RB-MAM-3500 Replacement Main Display for FX-3500 Fire Alarm Control Panel
The RB-MAM-3500 kit includes all necessary parts to replace a damaged MAM-3500 Main Display on an FX-3500 Fire Alarm Control Panel.
Parts List
- Qty 1: MAM-3500 Main Display
- Qty 4: #6-32 0.25” screws
- Qty 1: NP-1984 Insert sheet for labels
Installing the MAM-3500 Main Display
To install the MAM-3500, follow these steps:
- Power down the FX-3500.
- Replace the MAM-3500.
- Power up the FX-3500.
Refer to the sections below for detailed instructions.
A. Power down the FX-3500
- Disconnect the backup batteries.
- Disconnect the AC power going to the FX-3500 panel.
B. Replace the MAM-3500
- Disconnect the ribbon cable connected to P4 on the damaged MAM-3500 main display.
- Disconnect the ribbon cable connected to P2 on the damaged MAM-3500 main display.
- Remove the screws securing the MAM-3500 to the door.
- Remove the damaged MAM-3500 and replace it with the new MAM-3500.
- Attach the new MAM-3500 using the provided screws or the screws removed in step 3.
- Connect the ribbon cable from the main panel to P4 on the MAM-3500.
- Connect the ribbon cable from the adder annunciator board to P2 on the MAM-3500.
Figure 1: Locations of connectors on the MAM-3500. This diagram shows the P2 ribbon cable connector for the adder annunciator board and the P4 ribbon cable connector for the main panel on the MAM-3500 unit.
Figure 2: Location of MAM-3500 on the FX-3500 door. This illustration depicts the MAM-3500 mounted on the FX-3500 door, highlighting the securing screws and the adder annunciator boards.
C. Power up the FX-3500
- Connect the AC power to the FX-3500 panel.
- Connect the backup batteries.