Installation Instructions

Partial Flow Commercial Room Ventilator 24 Volt On/Off with Spring Return and Exhaust

Model: CRV-F5

For Use with Bard Wall Mount Air Conditioner and Heat Pump Models:

Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com

Manual: 2100-751A
Supersedes: 2100-751
Date: 3-28-23

General Information

Commercial Room Ventilator Model Nomenclature

The model nomenclature indicates the following:

Unpacking

Upon receipt, verify the model number on the shipping label matches the accessory identification information. Inspect the carton for any visible damage before signing the freight bill. Note any shortages or damage on all copies of the freight bill and contact the carrier immediately. Report concealed damage to the carrier within 15 days of receipt.

General

This ventilator should only be installed by a trained heating and air conditioning technician. These instructions are a guide for the technician. The ventilator housing is shipped in one carton containing the electrical harness, hardware, and instructions. The kit includes:

Commercial Room Ventilator Features

Description

The CRV-F5 ventilator is designed for specific Bard Wall Mount Air Conditioner and Heat Pump models with "letter" revision codes. The factory-installed vent is denoted by the letter "M" in the unit model nomenclature. This electromechanical vent system provides fresh air to meet indoor air quality standards.

Models

When installed in the listed models, the CRV-F5 provides built-in exhaust provisions. When the damper blade opens for fresh air intake, it also opens an exhaust relief. The condenser fan assists in drawing exhaust air out when operating with the compressor in cooling or heat pump mode.

Basic Installation

WARNING: Electrical shock hazard. Disconnect remote electrical power supply or supplies before servicing. Failure to do so could result in electric shock or death.

WARNING: Exposed moving parts. Disconnect electrical power before servicing. Failure to do so could result in severe injury or amputation.

CAUTION: Cut hazard. Wear gloves to avoid contact with sharp edges. Failure to do so could result in personal injury.

  1. Disconnect all power to the unit. [Power Disconnect Symbol]
  2. Remove both side grilles. [Side Grille Removal]
  3. Remove the upper blower door and outer control panel cover. [Blower Door and Control Panel Cover Removal]
  4. Remove blank off plates on both sides (behind side grilles) and discard. [Blank Off Plate Removal]
  5. Remove the exhaust blank off plate through return or through side intake openings. [Exhaust Blank Off Plate Removal]
  6. Install the 1913-013-2708 gasket 5/8" from the bend as shown. Then install the exhaust blade assembly using 10 screws. [Gasket and Exhaust Blade Assembly Installation]
  7. Remove both air filters and the low voltage inner control panel cover. [Filter and Control Panel Cover Removal]
  8. Connect the 3000-1622 wire assembly. Snap the 4-pin connector into the opening next to the low voltage box and plug the 12-pin male connector into the female plug in the low voltage box. [Wire Assembly Connection]
  9. Install the vent from the side. Slide the CRV onto the exhaust partition until flush with the side of the wall mount. [Vent Installation]
  10. Ensure the control plug is centered in the plug access opening on the front panel of the CRV. [Control Plug Centering]
  11. From the front, through the filter opening, plug the CRV power plug into the control panel plug. [CRV Power Plug Connection]
  12. The CRV exhaust blade is secured in the shipping position by the actuator blade stop. Remove the blade stop to release the blade. Proceed with caution as the actuator is spring-loaded. [Blade Stop Removal]
  13. Set the blade stop using the airflow charts on pages 9-12 to achieve the desired ventilation air. Loosen the screw on the actuator blade stop, slide to the desired setting using the notches and marks on the label, and tighten the screw. [Blade Stop Adjustment]
  14. Install the 539-405 intake sealing frame and the 543-223 lower block off plates on both sides. Install two (2) 1913-002-0708 7-1/2" foam gaskets below the intake sealing frame on both sides. [Intake Sealing Frame and Block Off Plate Installation]
  15. Bend the two (2) sheet metal tabs in the condenser partition up to hold the bottom of the mist eliminator. Install the 7003-084 mist filters on both sides. Re-install the side grilles. [Mist Filter Installation]
  16. Remove the front lower (condenser) grille. Bend the two (2) sheet metal tabs in the condenser partition up to hold the bottom of the bug screen. Install two (2) 1913-002-0808 8-1/2" foam gaskets to the sides of the cabinet. Install the 7003-083 exhaust bug screen. Re-install the grille. [Bug Screen and Gasket Installation]
  17. Restore power to the unit. Energize the "A" terminal to test blade operation. Disconnect power after testing.
  18. Install both filters, then re-install the inner control panel cover, outer control panel cover, and upper blower door.
  19. Restore power to the unit.

