Hayward I-Komfort Inverter Swimming Pool Heat Pump
Installation & Instruction Manual
1. Preface
Thank you for purchasing the Hayward heat pump for swimming pools. The Hayward I-KOMFORT heat pump has been designed to strict manufacturing standards meeting the highest levels of quality required.
Hayward heat pumps offer exceptional performance throughout your bathing season by adapting wattage, power usage, and noise levels to the heating requirements of your swimming pool thanks to FULL INVERTER control logic.
Important Safety Information:
ⓘ Read the instructions in this manual carefully before using the device.
Hayward heat pumps are designed exclusively to heat swimming pool water; do not use this equipment for any other purpose.
This manual includes all the necessary information for installation, troubleshooting, and maintenance.
Read this manual carefully before opening the unit or doing any maintenance work on it. The manufacturer of this product shall on no account accept any liability for injury to a user or damage to the unit further to any errors made during installation, troubleshooting, or unnecessary maintenance. It is particularly important to follow the instructions given in this manual at all times.
Otherwise, the guarantee will be voided.
Safety Instructions
⚠ This device contains R32.
- Never use a refrigerant other than R32. Any other gaseous body mixed with R32 could cause abnormally high pressure and lead to a failure or pipes bursting and injuring people.
- During repairs or maintenance operations, use copper tubes that comply with Standard EN 12375-1 (May 2020) and the European Pressure Equipment Directive 97/23 / EC.
- As the heat pump is pressurized, never pierce the pipes or attempt any brazing. There is a risk of explosion.
- Never expose the device to flames, sparks, or other sources of ignition. It could explode and cause serious or even fatal injuries.
⚠ The heat pump is designed exclusively for installation outside buildings.
- If kept in storage, the heat pump should be kept in a well-ventilated room with a floor area of more than Amin(m²) as calculated by the following formula: Amin = (M/(2.5 x 0.22759 x h0))². M is the quantity of refrigerant in the device in kg, and h0 is the storage height. If stored on the floor, h0 = 0.6 m.
- The unit must be installed by qualified personnel.
- Do not install the heat pump on a support that risks intensifying the unit's vibrations.
- Make sure the support provided for the unit is strong enough to bear the weight of the unit.
- Do not install the heat pump anywhere liable to amplify its noise level or anywhere where its noise could disturb neighbours.
- All the electrical connections must be fitted by a professional qualified electrician in accordance with the standards in force in the country of installation, see §3.4.
- Shut off the main power supply and disconnecting switch before doing any electrical work. Forgetting to do so could cause electrocution.
- Before installing the unit, check that the earth cable is not cut or disconnected.
- Connect and properly tighten the power cable. A loose connection could damage electrical components.
- Exposing the heat pump to water or a humid atmosphere could cause electrocution. Be very careful.
- If you detect a fault or any abnormal situation, do not install the heat pump and contact your dealer immediately.
- All maintenance work should be done at the recommended intervals, as specified in this manual.
- Repairs must be carried out by qualified personnel.
- Only use OEM spare parts.
- Never use a cleaning method other than the one recommended in this manual.
Important information concerning the refrigerant used
This makes contains fluorinated greenhouse gases regulated by the Kyoto protocol. Do not release these gases into the atmosphere.
Type of refrigerant: R32
GWP(1) value: 675, based in the 4th report of the IPCC.
The quantity of refrigerant, based on the F-Gas regulation no. 517/2014, is stated on the unit's rating plate.
Period checks for leaks of refrigerant may be required by European or local legislation. Please contact your local dealer for more information.
