Generac Protector® Series Standby Generators
XG Protector® Series - Liquid-Cooled Gaseous Engine
Standard Features
- Power Zone® 410 Controller, NFPA 110 System Control Capable
- Padlockable Control Panel Cover with UV Protection
- Cellular Connectivity for Mobile Link and Fleet
- Quiet Operation
- Corrosion Resistant Aluminum Enclosure, Electro-Galvanized Baseframe Components, and Stainless Steel Exhaust System
- 5 Year/2,000 Hour Limited Warranty
- High Motor-Starting & Surge Capacity
- ±1% Digital Voltage Regulation
- <5% Total Harmonic Distortion Power Quality
- Fuel Efficiency
- Controller-Selectable Fuel Type - Propane or Natural Gas
- 1-Phase or Configurable 3-Phase Voltage Output Models
- Single-Side Regular Maintenance Access
- EPA Emissions Certified
- CA & MA Emissions Compliant (40 & 48 kW Models Available)
- UL 2200 Listed
- SwRI listed and labeled allowing installation as close as 18 in (457 mm) to a structure
- 145 mph (233 km/h) Wind Speed Rating
Optional Field-Installable Features
- 3-Phase Voltage Configuration Cartridge (VCC)
- 3-Phase Circuit Breakers (1-Phase Generators Include the Circuit Breaker)
- Generator Ready-Status Indicator
- Push-Button Emergency Stop
- NFPA 110 System Control & Remote Annunciation
- Cold Weather Operation Heaters
- Provisions for Rooftop and Elevated Mounting
- Baseframe Blockoff
- Engine Fluid Containment
Features
Innovative Design & Prototype Testing: Generac's commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards ensures superior performance.
Mobile Link® Connectivity: Standard on Generac Liquid-Cooled XG Protector Series generators, Mobile Link Cellular allows users to monitor their generator status from anywhere via smartphone, tablet, or PC. Access real-time operating status, maintenance alerts, and generator readiness. Connect to an authorized generator servicer for proactive support.
One Configurable 3-Phase Voltage Model: Each XG power output 3-phase model can be configured for 208/120, 240/120, or 480/277 V 3-phase output. Factory configured for 208/120 V using a Voltage Configuration Cartridge (VCC). The 3-phase voltage can be changed by the installer using a different VCC available as an accessory. The single-piece VCC simplifies installation.
True Power™ Electrical Technology: Superior harmonics and sine wave form produce less than 5% Total Harmonic Distortion for utility-quality power, enabling confident operation of sensitive electronic equipment.
Solid-State, Frequency Compensated Voltage Regulation: Standard on all Generac models, this system provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at ±1%.
Single Source Service Response: Generac's extensive service network provides parts and service expertise for the entire unit.
Generac Transfer Switches: Generac offers its own transfer systems and controls for total system compatibility, ensuring long life and reliability.
Generator Specifications
Generator Output - Propane
Voltage | XG03245 | XG04045 | XG04845 | |||
---|---|---|---|---|---|---|
Power (kW) | Current (A) | Power (kW) | Current (A) | Power (kW) | Current (A) | |
120/240 V 1-Phase | 32 | 133 | 40 | 167 | 48 | 200 |
208/120 V 3-Phase | 32 | 111 | 40 | 139 | 48 | 167 |
240/120 V 3-Phase | 32 | 96 | 40 | 120 | 48 | 144 |
480/277 V 3-Phase | 32 | 48 | 40 | 60 | 48 | 72 |
Generator Output - Natural Gas
Voltage | XG03245 | XG04045 | XG04845 | |||
---|---|---|---|---|---|---|
Power (kW) | Current (A) | Power (kW) | Current (A) | Power (kW) | Current (A) | |
120/240 V 1-Phase | 32 | 133 | 40 | 167 | 48 | 200 |
208/120 V 3-Phase | 32 | 111 | 40 | 139 | 48 | 167 |
240/120 V 3-Phase | 32 | 96 | 40 | 120 | 48 | 144 |
480/277 V 3-Phase | 32 | 48 | 40 | 60 | 48 | 72 |
Emergency Standby Power (ESP) Rating: Standby ratings apply to installations served by a reliable utility source. The ESP rating is applicable to varying loads for the duration of a power outage. The average power output over 24 hours shall not exceed 70% of the ESP rating.