Control System Notes

This ventilation package can be set to meet current ASHRAE specifications for minimum occupied airflow rates.

On/Off Operation

Energizing the "A" terminal during occupied conditions drives the fresh air damper to the pre-selected fixed position. The "G" terminal operates the indoor blower.

Blade Adjustment for Desired Ventilator Air

The amount of ventilation air is dependent on return air duct static pressure drop, supply air duct static pressure drop, indoor blower motor speed, and damper blade open position setting. Refer to the appropriate graph on pages 9-12 to determine the necessary blade setting for the required ventilation air.

Graph 1: W3SAC CRV-F5 Ventilation Delivery

Supply & Return Grilles

  • 40 Duct Static
  • 20 Duct Static

Graph 2: W42°C CRV-F5 Ventilation Delivery

Supply & Return Grilles

  • 20 Duct Static
  • 40 Duct Static

Graph 3: W48*C and W4SAC CRV-F5 Ventilation Delivery

Graph 4: W60*C and W5SAC CRV-F5 Ventilation Delivery

Graph 5: W72AC CRV-F5 Ventilation Delivery

Supply & Return Grilles

  • .20 Duct Static
  • Outdoor Static: .40 Duct Static

Graph 6: C36H AND C42H CRV-F5 Ventilation Delivery

Damper Position

  • C36H & C42H Fan Only and C36H Part Load
  • C42H Part Load
  • C36H Full Load
  • C42H Full Load

Graph 7: C48H AND C60H CRV-F5 Ventilation Delivery

Damper Position

  • C48H & C60H Fan only
  • C48H Part load
  • C60H Part load
  • C48H Full load
  • C60H Full load

Wiring Diagrams and Tables

The document includes detailed wiring diagrams for various thermostat configurations (Programmable and Non-Programmable) with Single Stage Air Conditioners and Heat Pumps. It also provides tables outlining the unit operation with the "M" Ventilation Option for different Bard unit models (W**AC, W**HC, W*SAC, C**HY) under various operating conditions (Fan Only, Cooling, Heating, Dehumidify).

Figure 18: Programmable Thermostat Connections for CRV with Single Stage Air Conditioners

This figure illustrates the wiring connections between the CRV and a programmable thermostat for single-stage air conditioning systems.

Figure 19: Programmable Thermostat Connections for CRV with 2-Stage Air Conditioners

This figure illustrates the wiring connections between the CRV and a programmable thermostat for two-stage air conditioning systems.

Figure 20: Programmable Thermostat Connections for CRV with Heat Pumps

This figure illustrates the wiring connections between the CRV and a programmable thermostat for heat pump systems.

Figure 21: Non-Programmable Thermostat Connections for CRV with Single Stage Air Conditioners

This figure illustrates the wiring connections between the CRV and a non-programmable thermostat for single-stage air conditioning systems.

Figure 22: Non-Programmable Thermostat Connections for CRV with 2-Stage Air Conditioners

This figure illustrates the wiring connections between the CRV and a non-programmable thermostat for two-stage air conditioning systems.

Figure 23: Non-Programmable Thermostat Connections for CRV with Heat Pumps

This figure illustrates the wiring connections between the CRV and a non-programmable thermostat for heat pump systems.

Figure 24: CRV-F* Wiring Diagram

This figure provides a general wiring diagram for the CRV-F* series.