(1) Global warming potential
2. Technical Specifications
2.1 Heat pump technical data
Models | I-KOMFORT | IKOMFORTRC700 | IKOMFORTRC900 | IKOMFORTRC1200 | IKOMFORTRC1700 | |
---|---|---|---|---|---|---|
Supply voltage | V | 220V-240V ~/1ph/50Hz | ||||
Refrigerant | R32 | |||||
Load | kg | 0.350 | 0.430 | 0.480 | 0.650 | |
Mass in kgCO2 | 0.24 | 0.29 | 0.32 | 0.44 | ||
Leak check frequency | No specific frequency, but an annual check is recommended | |||||
Min--Max heating capacity (a) | kW | 1.62--7.33 | 2.18--8.97 | 1.97--11.66 | 2.85--17.06 | |
Min--Max electric input power(a) | kW | 0.15--1.17 | 0.17--1.54 | 0.16--1.99 | 0.26--3.13 | |
Min--Max continuous current rating (a) | A | 1.15--5.32 | 1.27--6.91 | 1.08--8.96 | 1.41--13.69 | |
Max--Min continuous power (COP) (a) | 11.04--6.30 | 12.77--5.81 | 12.57--5.84 | 11.08--5.45 | ||
Min--Max heating capacity (b) | kW | 1.44--5.36 | 1.58--6.94 | 1.79--8.62 | 2.74--13.08 | |
Min--Max electric input power(b) | kW | 0.24--1.14 | 0.27--1.53 | 0.290--1.90 | 0.428--2.97 | |
Max--Min continuous power (COP) (b) | 5.98--4.69 | 5.82--4.53 | 6.17--4.52 | 6.40--4.40 | ||
Maximum continuous current | A | 6.4 | 8.4 | 10.9 | 16.6 | |
Fuse rating | aM | 8 | 10 | 16 | 20 | |
Circuit-breaker curve D | D | 8 | 10 | 16 | 20 | |
Starting current | A | < maximum continuous current | ||||
Hydraulic connection | mm | 50 mm | ||||
Nominal water flow (a) | m³/h | 3.10 | 3.80 | 4.90 | 7.30 | |
Max. loss of head on water | kPa | 2.3 | 2.9 | 6.4 | 6.7 | |
Compressor | Mitsubishi DC Inverter | Highly DC Inverter | ||||
Type | Twin rotary | Twin rotary | ||||
Quantity | 1 | 1 | ||||
Coil resistance at 20°C | Ohm | 1.91 | 0.788 | |||
Fan | Axial | Axial | ||||
Quantity | 1 | 1 | ||||
Diameter | mm | 405 | 510 | |||
Number of blades | 3 | 3 | ||||
Motor | DC Inverter | DC Inverter | ||||
Quantity | 1 | 1 | ||||
Rotation speed | rpm | 600--700 | 600--800 | 850--950 | 600--850 | |
Silent mode speed | rpm | 400 | 400 | 400 | 300 | |
Sound pressure level at 1 metre | dB(A) | 46,2 | 44,9 | 48,8 | 45,7 | |
Sound pressure level at 10 metres | dB(A) | 28,8 | 27,5 | 31,4 | 28,8 | |
Unit's net dimensions (L-W-H) | mm | 1040/425/615 | 1130/460/780 | |||
Weight | kg | 42 | 45 | 46 | 60 |
(a) Dry air 27°C - Relative humidity 78% - Water inlet temperature 26°C.
(b) Dry air 15°C - Relative humidity 71% - Water inlet temperature 26°C
2.2 Operating range
Use the swimming pool heat pump unit within the following ranges of temperature and humidity to ensure safe and efficient operation.
Heating mode ☀️ | Cooling mode ❄️ | |
---|---|---|
Outside temperature | -7°C - +35°C | +7°C - +43°C |
Water temperature | +12°C - +32°C | +8°C - +40°C |
Relative humidity | < 80% | < 80% |
Setting range from the set point | +15°C - +32°C | +8°C - +32°C |
⚠ If the temperature or humidity does not correspond to these conditions, the security measures could be activated and the swimming pool heat pump unit may no longer work.
⚠ The maximum heating temperature is set at 32°C to prevent damage to the liners. Hayward cannot be held responsible if used at a temperature above +32°C.