Alternator System
XG03245 | XG04045 | XG04845 | |
---|---|---|---|
Voltage Output 1-Phase | 120/240 V Only | 120/240 V Only | 120/240 V Only |
Voltage Output 3-Phase | 208/120 V; Configurable for 240/120 or 480/277 V with Optional VCC | 208/120 V; Configurable for 240/120 or 480/277 V with Optional VCC | 208/120 V; Configurable for 240/120 or 480/277 V with Optional VCC |
Circuit Breaker (CB) Size (A) 1-Phase | 150 | 200 | 200 |
Circuit Breaker (CB) Size (A) 3-Phase | Not Included; Optional, Field-Installable Kit | Not Included; Optional, Field-Installable Kit | Not Included; Optional, Field-Installable Kit |
Alternator Type | Synchronous | ||
Rotor Insulation Class | F | ||
Stator Insulation Class | H | ||
Telephone Interference Factor (TIF) | <50 | ||
Bearings | Sealed Ball | ||
Coupling | Flexible Disc | ||
Excitation System | Direct | ||
Total Harmonic Distortion | <5% |
Voltage Regulation
Type | Digital |
Sensing | All Phases |
Regulation | ±1% |
Surge Capacity
Surge Amps at <0.4 Power Factor | XG03245 | XG04045 | XG04845 | |||
---|---|---|---|---|---|---|
15% Voltage Dip (A) | 30% Voltage Dip (A) | 15% Voltage Dip (A) | 30% Voltage Dip (A) | 15% Voltage Dip (A) | 30% Voltage Dip (A) | |
120/240 V 1-Phase | 107 | 204 | 117 | 267 | 220 | 340 |
208/120 V 3-Phase | 111 | 167 | 139 | 215 | 166 | 266 |
240/120 V 3-Phase | 91 | 140 | 114 | 150 | 144 | 230 |
480/277 V 3-Phase | 55 | 87 | 63 | 102 | 72 | 129 |
Engine System
XG03245 | XG04045 | XG04845 | |
---|---|---|---|
Make | Generac | ||
Model | 4.5 L, Inline 4-Cylinder, Naturally Aspirated | ||
Compression Ratio | 9.9:1 | ||
Lifter Type | Hydraulic | ||
Oil Pump Type | Gear | ||
Oil Filter Type | Full Flow Spin-on Cartridge | ||
Crackcase Capacity (qt (L)) | 12 (11) | ||
Temperature Derate | 1.7% per 10 °F above 77 °F (1.5% per 5 °C above 25 °C) | ||
Altitude Derate | 3% per 1,000 ft above 600 ft (1% per 100 m above 183 m) | ||
Exercise Speed (rpm) | 1,200 | ||
Operating Speed (rpm) | 1,800 | ||
Exhaust Flow at Rated Output (cfm (m³/min)) | 187 (8.3) | 235 (6.7) | 280 (7.9) |
Governor
XG03245 | XG04045 | XG04845 | |
---|---|---|---|
Type | Electronic | ||
Frequency Regulation | Isochronous |
Cooling System
XG03245 | XG04045 | XG04845 | |
---|---|---|---|
Coolant | 50/50 (50% Ethylene Glycol) | ||
Coolant System Capacity (US gal (L)) | 2.9 (11) | ||
Water Pump Type | Belt Driven | ||
