OPERATION AND SERVICE INSTRUCTIONS

Q-TECTM Commercial Room Ventilator with Spring Return and Exhaust

Models: QCRV-F3

For Use with Bard Q-TEC Heat Pumps Models:

Q24H4-A,-B,-C Q30H4-A,-B,-C Q36H4-A,-B,-C Q24H4DA,B,C Q30H4DA,B,C Q36H4DA,B,C

Manufacturer: Bard Manufacturing Company, Inc. Bryan, Ohio 43506

Website: www.bardhvac.com

Manual Number: 2100-741

Supersedes: NEW

Date: 9-17-20

Table of Contents

Safety Precautions

WARNING: Electrical shock hazard. Disconnect remote electrical power supply or supplies before servicing. Failure to do so could result in electric shock or death.

WARNING: Exposed moving parts. Disconnect all electrical power before servicing. Failure to do so can result in severe injury or amputation.

CAUTION: Sharp metallic edges. Take care and wear appropriate protective devices to avoid accidental contact with sharp edges. Failure to do so can result in personal injury.

QCRV-F3 Features

Model Nomenclature

The QCRV-F3 model designation breaks down as follows:

Description

The Bard QCRV-F3 Commercial Room Ventilator is an electromechanical ventilation system designed to provide fresh outdoor air to meet indoor air quality standards. It is intended for use with specific Bard heat pump models as designated on the front page of this manual.

This unit features an internally mounted damper with exhaust capabilities, designed to supply up to 50% fresh air. The damper blade is powered by a 24 VAC motor that provides a power-open function and a spring-return action upon power loss. The damper opens when the 'A' terminal is energized. Ten different airflow settings can be achieved by adjusting the blade stop screws located under the fresh air blade.

When installed in compatible Bard heat pump models, the QCRV-F3 integrates exhaust provisions. As the damper blade opens to admit fresh air, it simultaneously opens an exhaust relief. This exhaust air is directed into the unit's condenser section, where the condenser fan assists in drawing it out during cooling or heat pump operation.

Application

The quantity of outside fresh air introduced into a structure by the QCRV-F3 is influenced by several factors within the duct system: return air duct static pressure, supply air duct static pressure, and indoor blower motor speed. The damper blade's open position setting also plays a crucial role.

Refer to Graphs 1-3 on pages 7-8 for specific ventilation air delivery rates based on different blade settings and duct static pressures. For applications without ductwork, utilizing return air filter grilles and supply grilles, a supply air static pressure of 0.00 is assumed.

Blade Adjustment for Desired Ventilation Air

The amount of ventilation air supplied by the commercial room ventilator depends on four primary factors:

  1. Return air duct static pressure drop.
  2. Supply air duct static pressure drop.
  3. Indoor blower motor speed.
  4. Damper blade open position setting.

To determine the correct blade setting for the required airflow, consult the appropriate graph on the following pages. Adjust the blade stop screws accordingly, as illustrated in Figure 3.

Note: The unit is shipped from the factory with the blade set in the #2 position, which provides approximately 100-150 CFM of fresh air.

Figure 3: Blade Adjustment for Desired Ventilation Air

Illustration shows the internal mechanism of the QCRV-F3. A "BLADE STOP SCREW" is visible and labeled as the component to "MOVE BLADE STOP SCREW TO SET AIRFLOW".

Balanced Climate™ Mode

The Balanced Climate™ mode is suitable for both duct-free and ducted applications where the total static pressure is below 0.2" W.C. ESP. When this mode is activated, the blade stop screw positions must be adjusted to allow approximately 28% more outdoor air to ensure minimum ventilation requirements are met.

Thermostat Connections

Detailed wiring diagrams are provided for connecting thermostats to the QCRV-F3 unit. These diagrams include specific instructions for both programmable and non-programmable thermostats, as well as notes regarding jumper installations and configuration settings.

Figure 1: Programmable Thermostat Connections for QCRV-F3 with Heat Pumps

This diagram illustrates the wiring between Completestat models #CS9B-THO or #CS9BE-THO, and the Bard #8403-060 thermostat, and the QCRV-F3 unit's low voltage terminal strip and 12-pin vent plug. It details connections for 24V, COM, G, Y1, Y2, O/B, W2, W1/E, L, A, D, GND terminals. Notes indicate factory-installed jumpers that may need to be removed for fire alarm circuits or to activate Balanced Climate™ mode, and the need for additional wiring for dehumidification models.

Figure 2: Non-Programmable Thermostat Connections for QCRV-F3 with Heat Pumps

This diagram shows wiring for various non-programmable thermostats (e.g., 8403-057, 8403-089, 8403-058, 8403-090) and humidistats (8403-038, 8403-047) to the QCRV-F3 unit. It covers connections to the unit's low voltage terminal strip and 12-pin vent plug. Notes provide guidance on installing jumper plugs, connecting to fire alarm circuits, and specific configuration changes required for certain thermostat models (e.g., 8403-058) to enable Balanced Climate™ mode or specific heating/cooling stages.

Ventilation Delivery Graphs

The following graphs illustrate the ventilation airflow (in CFM) delivered by different QCRV-F3 models at various damper positions under specific static pressure conditions.

