MGC SGM-1004S: 4 NAC Output Module with Built-in Synchronization

Description

The SGM-1004S Module is compatible with MGC fire alarm control panels including the FA-1000, FX-2000 Series, FleX-Net FX-2000N Series, FleX-Net FX-4000N Series, and FX-MNS-6000. It provides up to 4 Class A or B (Style Z or Y) Indicating Circuits, enabling synchronized NAC circuits. This offers flexibility and cost savings by increasing the number of synchronized NAC circuits per panel and reducing the need for separate sync modules and wiring.

Each of the four indicating circuits is rated at Regulated 24 VDC/FWR with a maximum of 1.7 Amps per circuit (5 Amps maximum per SGM-1004S). For special applications, it is rated at 33 VDC/FWR with a maximum of 2.1 Amps per circuit (5 Amps maximum per SGM-1004S). Circuits can be configured as Non-Silenceable (Steady) or Silenceable. Each circuit includes an individual trouble indicator and is power limited for use with limited energy cable. The SGM-1004S also features terminals for a suite isolator option (part number CSIS-202A1).

Features

Applications

The SGM-1004S allows compatible fire alarm control panels to have synchronized NAC circuits. The maximum number of synchronized NAC circuits is determined by the panel's capacity for hosting adder modules. The module provides flexibility and cost savings by increasing the number of synchronized NAC circuits per panel while reducing the quantity of sync modules and wiring required.

Installation

The SGM-1004S consists of a PC board that mounts at the bottom of the chassis. The PC board connects via cables to the main chassis board. Labels are provided with each chassis. Removable terminal blocks facilitate easy connection of field wiring and servicing.

Technical Specifications

NAC Rating Power limited where applicable:
24 VDC/FWR regulated max. 1.7 A @49 °C per NAC circuit max. 5 A per SGM-1004S

Special application:
Max. voltage 33 VDC/FWR max. 2.1 A @49 °C per NAC circuit max. 5 A per SGM-1004S.
See LT-6734 for details
Standby Current 31 mA
Alarm Current (unloaded) 96 mA
End of Line Resistor 3.9K ohm ±5% per circuit
Operating Temperature Range 32°F to 120°F (0°C to 49°C)
Humidity Range 10% to 93% non-condensing

Wiring Diagram

The diagram illustrates the typical wiring for the SGM-1004S NAC Board. It shows four NAC outputs (NAC 1, NAC 2, NAC 3, NAC 4), each connectable to supervised NAC circuits. NAC 1 and NAC 3 are shown configured for CLASS B wiring, while NAC 2 and NAC 4 are configured for CLASS A wiring. The legend indicates that the wiring is for BELL, HORN OR STROBE devices, using a 3.9K 1/2W ELR (End of Line Resistor) as specified by S5434, Model MP-300, manufactured by Mircom.

Ordering Information

Model Description
SGM-1004S 4 NAC Output module with built-in synchronization

Manufacturer Information

Canada:
MGC
25 Interchange Way Vaughan, ON L4K 5W3
Telephone: (905) 660-4655 | Fax: (905) 660-4113

U.S.A.:
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: (888) 660-4655 | Fax Toll Free: (888) 660-4113

Website: www.mircom.com

This document is provided by Mircom Technologies Ltd., MGC Systems Corp., or their affiliates, subsidiaries and brands, for convenience or marketing only and does not describe products or services technically. For technical information refer to technical manuals. Mircom does not make representations or warranties regarding this information, including as to completeness or accuracy. Mircom may change these contents at any time and reserves all rights in the contents, including copyrights, trademarks and other intellectual property.

Catalog Number: 9530

Revision: 1

PDF preview unavailable. Download the PDF instead.

CAT-9530 SGM-1004S Four NAC Output Module Adobe PDF Library 17.0 Adobe InDesign 18.5 (Macintosh)

Related Documents

Preview MGC ANC-6000 Audio Network Controller Board Installation Instructions
Installation instructions for the MGC ANC-6000 Audio Network Controller Board, detailing module mounting, board layout, DIP switch configuration for addressing, and wiring for audio sources and paging microphones. Includes diagrams and technical specifications for system integration.
Preview RB-MAM-3500 Replacement Main Display Installation Instructions for FX-3500 Fire Alarm Control Panel
This document provides instructions for installing the RB-MAM-3500 Replacement Main Display kit for the FX-3500 Fire Alarm Control Panel. It includes a parts list and step-by-step guidance for powering down the system, replacing the display, and powering the system back up.
Preview MGC RA-1000 Series Remote Multiplex Annunciator Panels Installation and Wiring Manual
This manual provides installation and wiring instructions for the MGC RA-1000 Series Remote Multiplex Annunciator Panels, including details on mechanical installation, wiring, DIP switch settings, and specifications.
Preview RAXN-LCDG Network Remote Graphic Annunciator Installation and Wiring Manual
Installation and wiring manual for the MGC RAXN-LCDG Network Remote Graphic Annunciator. This document provides detailed instructions for installation, configuration, wiring, and specifications of the device.
Preview MGC RAXN-UB-BRACKET Installation Instructions: Module Mounting Bracket
Installation guide for the MGC RAXN-UB-BRACKET module mounting bracket, detailing kit contents and assembly steps for mounting the RAXN-4000LCDGC module onto a fire alarm enclosure's inner deadfront chassis.
Preview MGC BB-4002R and BB-4006R Multi Module Enclosures: Dimensions and Wiring Guide
Detailed dimensions, wiring diagrams, and cable routing instructions for MGC BB-4002R and BB-4006R Multi Module Enclosures, designed for MIX-4000-M Series Modules.
Preview MGC SPPS-104 Series Ceiling Speaker-Strobe Installation and Maintenance Instructions
Installation and maintenance instructions for MGC SPPS-104 Series ceiling speaker-strobes and SPP-104 Series ceiling speakers. Includes specifications, wiring diagrams, mounting instructions, and sound/light ratings.