Fan Type | Belt Driven | Belt Driven | Electric |
Fan Quantity | 1 | 1 | 3 |
Maximum Ambient Air Temperature (°F (°C)) | 122 (50) |
Fuel System
Usable Fuels | Liquid Propane (LP) Vapor or Natural Gas (NG) |
Fuel Type Configuration | Controller-Selected Only |
LP Vapor Pressure (in H2O (kPa)) | 7-14 (1.74-3.48) |
NG Pressure (in H2O (kPa)) | 3.5-14 (0.87-3.48) |
Fuel Shutoff Solenoid | Standard, Dual |
Fuel Consumption - Liquid Propane
XG03245 | XG04045 | XG04845 | ||||
---|---|---|---|---|---|---|
(US gph) | (L/h) | (US gph) | (L/h) | (US gph) | (L/h) | |
Rated Load | 1.1 | 4.1 | 1.1 | 4.1 | 1.1 | 4.1 |
No Load @ Exercise Speed | 2.6 | 10.0 | 2.8 | 10.7 | 3.0 | 11.5 |
25% | 3.4 | 13.0 | 3.8 | 14.4 | 4.2 | 15.9 |
50% | 4.2 | 15.9 | 4.8 | 18.1 | 5.4 | 20.4 |
75% | 5.0 | 18.9 | 5.8 | 21.9 | 6.6 | 24.8 |
100% | 5.0 | 18.9 | 5.8 | 21.9 | 6.6 | 24.8 |
Propane – 91,452 BTU/US gal (25.5 MJ/L); 36 ft³/US gal (0.27 m³/L); 2,516 BTU/ft³ (93.7 MJ/m³); 4.24 lb/US gal (0.508 kg/L)
Fuel Consumption - Natural Gas
XG03245 | XG04045 | XG04845 | ||||
---|---|---|---|---|---|---|
(CFH) | (m³/h) | (CFH) | (m³/h) | (CFH) | (m³/h) | |
Rated Load | 71 | 2.0 | 71 | 2.0 | 71 | 2.0 |
No Load @ Exercise Speed | 177 | 5.0 | 198 | 5.6 | 215 | 6.1 |
25% | 258 | 7.3 | 297 | 8.4 | 335 | 9.5 |
50% | 335 | 9.5 | 396 | 11.2 | 456 | 12.9 |
75% | 417 | 11.8 | 494 | 14.0 | 576 | 16.3 |
100% | 417 | 11.8 | 494 | 14.0 | 576 | 16.3 |
Natural Gas – 1,036 BTU/ft³ (37.3 MJ/m³)
See Emissions Data Sheets for maximum fuel flow for EPA and SCAQMD permitting purposes.
Electrical System
XG03245 | XG04045 | XG04845 | |
---|---|---|---|
System Voltage (V) | 12 | 12 | 12 |
Charge Alternator (A) | 37 | 37 | 145 |
Battery Charger (A) | 5 | 5 | 5 |
Recommended Battery (not included) | Flooded Lead Acid, Group 27, 600 CCA Minimum | ||
Maximum Allowable Battery | Flooded Lead Acid, Group 31, 750 CCA Minimum |
Enclosure
XG03245 | XG04045 | XG04845 | |
---|---|---|---|
Sound Level at Exercise Speed (dB(A) @ 23 ft (7 m)) | 59 | 59 | 54 |
Sound Level at Operating Speed & No Load (dB(A) @ 23 ft (7 m)) | 66 | 66 | 58 |
Wind Speed Rating (mph (km/h)) | 145 (233) | 145 (233) | 145 (233) |
Color | Metro Gray |
4 - Lowest sound level measurement of 8 locations around the generator. Sound levels at other locations around the generator may vary depending on the installation.
