MGC SPPS-104 Series Ceiling Speaker-Strobe and SPP-104 Series Ceiling Speaker Installation and Maintenance Instructions
This manual provides installation and maintenance information for MGC SPPS-104 Series ceiling speaker-strobes and SPP-104 Series ceiling speakers. It is intended as a quick reference for installation. For detailed information on using these devices with a Fire Alarm Control Panel (FACP), refer to the panel's manual.
Note: This manual should be left with the owner/operator of the equipment.
CAUTION / ATTENTION
DO NOT PAINT OR ALTER FACTORY APPLIED FINISH IN ANY WAY. NE PAS PEINDRE OU MODIFIER LA FINITION ORIGINALE.
SPEAKER/SPEAKER STROBE DESCRIPTION
The SPPS-104 speaker-strobe is designed to meet UL1480/ULC S541 requirements for speakers and UL1638 /ULC S526 requirements for visual notification appliances. The SPP-104 speaker is designed to meet UL1480/ULC S541 requirements for speakers.
FIGURE 1: MODEL FRONT
Diagram showing the front view of the SPPS-104 and SPP-104 series devices, with dimensions indicated as 180mm [7in].
SETTING THE CANDELA (SPPS series only)
The candela can be set to 15, 30, 75, 110, 125, 15/75 for SPPS-104-25 and SPPS-104-70 models. The candela can be set to 50, 75, 90, 130, 185, 15/75 for SPPS-104-25H and SPPS-104-70H models. The factory default setting is 15 for SPPS-104-25/70 models, and 50 for SPPS-104-25H/70H models.
- Pull out the candela selector from the device.
- Re-insert the selector tab into the notch that is labeled with the desired candela setting (when removing or inserting the candela selector, ensure to keep it straight).
FIGURE 2: INSERTING CANDELA SELECTOR
Diagram illustrating the process of inserting the candela selector.
SETTING THE DIP SWITCHES
FIGURE 3: DIP SWITCH
Diagram showing the DIP switch configuration with labels for SYNC, NON-SYNC, OFF, and ON.
DIP | OFF | ON |
Switch 1 Input* | Synchronized | Regulated 24VDC/ FWR (Non-sync.) |
*Note: Use "SYNC” when flash synchronization is required, either through a sync module or built-in synchronization on the control unit. Use "NON-SYNC" when the appliances do not need to be synchronized.
Note: DIP switch 1 default setting is OFF, synchronized.
Note: DIP switch 2 is not used. By default it is OFF.
SPECIFICATIONS
SPPS-104 SERIES | ||
UL Reverberant (dBA@10ft) | ULC Anechoic (dBA@3m) | |
Operating temperature | 0°C to 49°C (32°F to 122°F) | |
Humidity range | 0% to 93% | |
Strobe flash rate | 1 Hz (1 flash per sec.) | |
Nominal strobe voltage | Regulated 24VDC/VFWR* | |
Operating voltage range | 16-33 VDC/VFWR | |
Nominal speaker voltage | 25V or 70.7Vrms | |
Speaker Size | 4" | |
Power Setting | 1/4, 1/2, 1, 2 W | |
Speaker Frequency range | 400-4000 Hz | |
Terminal wire gauge | 12-22 AWG |
*Note: For FWR signaling use an MGC panel.
