MGC SPPS-104 Series Ceiling Speaker-Strobe and SPP-104 Series Ceiling Speaker Installation and Maintenance Instructions

This manual provides installation and maintenance information for MGC SPPS-104 Series ceiling speaker-strobes and SPP-104 Series ceiling speakers. It is intended as a quick reference for installation. For detailed information on using these devices with a Fire Alarm Control Panel (FACP), refer to the panel's manual.

Note: This manual should be left with the owner/operator of the equipment.

CAUTION / ATTENTION

DO NOT PAINT OR ALTER FACTORY APPLIED FINISH IN ANY WAY. NE PAS PEINDRE OU MODIFIER LA FINITION ORIGINALE.

SPEAKER/SPEAKER STROBE DESCRIPTION

The SPPS-104 speaker-strobe is designed to meet UL1480/ULC S541 requirements for speakers and UL1638 /ULC S526 requirements for visual notification appliances. The SPP-104 speaker is designed to meet UL1480/ULC S541 requirements for speakers.

FIGURE 1: MODEL FRONT

Diagram showing the front view of the SPPS-104 and SPP-104 series devices, with dimensions indicated as 180mm [7in].

SETTING THE CANDELA (SPPS series only)

The candela can be set to 15, 30, 75, 110, 125, 15/75 for SPPS-104-25 and SPPS-104-70 models. The candela can be set to 50, 75, 90, 130, 185, 15/75 for SPPS-104-25H and SPPS-104-70H models. The factory default setting is 15 for SPPS-104-25/70 models, and 50 for SPPS-104-25H/70H models.

  1. Pull out the candela selector from the device.
  2. Re-insert the selector tab into the notch that is labeled with the desired candela setting (when removing or inserting the candela selector, ensure to keep it straight).

FIGURE 2: INSERTING CANDELA SELECTOR

Diagram illustrating the process of inserting the candela selector.

SETTING THE DIP SWITCHES

FIGURE 3: DIP SWITCH

Diagram showing the DIP switch configuration with labels for SYNC, NON-SYNC, OFF, and ON.

DIP SWITCH
DIPOFFON
Switch 1 Input*SynchronizedRegulated 24VDC/ FWR (Non-sync.)

*Note: Use "SYNC” when flash synchronization is required, either through a sync module or built-in synchronization on the control unit. Use "NON-SYNC" when the appliances do not need to be synchronized.

Note: DIP switch 1 default setting is OFF, synchronized.

Note: DIP switch 2 is not used. By default it is OFF.

SPECIFICATIONS

Table 1: SPECIFICATIONS
SPPS-104 SERIES
UL Reverberant (dBA@10ft)ULC Anechoic (dBA@3m)
Operating temperature0°C to 49°C (32°F to 122°F)
Humidity range0% to 93%
Strobe flash rate1 Hz (1 flash per sec.)
Nominal strobe voltageRegulated 24VDC/VFWR*
Operating voltage range16-33 VDC/VFWR
Nominal speaker voltage25V or 70.7Vrms
Speaker Size4"
Power Setting1/4, 1/2, 1, 2 W
Speaker Frequency range400-4000 Hz
Terminal wire gauge12-22 AWG

*Note: For FWR signaling use an MGC panel.

SOUND PRESSURE LEVEL OUTPUT

Table 3: SOUND PRESSURE LEVEL OUTPUT
WATT TapSPPS-104 SERIESSPP-104 SERIES
UL Reverberant (dBA@10ft)ULC Anechoic (dBA@3m)UL Reverberant (dBA@10ft)ULC Anechoic (dBA@3m)
289.089.087.888.2
186.786.885.185.6
1/284.083.982.382.6
1/480.880.778.979.5
289.289.289.689.4
186.587.486.886.8
1/283.784.583.983.7
1/480.581.280.780.5

DIRECTIONAL SOUND CHARACTERISTICS

Table 4: DIRECTIONAL SOUND CHARACTERISTICS (Representative of both horizontal and vertical Axis)

ANGLEdBA
+40°, -43°-3
+76°, -74°-6
±90°-10.3
ANGLEdBA
+35°-3
±72°-6
±90°-10.6

STROBE RATINGS

Table 5: STROBE OPERATING RMS CURRENTS (mA)
CandelaSPPS-104 SERIESSPPS-104 H SERIES
Regulated 24VDCRegulated 24VFWRRegulated 24VDCRegulated 24VFWR
153333
304743
75111100
110204186
125295277
15/75112100
505457
757883
90100104
130159162
185343327
15/758287

LIGHT DISPERSION

Table 6: LIGHT DISPERSION

Degrees% of Candela Rating
±0114
±5111
±10106
±15100
±2094
±2590
±3087
±3582
±4078
±4577
±5077
±5576
±6075
±6563
±7043
±7533
±8036
±8541
+9039
Compound ±4578

Note: The values in Table 6 are shown as percentages of the rated light output at any candela setting.

WIRING

CAUTION

DO NOT LOOP SIGNAL CIRCUIT FIELD WIRES AROUND TERMINALS. ELECTRICAL SUPERVISION REQUIRES WIRE RUN TO BE BROKEN AT EACH END.