Table 1: W**AC and W**HC Unit Operation with M Ventilation Option

This table details the operational states of W**AC and W**HC units with the "M" Ventilation Option, correlating unit operation with occupancy signals, low voltage connections, fan speeds, compressor operation, and damper position.

Table 2: W*SAC Unit Operation with M Ventilation Option

This table details the operational states of W*SAC units with the "M" Ventilation Option, correlating unit operation with occupancy signals, low voltage connections, fan speeds, compressor operation, and damper position.

Table 3: C**HY Unit Operation with M Ventilation Option

This table details the operational states of C**HY units with the "M" Ventilation Option, correlating unit operation with occupancy signals, low voltage connections, compressor status, fan speed, and damper potentiometer settings.

Sequence of Operation

On/Off ventilation options are energized when the "A" low voltage strip terminal is energized, indicating occupancy, and de-energize when the signal is removed. The "G" low voltage strip terminal operates the indoor blower. The "M" On/Off CRV vent option uses a 24 VAC motor to open the damper blade to a pre-adjusted setting. The incoming airflow amount depends on the blower speed during unit operation.

Figures 25 & 26: Airflow Diagrams

Figure 25 illustrates the airflow path during a call for ventilation with or without compressor operation. Figure 26 shows the airflow path for compressor or fan-only operation with ventilation off. These diagrams depict outdoor air intake, mist eliminators, intake blades, exhaust air, bug screens, condenser air, and the condenser coil.

Models: CRV-F5 Wall Mount Ventilation, CRV-F5, Wall Mount Ventilation, Mount Ventilation, Ventilation

File Info : application/pdf, 23 Pages, 1.71MB

PDF preview unavailable. Download the PDF instead.

2100-751(A)

References

Adobe PDF Library 17.0

Related Documents

Preview Bard Wall Mount Air Conditioner Replacement Parts Manual
Comprehensive replacement parts manual for Bard wall mount air conditioner models including W42AC, W48AC, W60AC, and W72AC series. Details exploded views, usage lists, and part numbers for external, internal, and functional components.
Preview Bard Wall Mount Air Conditioner Replacement Parts Manual
This manual provides detailed replacement parts information for Bard Wall Mount Air Conditioners, including exploded views, parts lists, and compatibility across various models.
Preview Bard 11EER WA Series Wall Mount Air Conditioner Installation Instructions
Comprehensive installation guide for Bard 11EER WA Series Wall Mount Air Conditioners, covering general information, installation procedures, duct work, filters, fresh air intake, and safety precautions.
Preview Bard CHCRV-5A Commercial Room Ventilator Installation Instructions
Detailed installation guide for the Bard CHCRV-5A Commercial Room Ventilator with Exhaust, designed for use with Bard Single Stage Heat Pump Models C36H, C42H, C48H, and C60H. Covers unpacking, basic installation, sequence of operation, CO2 control, and blade adjustment.
Preview Bard I-TEC ERV Economizer Ventilator System Installation and Maintenance Guide
Comprehensive installation, operation, and maintenance guide for the Bard I-TEC ERV Economizer Ventilator System (Vent Code 'E'), including performance data, control wiring, and cleaning procedures.
Preview Bard Two Stage Heat Pumps Low Voltage Control Circuit Wiring Installation Instructions
Installation instructions for Bard two-stage heat pumps, covering low voltage control circuit wiring for various models including T**S, T**S*D, and C**H. This document details wiring diagrams, thermostat compatibility, and optional features like economizers and ventilation packages.
Preview Bard Q-TEC QCRV-F3 Commercial Room Ventilator Operation and Service Instructions
Comprehensive operation and service instructions for the Bard Q-TEC QCRV-F3 Commercial Room Ventilator. This guide covers model nomenclature, description, application, thermostat connections, blade adjustment, ventilation delivery graphs, airflow diagrams, and wiring schematics for optimal performance and maintenance.
Preview Bard Split Air Conditioner Units Installation Manual Index
Comprehensive index of installation manuals for Bard Split Air Conditioner Units, covering ECQ, HAC, and UAC series with document numbers, revisions, and release dates.