5 - ASCE 7-16 exposure B wind speed rating
Power Zone 410 Controller
Standard Features
- 128 x 64 Pixel Graphical Display with Heater
- Multilingual (English, Spanish, French, Portuguese)
- 3-Phase Sensing Digital Voltage Regulator
- Full Range Standby Operation
- Full System Status (3-Phase AC Voltage, 3-Phase Current, Power, Power Factor, Oil Pressure, Engine Coolant Temperature, Oil Temperature, Fuel Pressure, Engine Speed, Battery Voltage, Time, Date)
- Load On Line Power and Gen Power Hourmeter
- Service Reminders
- Fault History (Alarm Log)
- Remote Communications
- Programmable Auto Crank
- Emergency Stop
- Not in Auto Flashing Light
- Selectable Low Speed Exercise
- NFPA 110 System Control Capable
- 5A Integrated Battery Charger
Standard Protections
- Low Oil Pressure
- Low Coolant Level
- High/Low Coolant Temperature
- Oil Temperature
- Over/Under Speed
- Over/Under Voltage
- Over/Under Frequency
- Over/Under Current
- Overload
- Battery Voltage
- Battery Charger Current
- Phase-to-Phase and Phase-to-Neutral Short Circuits (I²T Algorithm)
- Ground Fault
Display
- Easy Menu Structure
- Multilingual (English, Spanish, French, Portuguese)
- On Screen Editable Parameters
Key Function Monitoring
- 3-Phase Voltage, Amperage, Power, Apparent Power, Reactive Power
- Selectable Average or Line-to-Neutral Voltage Measurements
- Frequency
- Engine Speed
- Engine Coolant Temperature
- Oil Pressure
- Battery Voltage
- Warning and Alarm Indication
- Diagnostics
- Maintenance Events/Information
- Hourmeter
Control Panel
- AUTO/OFF/MANUAL Operation Through Onboard Buttons or Optional Key Switch
- Indication Through Display Screen and LEDs
- Audible Alarm and Silence
- Auxiliary Shutdown Rocker Switch (on controller)
Voltage Regulation
- Digital Control
- 3-Phase Sensing
- Variable V/F Slope Settings
- Negative Power Limit
Fault Protection (I²T Function)
- Loss of Sensing Protection
- High Voltage Limit
- Low Voltage Limit
- Maximum Power Limit
Governor Functionality
- Speed Control through ECM Integration
Communications Ports
- 1 CANbus Port
- 1 USB Port (for Configuration Transfer and Firmware Upgrades)
- 1 RS-485 Modbus Master Port (for External RAP/RRP/External I/O Modules)
- 1 RS-485 Modbus Slave Port (for other uses, e.g. Building Management System)
- 2 RS-232 Communication Ports (for GGCAC or other uses)
Codes And Standards
- UL 6200
- CE
- NFPA 110
Accessories
3-Phase XG Generator Model Kits
Product | Part Number | Description |
---|---|---|
XG032/40/48 'G' 208/120 V 3-Phase Voltage Configuration Cartridge | G0099010 | Voltage Configuration Cartridge (VCC) for 208/120 V 3-phase output. It is INSTALLED in every 3-phase XG03245, XG04045, and XG04845 model. Offered as an accessory if a replacement is needed for any reason. |
XG032/40/48 'J' 240/120 V 3-Phase Voltage Configuration Cartridge | G0099020 | Voltage Configuration Cartridge (VCC) for 240/120 V 3-phase output. It is NOT included with any XG03245, XG04045, or XG04845 model. |
XG032/40/48 'K' 480/277 V 3-Phase Voltage Configuration Cartridge | G0099030 | Voltage Configuration Cartridge (VCC) for 480/277 V 3-phase output. It is NOT included with any XG03245, XG04045, or XG04845 model. |
60 A 3-Pole Circuit Breaker (CB) Kit | G0099040 | 3-pole, 60 A CB and mounting hardware (typical for 32 kW, 480/277 V 3-phase generator). |
70 A 3-Pole Circuit Breaker (CB) Kit | G0099190 | 3-pole, 70 A CB and mounting hardware (typical for 40 kW, 480/277 V 3-phase generator). |
80 A 3-Pole Circuit Breaker (CB) Kit | G0099050 | 3-pole, 80 A CB and mounting hardware (typical for 48 kW, 480/277 V 3-phase generator). |
100 A 3-Pole Circuit Breaker (CB) Kit | G0099060 | 3-pole, 100 A CB and mounting hardware (typical for 32 kW, 240/120 V 3-phase generator). |