2.3 Dimensions
Models: IKOMFORTRC700 / IKOMFORTRC900 / IKOMFORTRC1200
B
Water outlet Ø 50 mm
C
D
Water inlet Ø 50 mm
E
A
F
IKOMFORTRC1700
B
Water outlet Ø 50 mm
C
D
Water inlet Ø 50 mm
E
G
A
F
Unit: mm
Size | Type(*) | IKOMFORTRC700 / IKOMFORTRC900 / IKOMFORTRC1200 | IKOMFORTRC1700 |
---|---|---|---|
A | 956 | 1002 | |
B | 360 | 415 | |
C | 605 | 767 | |
D | 350 | 350 | |
E | 98 | 101 | |
F | 545 | 615 | |
G | 380 | 442 |
3. Installation and Connection
3.1 Functional Diagram
Water outlet valve
Chlorinator cell (or other treatment)
Water outlet
By-pass valve
Water Inlet valve
Pool
Filter
Pump filtration
Note: The swimming pool heat pump unit is sold without any treatment or filtration equipment. The components presented in the diagram are spare parts to be supplied by the installer.
3.2 Heat pump unit
⚠ Place the heat pump outdoors and away from any enclosed technical space.
Placed under a shelter, the minimum required distances mentioned below must be respected in order to avoid any risk of air recirculation and a deficiency in the unit's overall performance.
Unit: mm
700mm
Air outlet
2500mm
500mm
Air inlet
700mm
300mm
3.3 Hydraulic connection
⚠ It is advised to install the unit on a dissociated cement block or a mounting bracket designed for this use and to set up the unit on the supplied rubber bushing (fastenings and washers not supplied).
The maximum installation distance between the unit and the swimming pool is 15 metres.
The total length of the piping to and from the unit is 30 metres.
Insulate both the above ground and buried hydraulic piping.
The heat pump must be installed at a minimum distance from the pool in compliance with NF C 15-100 (3.5 m from the water for France) or in compliance with installation standards applicable in other countries.
Do not install the heat pump close to a heat source.
For installation in snowy regions, we recommend sheltering the machine to avoid snow accumulating on the evaporator.
The unit is supplied with two 50 mm Ø union connections. Connect the water inlet to the heat pump coming from the filtration group then connect the water outlet to the heat pump at the water conduit going to the pool (see diagram below).
Water outlet Ø 50 mm
Water inlet Ø 50 mm
Install a by-pass valve between the heat pump entrance and exit.
⚠ If an automatic distributor or an electrolyser is used, it should be installed imperatively after the heat pump with the goal of protecting the titanium condenser against an elevated concentration of chemicals.
⚠ Be sure to install the by-pass valve and the supplied union connections at the water inlet and outlet level in order to simplify purging during the winter period and to facilitate access when disassembling for maintenance.
3.4 Electrical connection
⚠ Electrical installation and wiring for this equipment must be in conformity with local installation standards.
Country Code | Standard | Country Code | Standard |
---|---|---|---|
F | NF C15-100 | GB | BS7671:1992 |
D | DIN VDE 0100-702 | EW | EVHS-HD 384-7-702 |
A | ÖVE 8001-4-702 | E | MSZ 2364-702/1994/MSZ 10-553 1/1990 |
UNE 20460-7-702 1993, RECBT ITC-BT-31 2002 | H | MSA HD 384-7-702.S2 | |
IRL | Wiring Rules + IS HD 384-7-702 | PL | PN-IEC 60364-7-702:1999 |
I | CEI 64-8/7 | CZ | CSN 33 2000 7-702 |
LUX | 384.7.702 S2 | SK | STN 33 2000-7-702 |
NL | NEN 1010-7-702 | SLO | SIST HD 384-7-702.S2 |
P | RSIUEE | TR | TS IEC 60364-7-702 |
⚠ Verify that the available electrical power supply and the network frequency correspond to the required operating current taking into account the appliance's specific location, and the current required to supply any other appliance connected to the same circuit.
KOMFORTRC700 / IKOMFORTRC900 / IKOMFORTRC1200 / IKOMFORTRC1700
230V ~ +/- 10 % 50 Hz 1 Phase
See the corresponding wiring diagram in the appendix. The connection box is located on the right side of the unit. Three connections are designed for the power supply and two are for controlling the filter pump (Enslavement).
