warranty applies only to the PolyGard®2 devices. INTEC Controls and MSR-Electronic GmbH shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard®2 devices.

Models: PolyGard-2 DT6, PolyGard-2 DT6 Digital Gas Transmitters, Digital Gas Transmitters, Gas Transmitters, Transmitters

File Info : application/pdf, 15 Pages, 712.40KB

PDF preview unavailable. Download the PDF instead.

DT6 UserManual

References

Adobe PDF Library 17.0