125 A 3-Pole Circuit Breaker (CB) Kit | G0099070 | 3-pole, 125 A CB and mounting hardware (typical for 32 kW, 208/120 V; and 40 kW, 240/120 V 3-phase generators). |
150 A 3-Pole Circuit Breaker (CB) Kit | G0099080 | 3-pole, 150 A CB and mounting hardware (typical for 40 kW, 208/120 V and 48 kW, 240/120 V 3-phase generators). |
175 A 3-Pole Circuit Breaker (CB) Kit | G0099090 | 3-pole, 175 A CB and mounting hardware (typical for 48 kW, 208/120 V 3-phase generator). |
Control System Kits
Product | Part Number | Description |
---|---|---|
Generator Ready-Status Indicator Kit | G0099100 | 3-color LED providing at-a-glance indication of generator ready-to-run status. The display mounts to the front of the generator and plugs into the wire harness. |
Enclosure Mounted Emergency Stop Kit | G0079930 | Emergency Stop consists of a red push button switch. It mounts to the exterior of the generator enclosure replacing the Generator Emergency Shutdown rocker switch in the same location. |
Remote Emergency Stop Kit, Surface Mount | G0099250 | Emergency Stop consists of a red push button switch with twist release. The switch has an aluminum enclosure which can be mounted extending out from a surface. It mounts remote from the generator such as near an electrical panel. |
Remote Emergency Stop Kit, Flush Mount | G0099260 | Emergency Stop consists of a red push button switch with twist release. The switch has an aluminum enclosure which can be mounted flush. It mounts remote from the generator such as near an electrical panel. |
Remote Emergency Stop Kit, Break Glass | G0099270 | Emergency Stop consists of a spring-loaded switch behind breakable glass. The glass can be broken with the tethered hammer. The switch has an aluminum enclosure which can be mounted extending out from a surface. It mounts remote from the generator such as near an electrical panel. |
Generac Load Manager, 50 A | G0070001 | 50 A Load Manager helps optimize the performance of the standby generator by managing large electrical loads upon startup and shed them to aid in recovery when overloaded. |
Generac Load Manager, 100 A | G0070061 | 100 A Load Manager helps optimize the performance of the standby generator by managing large electrical loads upon startup and shed them to aid in recovery when overloaded. |
Generac LTE Propane Tank Fuel Level Monitor | G0070090 | The Propane Tank Fuel Level Monitor connects to 4G LTE cellular service to measure and report the amount of LP fuel remaining in the tank. The app alerts the user of both remaining LP fuel and usage reports. |
Power Zone Kits
Product | Part Number | Description |
---|---|---|
NFPA 110 Controller Kit | G0099120 | Includes controller module with Key Switch, Alarm Horn, and Emergency Stop Switch that connects to the Power Zone 410 controller. The module mounts below the controller and is visible through the control panel cover. The G0098511, G0098521, or G0098531 panel and a capable transfer switch are required to be considered for NFPA 110 system control and remote annunciation. |
Remote Annunciator Panel with 8 Relays | G0098511 | Remote annunciator panel with relays. The panel mounts in the structure that is connected to the backup generator. |
Remote Relay Panel | G0098521 | Remote relay panel without LEDs or keypad. The panel mounts in the structure that is connected to the backup generator. |
Remote Annunciator Panel without Relays | G0098531 | Remote annunciator panel without relays. The panel mounts in the structure that is connected to the backup generator. |
Power Zone 410 I/O Extender Kit | G0089370 | The kit expands I/O for the Power Zone 410 controller to provide connections for additional accessories. It connects to the controller with a 3-wire RS-485 interface. |
Power Zone Gateway Kit | G0089360 | The Gateway provides an Ethernet connection port for the generator for a Building Management System (BMS). The Gateway is NOT intended for or able to be used with Mobile Link or Fleet. |