Wiring Diagram:
L = Live
N = Neutral
= = Ground
1 2 = Dry contact 16 A max, potential free, Priority heating function
Power supply 230V / 50Hz
⚠ The electrical power supply must have, when appropriate, a fuse protection device like a feed motor (aM) or D curve circuit breaker as well as a differential circuit breaker 30mA (see following table).
Models | IKOMFORTRC700 | IKOMFORTRC900 | IKOMFORTRC1200 | IKOMFORTRC1700 | |
---|---|---|---|---|---|
Power supply V/Ph/Hz | 230V 50Hz | 230V 50Hz | 230V 50Hz | 230V 50Hz | |
aM type fuse calibre | 8 aM | 10 aM | 16 aM | 20 aM | |
Curve D circuit breaker | 8 D | 10 D | 16 D | 20 D | |
Cable section | mm² | 3G 2,5 | 3G 2,5 | 3G 2,5 | 3G 4 |
⚠ Use an RO 2V/R 2V or equivalent power cord.
⚠ The cables sections are given for a maximum length of 25 m. They must however be checked and adjusted according to the installation conditions.
⚠ Always shut down the main power supply before opening the electrical control box.
3.5 Initial start-up
Start-up procedure - After installation is complete, follow these steps:
- Rotate the fans by hand to verify that they can turn freely by hand, and that the turbine is correctly affixed to the motor shaft.
- Ensure that the unit is connected correctly to the main power supply (see the wiring diagram in the appendix).
- Activate the filtration pump.
- Verify that all water valves are open and that the water flows toward the unit before switching on the heating or cooling mode.
- Verify that the drainage hose is correctly affixed and that it causes no obstructions.
- Activate the unit power supply, then press the On/Off button <0xE2><0x97><0x89> on the control panel.
- Make sure the alarm or lock symbols are not displayed. If need be, see the trouble-shooting guide (see § 6.4).
- Set the water flow using the by-pass valve (see § 3.6 and 2.1), as provided for by each model, to obtain an Entry/Exit temperature of 2°C.
- After running for several minutes, verify that the air exiting the unit is cool (between 5 and 10°).
- With the unit operating, turn off the filter pump. The unit should automatically turn off and display error code E03 (See § 6.4).
- Allow the unit and the pool pump to run 24 hours per day until the desired water temperature has been reached. When the set water inlet temperature is reached, the unit will turn off. It will automatically restart (as long as the pool pump is running) if the pool temperature is at least 0.5°C below the set temperature.
Water flow switch - The unit is equipped with a flow switch that turns on the heat pump when the pool filtration pump is running, and deactivates it when the filtration pump is out of order. If the water is low, the E03 alarm code will appear on the regulator (See § 6.4).
Time delay - The unit is equipped with a time delay of 3 minutes in order to protect the control circuit components, to eliminate restart cycling and contactor chatter. Thanks to this time delay, the unit automatically restarts approximately 3 minutes after each control circuit interruption. Even a brief power interruption will activate the restart time delay.
3.6 Water flow setting
With the water entry and exit valves being open, adjust the by-pass valve in order to obtain a difference of 2°C between the inflow and outflow temperature (see principle diagram § 3.1). You can verify the switch by seeing the entry/exit temperatures directly on the control panel.
HAYWARD Inlet Water 20.0 °C
Time 07:00 Temp Setting 28.0 °C Outlet Water 22.0 °C
Water inlet temperature
Water outlet temperature
Note: Opening the by-pass valve creates a weaker flow, which leads to an increase in ∆T. Closing the by-pass valve creates a stronger flow, which leads to a decrease in AT.
4. User Interface
4.1 General presentation
The heat pump is equipped with a digital control panel with a touch screen, electronically connected and pre-set at the factory in heating mode.
Control Panel Display Elements:
- 1. Water Input temperature
- 2. Defrost mode
- 3. Operating mode
- 4. Compressor's ON indicator
- 5. Lock screen
- 6. Alarm
- 7. Water Output temperature
- 8. On/Off/Back
- 9. Setpoint temperature
- 10. Hour
- 11. Operating mode selection
- 12. Adjust setpoint
- 13. Setting silence mode timer
- 14. Activate silent mode
- 15. Set date and time
- 16. Set On/Off timers
- 17. Access Advanced Settings
- 18. Access list of faults
- 19. Back (changes not confirmed)
- 20. Confirm
Mode Switching:
OFF mode: When the heat pump is idle (in standby mode), OFF is displayed on the screen. The black screen indicates that the heat pump is idle; settings can be adjusted in this mode.