Diagram showing correct and incorrect wiring practices for supervision.

FIGURE 4: Figure 4 WIRING TAPS

Diagram illustrating wiring taps for speaker power selection and strobe input power.

Note: This device should be installed as per applicable requirements of the authorities having jurisdiction.

Use the information in this document to determine the total power or current of the devices. The total power or current of the devices must not exceed the output rating of the panel. Refer to the FACP installation guide for the wire size required according to the loop length and devices power usage. For maximum strobe operating current, please refer to Table 5.

FIGURE 5: DEVICE CONNECTION

Diagram showing device connection from a Fire Alarm Control Panel and to the next device, including wiring for speaker and strobe inputs.

*Note: When using with MGC panel or sync module, use MP-300 (3.9K).

Note: Wiring must be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations section 32 and NFPA 70.

CAUTION

FOR ALL TERMINAL TAPS USED FOR SYSTEM SUPERVISION, DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

ATTENTION

NE PAS UTILISER DE FILS EN BOUCLE SOUS LES BORNES. OUVRIR LA LIGNE POUR CONFIRMER LA SUPERVISION DES CONNEXIONS.

MOUNTING

MGC recommends spacing speaker strobe appliances in compliance with CAN/ULC S524 and NFPA72.

(Optional: In case of using a standard 4" square 2 1/8 deep electrical box, attach MP-184 adaptor ring from SPKC-W kit to the unit using 4 snaps.)

  1. Attach the unit to the IB-104 electrical box with the 2 included mounting screws.
  2. Rotate the top cover clockwise to snap it in place.
  3. Secure the top cover with the included securing screw and snap the nameplate over the securing screw.

FIGURE 6: MOUNTING DIAGRAM

Diagram showing the mounting steps: attaching the device to the electrical box, securing the top cover, and attaching the nameplate.

Model Numbers

  • SPPS-104-25 Ceiling mounted speaker strobe 25V white
  • SPPS-104-70 Ceiling mounted speaker strobe 70V white
  • SPPS-104-25R Ceiling mounted speaker strobe 25V red
  • SPPS-104-70R Ceiling mounted speaker strobe 70V red
  • SPPS-104-25H Ceiling mounted speaker strobe 25V with High candela white
  • SPPS-104-70H Ceiling mounted speaker strobe 70V with High candela white
  • SPPS-104-25HR Ceiling mounted speaker strobe 25V with High candela red
  • SPPS-104-70HR Ceiling mounted speaker strobe 70V with High candela red
  • SPP-104-25 Ceiling mounted speaker 25V white
  • SPP-104-70 Ceiling mounted speaker 70V white
  • SPP-104-25R Ceiling mounted speaker 25V red
  • SPP-104-70R Ceiling mounted speaker 70V red

Accessories

  • IB-104 Round backbox
  • SPKC-W Optional spacer
  • MP-300 End of line resistor 3.9k Ohm
Models: SPPS-104-25, SPPS-104-70, SPPS-104-25H, SPPS-104-70H, SPPS-104-25 Ceiling Speaker Strobe, SPPS-104-25, Ceiling Speaker Strobe, Speaker Strobe, Strobe

File Info : application/pdf, 4 Pages, 917.39KB

PDF preview unavailable. Download the PDF instead.

LT-6916-Ceiling-Speaker-Strobe-Installation

References

Acrobat Distiller 22.0 (Windows)

Related Documents

Preview RAXN-LCDG Network Remote Graphic Annunciator Installation and Wiring Manual
Installation and wiring manual for the MGC RAXN-LCDG Network Remote Graphic Annunciator. This document provides detailed instructions for installation, configuration, wiring, and specifications of the device.
Preview MGC BB-4002R and BB-4006R Multi Module Enclosures: Dimensions and Wiring Guide
Detailed dimensions, wiring diagrams, and cable routing instructions for MGC BB-4002R and BB-4006R Multi Module Enclosures, designed for MIX-4000-M Series Modules.
Preview MGC RAXN-UB-BRACKET Installation Instructions: Module Mounting Bracket
Installation guide for the MGC RAXN-UB-BRACKET module mounting bracket, detailing kit contents and assembly steps for mounting the RAXN-4000LCDGC module onto a fire alarm enclosure's inner deadfront chassis.
Preview MGC ANC-6000 Audio Network Controller Board Installation Instructions
Installation instructions for the MGC ANC-6000 Audio Network Controller Board, detailing module mounting, board layout, DIP switch configuration for addressing, and wiring for audio sources and paging microphones. Includes diagrams and technical specifications for system integration.
Preview MGC RA-1000 Series Remote Multiplex Annunciator Panels Installation and Wiring Manual
This manual provides installation and wiring instructions for the MGC RA-1000 Series Remote Multiplex Annunciator Panels, including details on mechanical installation, wiring, DIP switch settings, and specifications.
Preview MGC SGM-1004S: 4 NAC Output Module with Built-in Synchronization
The MGC SGM-1004S is a 4 NAC output module designed for fire alarm control panels, offering built-in synchronization for system devices like horns and strobes. It supports various wiring configurations and provides flexibility for synchronized signaling.