Operating Environment Kits
Product | Part Number | Description |
---|---|---|
Battery Heater Kit | G0079920 | Recommended for operating environments where the temperature drops below 32 °F (0 °C). The heater is externally powered by 120 VAC, 60 Hz. |
Engine Block Heater Kit | G0099230 | Recommended for operating environments where the temperature drops below 0 °F (-18 °C). The heater is externally powered by 120 VAC, 60 Hz. |
Extreme High Wind Kit | G0099130 | Increases wind speed rating of generator to 186 mph (300 km/h). The kit assembles to the exterior of the generator enclosure and frame. |
Installation Kits
Product | Part Number | Description |
---|---|---|
Baseframe Blockoff Kit | G0099150 | Aluminum panel and hardware to close off the bottom of the generator. It allows correct airflow is maintained through the generator for cooling while keeping objects out? It is required anytime the generator is elevated. Fits XG03245, XG04045, and XG04845. |
Engine Fluid Containment Kit | G0099160 | Containment pan to capture all engine oil and coolant. Kit includes a sensor to detect the presence of fluid in the pan then displays a warning on the controller screen. The G0089370 Power Zone 410 I/O Extender Kit is required for the sensor installation. |
Base Plug Kit | G0056510 | Base plugs to fit in the lifting holes of the baseframe to keep debris out. |
Maintenance Kits
Product | Part Number | Description |
---|---|---|
4.5 L Gaseous Engine Regular Maintenance Kit | G0079910 | Regular maintenance kit includes oil filter, oil funnel, air filter, and spark plugs. |
Metro Gray Paint Kit | G0099180 | It is important to touch-up the paint to protect against corrosion if the generator enclosure is scratched or damaged. The paint kit includes the necessary paint to correctly maintain or touch-up a generator enclosure. |
Transfer Switch Kits
Product | Part Number | Description |
---|---|---|
3-Phase Voltage Sensing Kit for 208/120 & 240/120 V RTS Transfer Switch | G0074110 | 3-phase Voltage Sensing Kit required for RTS Transfer Switches when used with the Power Zone 410 controller for 'G' 208/120 or 'J' 240/120 V 3-phase voltage. The kit is used with 3-phase XG03245, XG04045, and XG04845 models configured for 'G' or 'J' voltage. |
3-Phase Voltage Sensing Kit for 480/277 V RTS Transfer Switch | G0074120 | 3-phase Voltage Sensing Kit required for RTS Transfer Switches when used with the Power Zone 410 controller for 'K' 480/277 V 3-phase voltage. The kit is used with 3-phase XG03245, XG04045, and XG04845 models configured for 'K' voltage. |
Installation Drawing
Dimensions and Weight Data:
- Genset Only Weight: 769 kg [1695 lbs]
- Shipping Skid Weight: 43 kg [95 lbs]
- Shipping Weight: 812 kg [1790 lbs]
- Center of Gravity: See Note 5
Service Item Locations:
- Oil Fill Cap: Left Side
- Oil Dip Stick: Left Side
- Oil Filter: Left Side
- Oil Drain Hose: Left Side
- Radiator Drain Hose: Left Side
- Coolant Recovery Bottle: Right Side
- Radiator Fill Cap: Roof Top
- Air Cleaner Element: Left Side
- Spark Plugs: Left Side
- Muffler: See Note 11
- Drive Belt: Either Side
- Battery: Left Side
Notes:
- Minimum recommended concrete pad size is 6" offset of overall length and width of generator. Reference Installation Guide for concrete pad guidelines.
- Allow sufficient room on all sides for maintenance and servicing. Install in accordance with applicable NFPA 37 and NFPA 70 standards, and other codes.
- Control Panel / Circuit Breaker Information: Accessible through customer access assembly door on rear of generator.
- Remove rear enclosure cover panel to access stub-up areas for high voltage connection, neutral connection, battery charger 120V AC connection, and low voltage connection.