ON mode: When the heat pump is running or priming (setpoint reached), the screen turns blue.
To switch from OFF to ON mode and vice versa, press the <0xE2><0x97><0x89> button.
4.2 Timer function settings
The date and time can be set either in ON or in OFF mode.
Press 1 times on <0xE2><0x97><0x89> to return to the main screen.
4.3 Setting the On/Off timers
Setting this function is necessary if you would like to run the heat pump for a shorter period than what is defined by the filtration clock. Therefore, you can program a deferred start and an anticipated stop or simply stop a certain timeframe from running (at night, for example).
It is possible to set one Start Timer and one Stop Timer. The setting step is "hour to hour".
Timer Settings:
- ON: 08:00
- OFF: 18:00
Blue highlighting = Activated
Grey = Deactivated
Press 2 times on <0xE2><0x97><0x89> to return to the main screen.
The setting step is "hour to hour". Once the Timer is activated, it is active 7 days a week.
4.4 Adjust setpoint
The setpoint can be changed either in ON or in OFF mode with an accuracy of 0.5°C.
⚠ It is recommended to never exceed 30°C to avoid alteration of the liners.
4.5 Locking and unlocking the touch screen
The screen can be locked or unlocked either in ON or in OFF mode.
Lock activated
Lock deactivated
4.6 SILENT function settings
Silence mode enables the heat pump to be used in economic and very silent mode when the heating needs are low (maintaining the pool temperature or need for ultra-silent operation). This function can be Activated/Deactivated manually or using a Timer.
Activation/Deactivation
Silent mode deactivated
Silent mode activated
Press 1 times on <0xE2><0x97><0x89> to return to the main screen.
Adjusting the SILENT mode Timer
5. Maintenance and Winterising
5.1 Maintenance
These maintenance operations must be carried out once per year in order to guarantee the longevity and the good working condition of the heat pump.
- Clean the coil with the help of a soft brush or jet of air or water (⚠ never use a high pressure cleaner).
- Verify that the drains flow well.
- Verify the tightening of the hydraulic and electrical connections.
- Verify the hydraulic sealing of the condenser.
- Have the leak-tightness of the cooling circuit to the leak detector checked by an accredited professional.
⚠ Before any maintenance operation, the heating pump must be disconnected from any electrical current source. The maintenance operations must only be carried out by personnel that is qualified and authorised to handle liquid refrigerants.
5.2 Winterising
- Put the heat pump in “OFF” mode.
- Cut the power supply to the heat pump.
- Empty the condenser with the help of the drain to avoid any risk of deterioration (high risk of freezing).
- Close the by-pass valve and unscrew the entry/exit connection unions.
- Eliminate the maximum amount of residual stagnant water from the condenser with the help of an air gun.
- Close the water entry and exit areas of the heating pump to avoid introducing foreign bodies.
- Cover the heating pump with a dedicated winterising case.
⚠ Any damage caused by poor winterising maintenance will lead to cancellation of the warranty.
