OPERATION AND SERVICE INSTRUCTIONS
Q-TECTM Commercial Room Ventilator with Spring Return and Exhaust
Models: QCRV-F3
For Use with Bard Q-TEC Heat Pumps Models:
Q24H4-A,-B,-C Q30H4-A,-B,-C Q36H4-A,-B,-C Q24H4DA,B,C Q30H4DA,B,C Q36H4DA,B,C
Manufacturer: Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Website: www.bardhvac.com
Manual Number: 2100-741
Supersedes: NEW
Date: 9-17-20
Table of Contents
- Model Nomenclature: 3
- Description: 3
- Application: 3
- Blade Adjustment for Desired Ventilation Air: 6
- Balanced Climate™ Mode: 6
- Figures:
- Figure 1: Programmable Thermostat Connections for QCRV-F3 with Heat Pumps: 4
- Figure 2: Non-Programmable Thermostat Connections for QCRV-F3 with Heat Pumps: 5
- Figure 3: Blade Adjustment for Ventilation Air: 6
- Figure 4: Call for Ventilation With or Without Compressor Operation: 9
- Figure 5: Call for Compressor or Fan Only with Ventilation Off: 10
- Figure 6: Wiring Diagram: 11
- Graphs:
- Graph 1: Q24H4 CRV Ventilation Delivery: 7
- Graph 2: Q30H4 CRV Ventilation Delivery: 7
- Graph 3: Q36H4 CRV Ventilation Delivery: 8
Safety Precautions
WARNING: Electrical shock hazard. Disconnect remote electrical power supply or supplies before servicing. Failure to do so could result in electric shock or death.
WARNING: Exposed moving parts. Disconnect all electrical power before servicing. Failure to do so can result in severe injury or amputation.
CAUTION: Sharp metallic edges. Take care and wear appropriate protective devices to avoid accidental contact with sharp edges. Failure to do so can result in personal injury.
QCRV-F3 Features
- Exhaust air damper: Built-in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings.
- Actuator motor: 24 volt, power open, spring return with built-in torque limiting switch.
Model Nomenclature
The QCRV-F3 model designation breaks down as follows:
- QCRV: Q-TEC Commercial Room Ventilator
- F: Fixed (24V ON/OFF)
- 3: Chassis Size (3-2, 2.5 & 3 Ton)
Description
The Bard QCRV-F3 Commercial Room Ventilator is an electromechanical ventilation system designed to provide fresh outdoor air to meet indoor air quality standards. It is intended for use with specific Bard heat pump models as designated on the front page of this manual.
This unit features an internally mounted damper with exhaust capabilities, designed to supply up to 50% fresh air. The damper blade is powered by a 24 VAC motor that provides a power-open function and a spring-return action upon power loss. The damper opens when the 'A' terminal is energized. Ten different airflow settings can be achieved by adjusting the blade stop screws located under the fresh air blade.
When installed in compatible Bard heat pump models, the QCRV-F3 integrates exhaust provisions. As the damper blade opens to admit fresh air, it simultaneously opens an exhaust relief. This exhaust air is directed into the unit's condenser section, where the condenser fan assists in drawing it out during cooling or heat pump operation.
Application
The quantity of outside fresh air introduced into a structure by the QCRV-F3 is influenced by several factors within the duct system: return air duct static pressure, supply air duct static pressure, and indoor blower motor speed. The damper blade's open position setting also plays a crucial role.
Refer to Graphs 1-3 on pages 7-8 for specific ventilation air delivery rates based on different blade settings and duct static pressures. For applications without ductwork, utilizing return air filter grilles and supply grilles, a supply air static pressure of 0.00 is assumed.
Blade Adjustment for Desired Ventilation Air
The amount of ventilation air supplied by the commercial room ventilator depends on four primary factors:
- Return air duct static pressure drop.
- Supply air duct static pressure drop.
- Indoor blower motor speed.
- Damper blade open position setting.
To determine the correct blade setting for the required airflow, consult the appropriate graph on the following pages. Adjust the blade stop screws accordingly, as illustrated in Figure 3.