- Center of gravity and weight may change due to unit options.
- Bottom of generator set must be enclosed to prevent pest intrusion and recirculation of discharge air.
- Reference Owners Manual for lifting warnings.
- Recommended mounting bolts or studs: 1/2" diameter (use standard SAE torque specs).
- Must allow free flow of intake air, discharge air, and exhaust. See spec sheet for minimum air flow and maximum restriction requirements.
- Generator must be installed such that fresh cooling air is available and discharge air is not recirculated.
- Exhaust muffler enclosed within generator enclosure; remove front panel to access.
Dimensions:
- Overall Length: 2012 mm [79.2 in]
- Overall Width: 854.1 mm [33.6 in]
- Overall Height: 1094 mm [43.1 in]
- Stub-up Conduit Height Requirement From Bottom of Frame: 57.6 mm [2.3 in]
Top View: Shows air intake on both sides, radiator/exhaust discharge air, and enclosed exhaust muffler.
Front View (Service Left): Shows one lift-off door with latch, customer access assembly for control panel access, battery charger located within right enclosure cover panel.
Right View (Service Rear): Shows circuit breaker access.
Rear View (Service Right): Shows fuel line connection (1-1/4" NPT female tee through baseframe opening).
Side View (Top View Mounting Slot Centers): Shows mounting slot centers.
Side View (Front Service Left): Shows stub-up area for high and low voltage connections, circuit breaker, neutral, and customer connection opening.
Side View (Right Service Rear): Shows stub-up area.
File Info : application/pdf, 9 Pages, 11.44MB
DocumentDocumentReferences
PDFlib PDI 10.0.0p5 (C /Win64)Related Documents
![]() |
Generac Protector Series Standby Generators: XG03245 & XG04045 Specifications Detailed specifications and features for Generac Protector Series standby generators, including models XG03245 (32 kW) and XG04045 (40 kW), highlighting performance, control systems, and accessories. |
![]() |
Generac Protector Series Standby Generators: Specifications, Features, and Installation Guide Explore the Generac Protector Series of liquid-cooled gaseous standby generators (25-60 kW). This document details model specifications, key features like True Power™ technology, advanced controllers, fuel consumption, and installation layout information. |
![]() |
Generac Protector Series 48 kW Standby Generator Specifications and Data Detailed specifications, application data, and installation layout for the Generac Protector Series 48 kW liquid-cooled gaseous standby generator. Includes features, engine specifications, electrical system details, enclosure information, and available accessories. |
![]() |
Generac RG Protector Series Liquid-Cooled Standby Generators: Specifications Detailed specifications for Generac RG Protector Series liquid-cooled gaseous standby generators, covering models from 22 kW to 60 kW. Includes features, technical data, engine specifications, fuel consumption, electrical system details, enclosure information, controller features, and available accessories. |
![]() |
Generac RG Protector Series Standby Generators: Specifications and Installation Details Comprehensive specifications, features, and installation drawings for Generac RG Protector Series Standby Generators, including models RG04845, RG06045, and RG08045. Covers engine, fuel, electrical, and enclosure details, plus installation guidance. |
![]() |
Generac 20 kW Guardian Series Standby Generator: Features, Specifications, and Accessories Detailed overview of the Generac 20 kW Guardian Series Standby Generator, covering its key features, technical specifications, engine and generator details, installation system, remote monitoring capabilities, and available accessories for residential and commercial use. |
![]() |
Generac Guardian Series Standby Generators: Features, Specifications, and Data Explore the Generac Guardian Series of liquid-cooled gas engine standby generators. This document details features, technical specifications, operating data, and installation layouts for models QT025, QT030, QT045, and QT060. |
![]() |
Generac Guardian Series 8/10/13 kVA Residential Standby Generators - Specifications & Features Detailed specifications, features, and benefits of Generac Guardian Series 8, 10, and 13 kVA residential standby generators. Includes engine, generator, and control system information, along with available accessories and dimensions. |