6. Appendix
6.1 Electrical diagrams
IKOMFORTRC700 / IKOMFORTRC900 / IKOMFORTRC1200
Power supply 220-240V~/50Hz
Dry Contact 16 A max
REMARKS:
- AT: AIR TEMPERATURE SENSOR
- COMP: COMPRESSOR
- CT: EVAPORATOR TEMPERATURE SENSOR
- EEV: ELECTRONIC EXPANSION VALVE
- FM: FAN MOTOR
- FS: WATER FLOW SWITCH
- HP: HIGH PRESSURE SWITCH
- IT: WATER INLET TEMPERATURE SENSOR
- LP: LOW PRESSURE SWITCH
- OT: OUTLET WATER TEMPERATURE SENSOR
- SUT: SUCTION TEMPERATURE SENSOR
- 4V: 4 WAYS VALVE
- K2: DRY CONTACT 16 A MAX
- ET: DISCHARGE TEMPERATURE SENSOR
- : OPTION
IKOMFORTRC1700
Power supply 220-240V~/50Hz
Dry Contact 16 A max
REMARKS:
- AT : AIR TEMPERATURE SENSOR
- COMP : COMPRESSOR
- CT : EVAPORATOR TEMPERATURE SENSOR
- EEV : ELECTRONIC EXPANSION VALVE
- FM : FAN MOTOR
- FS : WATER FLOW SWITCH
- HP : HIGH PRESSURE SWITCH
- IT : WATER INLET TEMPERATURE SENSOR
- LP : LOW PRESSURE SWITCH
- OT : OUTLET WATER TEMPERATURE SENSOR
- SUT : SUCTION TEMPERATURE SENSOR
- 4V : 4 WAYS VALVE
- K2 : DRY CONTACT 16 A MAX
- ET : DISCHARGE TEMPERATURE SENSOR
- : OPTION
6.2 Heating priority wiring for monophasic pump
Power supply 230V~ / 50Hz
Terminals 1 and 2 deliver a potential-free dry contact, 230V~ / 50 Hz, no polarity.
Wire terminals 1 and 2 as indicated in the diagram above, to activate the operation of the filtration pump in 2-minute cycles each hour if the temperature of the pool is lower than the set point.
⚠ Never connect the power supply of the filtration pump directly to terminals 1 and 2.
Monophasic pump
Dry contact 16 A max
K2
L N 1 2
Power supply 230V~ / 50Hz
6.3 Exploded view and spare parts / Addendum
IKOMFORTRC700 / IKOMFORTRC900 / IKOMFORTRC1200 / IKOMFORTRC1700
Spare Parts List:
Mark | Description | Ref. | IKOMFORTRC700 | IKOMFORTRC900 | IKOMFORTRC1200 | IKOMFORTRC1700 |
---|---|---|---|---|---|---|
1 | Fan protection grille | HWX20000220245 | ✔️ | ✔️ | ✔️ | n/a |
HWX20000220369 | n/a | n/a | n/a | ✔️ | ||
2 | Fan blade | HWX301030000006 | ✔️ | ✔️ | ✔️ | n/a |
HWX301030000001 | n/a | n/a | n/a | ✔️ | ||
3 | Front panel | HWX80900099 | ✔️ | ✔️ | ✔️ | n/a |
HWX80900100 | n/a | n/a | n/a | ✔️ | ||
4 | Smoked Protection cover | HWX80900320 | ✔️ | ✔️ | ✔️ | ✔️ |
5 | LED Controller | HWX82300038 | ✔️ | ✔️ | ✔️ | ✔️ |
6 | Compressor | HWX20000110448 | ✔️ | ✔️ | ✔️ | n/a |
Compressor | HWX80100003 | n/a | n/a | n/a | ✔️ | |
7 | / | / | / | / | / | / |
8 | / | / | / | / | / | / |
9 | Titanium/PVC condenser | HWX80600037 | ✔️ | n/a | n/a | n/a |
HWX32012120061 | n/a | ✔️ | n/a | n/a | ||
HWX32012120056 | n/a | n/a | ✔️ | n/a | ||
HWX80600096 | n/a | n/a | n/a | ✔️ | ||
10 | Right panel | HWX80700445 | ✔️ | ✔️ | ✔️ | n/a |
HWX80700314 | n/a | n/a | n/a | ✔️ | ||