Graph 1: Q24H4 CRV Ventilation Delivery

This graph plots Ventilation CFM on the Y-axis (0-800 CFM) against Damper Position on the X-axis (2-7). It shows the ventilation delivery for the Q24H4 model under constant CFM conditions ranging from .10 to .5 Static pressure.

Graph 2: Q30H4 CRV Ventilation Delivery

This graph plots Ventilation CFM on the Y-axis (0-800 CFM) against Damper Position on the X-axis (2-7). It shows the ventilation delivery for the Q30H4 model under constant CFM conditions ranging from 1.0 to .5 Static pressure.

Graph 3: Q36H4 CRV Ventilation Delivery

This graph plots Ventilation CFM on the Y-axis (0-800 CFM) against Damper Position on the X-axis (2-7). It shows the ventilation delivery for the Q36H4 model under constant CFM conditions ranging from .10 to .5 Static pressure.

Airflow Diagrams

The following figures illustrate the airflow paths within the QCRV-F3 unit under different operating conditions.

Figure 4: Call for Ventilation With or Without Compressor Operation

This diagram depicts the airflow when the unit is calling for ventilation. Return Air enters the unit and passes through an Air Filter and the Cooling Coil. Outdoor Air is drawn in through the Damper Blade, mixes with the return air, and then exits as Supply Air. Condenser Air is drawn through the Condenser Coil.

Figure 5: Call for Compressor or Fan Only with Ventilation Off

This diagram shows the airflow when the unit is operating for heating/cooling (compressor or fan only) with ventilation turned off. 100% Return Air enters the unit, passes through an Air Filter and the Cooling Coil, and exits as Supply Air. The Damper Blade is closed, preventing outdoor air intake. Condenser Air is drawn through the Condenser Coil.

Wiring Diagram

Figure 6: Wiring Diagram

This diagram illustrates the electrical connections for the QCRV-F3 unit. It details the wiring for the Damper Motor and the 12-PIN VENT PLUG. Connections are shown with specific wire colors (BLACK, BLACK/WHITE, PURPLE, RED, BROWN/WHITE, YELLOW) and terminal numbers (e.g., 6, 7, 3, 9, 1, 5, 2, 8, 4, 10, 11, 12) for both male and female connectors. It also includes reference numbers like '38' and '4056-258'.

Models: Bard, Q-TEC, Commercial, Room Ventilator, with, Spring Return, and, Exhaust

PDF preview unavailable. Download the PDF instead.

2100-741 Adobe PDF Library 15.0

Related Documents

Preview Bard BrightStat Air Conditioner/Heat Pump Room Controller: Advanced Programming & Setup Guide
A comprehensive guide to the advanced programming and user interface setup for the Bard BrightStat Air Conditioner/Heat Pump Room Controller. Learn about system modes, scheduling, network configurations, and detailed HVAC parameter settings.
Preview Bard 8403-060 Temperature and Humidity Controller with Ventilation Output
Bard 8403-060 Controller offers temperature, humidity, and ventilation control with an easy-to-use interface, programmable scheduling, and smart recovery mode for energy savings. This document details its features, specifications, and connections.
Preview Bard LV1000-300 Controller: Service and Installation Manual
Comprehensive service and installation guide for the Bard LV1000-300 Controller, detailing setup, operation, wiring, alarms, and troubleshooting for FUSION-TEC HR Series air conditioning systems.
Preview Bard CompleteStat™ CS9B/CS9BE Series Installation, Operation & Quick Start Guide
Comprehensive guide for installing, operating, and quickly starting Bard CompleteStat™ thermostats (models CS9B-THO, CS9B-THOC, CS9BE-THO, CS9BE-THOC). Includes installation, operation, terminal descriptions, and wiring diagrams for HVAC systems.
Preview Bard CHCRV-5A Commercial Room Ventilator Installation Instructions
Detailed installation guide for the Bard CHCRV-5A Commercial Room Ventilator with Exhaust, designed for use with Bard Single Stage Heat Pump Models C36H, C42H, C48H, and C60H. Covers unpacking, basic installation, sequence of operation, CO2 control, and blade adjustment.
Preview CompleteStat Controller Installation, Operation & Quick Start Guide
This guide provides instructions for the installation, operation, and quick start of the Bard CompleteStat Controller, including models CS9B-THOA, CS9BE-THOA, CS9B-THOCA, and CS9BE-THOCA. It covers basic setup, system selection, air conditioner and heat pump applications, fan and humidity settings, and setpoint adjustments.
Preview Bard WALL MOUNT, I-TEC, Q-TEC User Application Guide & Technical Overview
Comprehensive user application guide and technical product overview for Bard WALL MOUNT, I-TEC, and Q-TEC heating and cooling systems, covering installation, operation, maintenance, and troubleshooting.
Preview Bard I-TEC ERV Economizer Ventilator System Installation and Maintenance Guide
Comprehensive installation, operation, and maintenance guide for the Bard I-TEC ERV Economizer Ventilator System (Vent Code 'E'), including performance data, control wiring, and cleaning procedures.