SOUND PRESSURE LEVEL OUTPUT
WATT Tap | SPPS-104 SERIES | SPP-104 SERIES | ||
UL Reverberant (dBA@10ft) | ULC Anechoic (dBA@3m) | UL Reverberant (dBA@10ft) | ULC Anechoic (dBA@3m) | |
2 | 89.0 | 89.0 | 87.8 | 88.2 |
1 | 86.7 | 86.8 | 85.1 | 85.6 |
1/2 | 84.0 | 83.9 | 82.3 | 82.6 |
1/4 | 80.8 | 80.7 | 78.9 | 79.5 |
2 | 89.2 | 89.2 | 89.6 | 89.4 |
1 | 86.5 | 87.4 | 86.8 | 86.8 |
1/2 | 83.7 | 84.5 | 83.9 | 83.7 |
1/4 | 80.5 | 81.2 | 80.7 | 80.5 |
DIRECTIONAL SOUND CHARACTERISTICS
Table 4: DIRECTIONAL SOUND CHARACTERISTICS (Representative of both horizontal and vertical Axis)
ANGLE | dBA |
+40°, -43° | -3 |
+76°, -74° | -6 |
±90° | -10.3 |
ANGLE | dBA |
+35° | -3 |
±72° | -6 |
±90° | -10.6 |
STROBE RATINGS
Candela | SPPS-104 SERIES | SPPS-104 H SERIES | ||
Regulated 24VDC | Regulated 24VFWR | Regulated 24VDC | Regulated 24VFWR | |
15 | 33 | 33 | ||
30 | 47 | 43 | ||
75 | 111 | 100 | ||
110 | 204 | 186 | ||
125 | 295 | 277 | ||
15/75 | 112 | 100 | ||
50 | 54 | 57 | ||
75 | 78 | 83 | ||
90 | 100 | 104 | ||
130 | 159 | 162 | ||
185 | 343 | 327 | ||
15/75 | 82 | 87 |
LIGHT DISPERSION
Table 6: LIGHT DISPERSION
Degrees | % of Candela Rating |
±0 | 114 |
±5 | 111 |
±10 | 106 |
±15 | 100 |
±20 | 94 |
±25 | 90 |
±30 | 87 |
±35 | 82 |
±40 | 78 |
±45 | 77 |
±50 | 77 |
±55 | 76 |
±60 | 75 |
±65 | 63 |
±70 | 43 |
±75 | 33 |
±80 | 36 |
±85 | 41 |
+90 | 39 |
Compound ±45 | 78 |
Note: The values in Table 6 are shown as percentages of the rated light output at any candela setting.
WIRING
CAUTION
DO NOT LOOP SIGNAL CIRCUIT FIELD WIRES AROUND TERMINALS. ELECTRICAL SUPERVISION REQUIRES WIRE RUN TO BE BROKEN AT EACH END.
Diagram showing correct and incorrect wiring practices for supervision.
FIGURE 4: Figure 4 WIRING TAPS
Diagram illustrating wiring taps for speaker power selection and strobe input power.
Note: This device should be installed as per applicable requirements of the authorities having jurisdiction.
Use the information in this document to determine the total power or current of the devices. The total power or current of the devices must not exceed the output rating of the panel. Refer to the FACP installation guide for the wire size required according to the loop length and devices power usage. For maximum strobe operating current, please refer to Table 5.
FIGURE 5: DEVICE CONNECTION
Diagram showing device connection from a Fire Alarm Control Panel and to the next device, including wiring for speaker and strobe inputs.
*Note: When using with MGC panel or sync module, use MP-300 (3.9K).
Note: Wiring must be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations section 32 and NFPA 70.
CAUTION
FOR ALL TERMINAL TAPS USED FOR SYSTEM SUPERVISION, DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION
NE PAS UTILISER DE FILS EN BOUCLE SOUS LES BORNES. OUVRIR LA LIGNE POUR CONFIRMER LA SUPERVISION DES CONNEXIONS.
MOUNTING
MGC recommends spacing speaker strobe appliances in compliance with CAN/ULC S524 and NFPA72.
(Optional: In case of using a standard 4" square 2 1/8 deep electrical box, attach MP-184 adaptor ring from SPKC-W kit to the unit using 4 snaps.)
- Attach the unit to the IB-104 electrical box with the 2 included mounting screws.
- Rotate the top cover clockwise to snap it in place.
- Secure the top cover with the included securing screw and snap the nameplate over the securing screw.
FIGURE 6: MOUNTING DIAGRAM
Diagram showing the mounting steps: attaching the device to the electrical box, securing the top cover, and attaching the nameplate.
Model Numbers
- SPPS-104-25 Ceiling mounted speaker strobe 25V white
- SPPS-104-70 Ceiling mounted speaker strobe 70V white
- SPPS-104-25R Ceiling mounted speaker strobe 25V red
- SPPS-104-70R Ceiling mounted speaker strobe 70V red
- SPPS-104-25H Ceiling mounted speaker strobe 25V with High candela white
- SPPS-104-70H Ceiling mounted speaker strobe 70V with High candela white
- SPPS-104-25HR Ceiling mounted speaker strobe 25V with High candela red
- SPPS-104-70HR Ceiling mounted speaker strobe 70V with High candela red
- SPP-104-25 Ceiling mounted speaker 25V white
- SPP-104-70 Ceiling mounted speaker 70V white
- SPP-104-25R Ceiling mounted speaker 25V red
- SPP-104-70R Ceiling mounted speaker 70V red
Accessories
- IB-104 Round backbox
- SPKC-W Optional spacer
- MP-300 End of line resistor 3.9k Ohm