11 | Compressor aspiration sensor 5k-560mm | HWX83000044 | ✔️ | ✔️ | ✔️ | n/a |
Compressor aspiration sensor 5k-760mm | HWX83000053 | n/a | n/a | n/a | ✔️ | |
Ambiente temp sensor 5k-350mm | HWX83000049 | ✔️ | ✔️ | ✔️ | ✔️ | |
Water outlet sensor 5k-410mm | HWX83000050 | ✔️ | ✔️ | ✔️ | ✔️ | |
Water inlet sensor 5k-850mm | HWX83000052 | ✔️ | ✔️ | ✔️ | ✔️ | |
Compressor Discharge probe 50k-660mm | HWX83000026 | ✔️ | ✔️ | ✔️ | ✔️ | |
De-icing sensor 5k-680mm | HWX83000051 | ✔️ | ✔️ | ✔️ | n/a | |
De-icing sensor 5k-1040mm | HWX83000045 | n/a | n/a | n/a | ✔️ | |
12 | Access hatch | HWX320922029 | ✔️ | ✔️ | ✔️ | ✔️ |
13 | 4 ways valve | HWX20041437 | ✔️ | ✔️ | ✔️ | ✔️ |
14 | Filter ø9.7-ø9.7 (Ø19) | HWX20000140178 | ✔️ | ✔️ | ✔️ | n/a |
Filter ø9.7-ø9.7 (Ø28) | HWX20041444 | n/a | n/a | n/a | ✔️ | |
15 | T connector ø9.52-2 x ø6.35(T) x 1.0 | HWX30403000002 | ✔️ | ✔️ | ✔️ | ✔️ |
16 | Electronic expansion valve | HWX20000140570 | ✔️ | ✔️ | ✔️ | n/a |
HWX81000013 | n/a | n/a | n/a | ✔️ | ||
17 | T connector ø6.5-2 x ø6.5(T) x 0.75 | HWX20001460 | ✔️ | ✔️ | ✔️ | ✔️ |
18 | Water flow detector | HWX83000012 | ✔️ | ✔️ | ✔️ | ✔️ |
19 | Low pressure switch NO 0.30MPa/0.15MPa | HWX20000360157 | ✔️ | ✔️ | ✔️ | ✔️ |
20 | Pressure Tap 40mm 1/2" | HWX20000140150 | ✔️ | ✔️ | ✔️ | ✔️ |
21 | High pressure switch NC 3.2MPa/4.4MPa | HWX20013605 | ✔️ | ✔️ | ✔️ | ✔️ |
22 | / | / | / | / | / | / |
23 | / | / | / | / | / | / |
24 | Top cover | HWX80900055 | ✔️ | ✔️ | ✔️ | n/a |
HWX301090200806 | n/a | n/a | n/a | ✔️ | ||
25 | / | / | / | / | / | / |
26 | Motor bracket | HWX80700218 | ✔️ | ✔️ | ✔️ | n/a |
HWX80700248 | n/a | n/a | n/a | ✔️ | ||
27 | Fin coil | HWX301060202502 | n/a | n/a | n/a | n/a |
HWX80600042 | n/a | n/a | n/a | n/a | ||
HWX80600043 | n/a | n/a | n/a | n/a | ||
HWX80600044 | n/a | n/a | n/a | n/a | ||
28 | / | / | / | / | / | / |
16A 50Hz 5mH coil | HWX82500006 | ✔️ | ✔️ | n/a | n/a | |
29 | 20A 50Hz 5.2mH coil | HWX82500005 | n/a | n/a | n/a | n/a |
30 | Left panel | HWX80700446 | ✔️ | ✔️ | ✔️ | n/a |
HWX80700315 | n/a | n/a | n/a | n/a | ||
31 | DC ventilator motor | HWX80200018 | ✔️ | ✔️ | ✔️ | n/a |
HWX20000330132 | n/a | n/a | n/a | n/a | ||
32 | Printed circuit board Driver | HWX82300052 | ✔️ | ✔️ | n/a | n/a |
HWX82300007 | n/a | n/a | n/a | n/a | ||
33 | 230V/12VDC transformer | HWX82600008 | ✔️ | ✔️ | ✔️ | ✔️ |
34 | Terminal block L-N-GND -5 connections 4mm² | HWX40003901 | ✔️ | ✔️ | ✔️ | ✔️ |
35 | K2 relay | HWX20000360297 | ✔️ | ✔️ | ✔️ | ✔️ |
6.4 Troubleshooting guide
⚠ Certain operations must be carried out by an authorized technician.
If a fault occurs on the heat pump ⚠ appears in the top left-hand corner of the screen. Refer to following table.