Note: The unit is shipped from the factory with the blade set in the #2 position, which provides approximately 100-150 CFM of fresh air.
Illustration shows the internal mechanism of the QCRV-F3. A "BLADE STOP SCREW" is visible and labeled as the component to "MOVE BLADE STOP SCREW TO SET AIRFLOW".
Balanced Climate™ Mode
The Balanced Climate™ mode is suitable for both duct-free and ducted applications where the total static pressure is below 0.2" W.C. ESP. When this mode is activated, the blade stop screw positions must be adjusted to allow approximately 28% more outdoor air to ensure minimum ventilation requirements are met.
Thermostat Connections
Detailed wiring diagrams are provided for connecting thermostats to the QCRV-F3 unit. These diagrams include specific instructions for both programmable and non-programmable thermostats, as well as notes regarding jumper installations and configuration settings.
This diagram illustrates the wiring between Completestat models #CS9B-THO or #CS9BE-THO, and the Bard #8403-060 thermostat, and the QCRV-F3 unit's low voltage terminal strip and 12-pin vent plug. It details connections for 24V, COM, G, Y1, Y2, O/B, W2, W1/E, L, A, D, GND terminals. Notes indicate factory-installed jumpers that may need to be removed for fire alarm circuits or to activate Balanced Climate™ mode, and the need for additional wiring for dehumidification models.
This diagram shows wiring for various non-programmable thermostats (e.g., 8403-057, 8403-089, 8403-058, 8403-090) and humidistats (8403-038, 8403-047) to the QCRV-F3 unit. It covers connections to the unit's low voltage terminal strip and 12-pin vent plug. Notes provide guidance on installing jumper plugs, connecting to fire alarm circuits, and specific configuration changes required for certain thermostat models (e.g., 8403-058) to enable Balanced Climate™ mode or specific heating/cooling stages.
Ventilation Delivery Graphs
The following graphs illustrate the ventilation airflow (in CFM) delivered by different QCRV-F3 models at various damper positions under specific static pressure conditions.
This graph plots Ventilation CFM on the Y-axis (0-800 CFM) against Damper Position on the X-axis (2-7). It shows the ventilation delivery for the Q24H4 model under constant CFM conditions ranging from .10 to .5 Static pressure.
This graph plots Ventilation CFM on the Y-axis (0-800 CFM) against Damper Position on the X-axis (2-7). It shows the ventilation delivery for the Q30H4 model under constant CFM conditions ranging from 1.0 to .5 Static pressure.
This graph plots Ventilation CFM on the Y-axis (0-800 CFM) against Damper Position on the X-axis (2-7). It shows the ventilation delivery for the Q36H4 model under constant CFM conditions ranging from .10 to .5 Static pressure.
Airflow Diagrams
The following figures illustrate the airflow paths within the QCRV-F3 unit under different operating conditions.
This diagram depicts the airflow when the unit is calling for ventilation. Return Air enters the unit and passes through an Air Filter and the Cooling Coil. Outdoor Air is drawn in through the Damper Blade, mixes with the return air, and then exits as Supply Air. Condenser Air is drawn through the Condenser Coil.
This diagram shows the airflow when the unit is operating for heating/cooling (compressor or fan only) with ventilation turned off. 100% Return Air enters the unit, passes through an Air Filter and the Cooling Coil, and exits as Supply Air. The Damper Blade is closed, preventing outdoor air intake. Condenser Air is drawn through the Condenser Coil.
Wiring Diagram
This diagram illustrates the electrical connections for the QCRV-F3 unit. It details the wiring for the Damper Motor and the 12-PIN VENT PLUG. Connections are shown with specific wire colors (BLACK, BLACK/WHITE, PURPLE, RED, BROWN/WHITE, YELLOW) and terminal numbers (e.g., 6, 7, 3, 9, 1, 5, 2, 8, 4, 10, 11, 12) for both male and female connectors. It also includes reference numbers like '38' and '4056-258'.