Error Codes and Descriptions:
Problem | Error codes | Description | Solution |
---|---|---|---|
Water inlet sensor fault | P01 | The sensor is open or has short-circuited. | Verify the CN21/RES1 connectors on the board and the extension connector or replace the sensor. |
Water outlet sensor fault | P02 | Verify the N22/RES2 connectors on the board and the extension connector or replace the sensor. | |
Outside temperature sensor fault | P04 | The sensor is open or has short-circuited. | Verify the CN12/PH connectors on the board and the extension connector or replace the sensor. |
De-icing sensor fault | P05 | Verify the CN8/OPT connectors on the board and the extension connector or replace the sensor. | |
Compressor aspiration sensor select | P07 | Verify the CN7/OAT connectors on the board and the extension connector or replace the sensor. | |
Compressor discharge sensor fault | P081 | Verify the CN9/OHT connectors on the board and the extension connector or replace the sensor. | |
High pressure protection | E01 | The sensor is open or has short-circuited. | Verify the CN30/HP connectors on the card or replace the sensor. Check the water flow. Check the water flow detector. Check the valve opening. Check the by-pass. Check the evaporator is not clogged. Water temperature too hot. Incondensable problem after maintenance, empty and evacuate the cooling circuit. Fluid load too high, remove fluid into a liquid bottle. |
Low pressure protection | E02 | The sensor is open or has short-circuited. | Check the Al/D103 connections on the card or replace the sensor. Large coolant leak, search for the leak with the detector. Air flow too low, check the ventilator rotation speed. Check the evaporator is not clogged, clean its surface. |
Flow sensor fault | E03 | The sensor is open or has short-circuited. | Check the Al/D102 connections on the card or replace the sensor. Lack of water, check the filtration pump operation. Check the stop valve opening. Check the by-pass adjustment. |
Input/Output temperature difference > 13°C | E06 | Applicable in Cold mode only | Lack of water, check the filtration pump operation. Check the stop valve opening. Check the by-pass adjustment. |
Antifreeze protection Cold mode | E07 | Water output temperature < 4°C | Stop the heat pump, empty the condenser risk of freezing. |
Communication problem | E08 | No communication between the printed circuit board and the user interface | Check the connectors - see the wiring diagram. |
Level 1 antifreeze protection | E19 | 2°< Water temperature < 4° and Air temperature < 0° | Stop heat pump operation, empty the condenser to avoid freezing, by default the heat pump starts the filtration pump to avoid icing over. |
Level 2 antifreeze protection | E29 | Water temperature < 2° and Air temperature < 0° | Stop heat pump operation, empty the condenser to avoid freezing, by default the heat pump starts the filtration pump and the heat pump to avoid icing over. |
Fan motor fault | F031 | Motor jammed or faulty connection | Check free rotation; check CN97/DC connectors; replace the motor. |
Fan motor fault | F051 | Faulty connection | Check the DCFAN/CN97 connector; replace the motor. |
Exterior temperature too low | TP | Operating limit reached | Stop the heat pump. |
⚠ When the problem is resolved, the error is automatically acknowledged and the triangle disappears.
- To delete the error list, press on Del
- Press 2 times on <0xE2><0x97><0x89> to return to the main screen.
6.5 Warranty
WARRANTY CONDITIONS
All HAYWARD products are guaranteed to be free from manufacturing or material faults for a period of two years as from the date of purchase. Any claim made under the terms of the warranty must be accompanied by a dated proof of purchase. We therefore recommend that you keep your invoice.
The HAYWARD warranty is limited to the repair or replacement, at HAYWARD's discretion, of faulty products, provided they have been used under normal conditions, as described in their user guide, and that the product has not been modified in any way and has been used only with HAYWARD components and parts. Frost and chemical damage are not covered.
No other costs (transportation, labour, etc.) are covered by the warranty.
HAYWARD cannot be held liable for any direct or indirect damage caused by the incorrect installation, connection or operation of a product.
Please contact your retailer if you want to make a claim under the terms of the warranty and request the repair or replacement of an item. No equipment returned to our factory will be accepted without our prior written agreement.
Worn parts are not covered by the warranty.