Kohler RXT Automatic Transfer Switch

Model: RXT, 100-400 Amps

Product Overview

The Kohler Model RXT automatic transfer switch is designed for use with Kohler® generator sets equipped with the RDC2 generator set/transfer switch controller. The transfer switch operation is controlled by the RDC2 controller.

Available Models

A range of RXT models are available, including:

Refer to page 7 for a comprehensive list of available models.

Standard Features

Interface Boards

Standard Interface Board

Connects to the Model RDC2 generator set/transfer switch controller. Includes a load control contact with a 5-minute time delay for starting selected loads after transfer to the emergency source, suitable for large motor loads.

Combined Interface/Load Management Board

An optional board that replaces the standard interface board. Available on single-phase standard and service entrance models (not on 3-phase or load center models). This board automatically manages up to six residential loads:

Load Management Features:

Priority Setting:

Viewing Load Shed Outputs with OnCue® Plus:

Current Transformer (CT):

The combined load management board option includes a 400 amp CT for load monitoring. Larger diameter CTs (400A or 500A) are available for specific applications. See the table below for specifications.

Current Transformer Specifications
Ratio (Amps:VAC) Outer Diameter mm (in.) Inner Diameter mm (in.) Service Part Number Sales Kit Part Number CT Availability
400:3 63.5 (2.5) 28.7 (1.13) GM83929 N/A Included with combined board
400:3 111.8 (4.4) 57.2 (2.25) GM17250 GM17250-KP1-QS Sold Separately
500:3 171.5 (6.75) 108.0 (4.25) GM60264 GM17250-KP2-QS Sold Separately (use with 60RCL)

Load Shed Specifications:

Load Shed Connections and Ratings
Connection Rating Connection Type
Pilot Relays* 125VAC, 10 A total (general purpose)
120VAC, 125VA (pilot duty)
#12-20 AWG
HVAC Relays (qty. 2) 125VAC, 10 A (general purpose)
120VAC, 125VA (pilot duty)
#12-20 AWG
RBUS Communication and Power Connections to the RDC2 controller 0.5 A @ 12 VDC Use Belden #9402 or equivalent 20 AWG shielded, twisted-pair communications cable †

* Four (4) pilot relays for customer-supplied normally closed load-switching contactors/relays. Total current draw for four relays cannot exceed 10 amps. Kohler® power relay modules recommended.

† For long distances, use equivalent shielded, twisted-pair cable for RBUS and individual 12-20 AWG wires (qty. 2) for power connections.

Codes and Standards

The ATS meets or exceeds the requirements of the following specifications:

Specifications

Standard Interface Board Specifications

Description Details
Controller interface connections A and B #20 AWG shielded twisted-pair, Belden 9402 or 8762 or equivalent
Controller interface connections PWR and COM #12-20 AWG (see ATS Installation Manual)
Load control contact rating 10 A @ 250 VAC
Load control connections #12-18 AWG

For combined interface/load management board specifications, see page 3.

Environmental Specifications

Parameter Value
Operating temperature -20°C to 70°C (-4°F to 158°F)
Storage temperature -40°C to 85°C (-40°F to 185°F)
Humidity 5 to 95% noncondensing

Contact Ratings

Parameter Rating
Engine start 10 A @ 32 VDC (SPST normally closed)
Load control 10 A @ 125 VAC (SPST normally open)

Auxiliary Position-Indicating Contacts

Model Number of contacts (Normal, Emergency) Contact Rating
100-200A 1 Ph 1, 1 Optional 15 A @ 250VAC
100-200 A 1 Ph SE 1, 1 Optional 15 A @ 250VAC
300-400 A 1 Ph SE 2, 2 Standard
1, 1 Optional
10 A @ 480 VAC
400 A 1 Ph and 3Ph/3P 2, 2 Standard
1, 1 Optional
10 A @ 480 VAC
400 A 3Ph/4P 8, 8 Standard 10 A @ 480 VAC

Cable Sizes (AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections)

Switch Size, Amps Switch Ph. Range of Wire Sizes, Cu/Al (per phase) Neutral Ground
Normal Emergency and Load
100 1 (Standard) (1) #14 - 1/0 AWG (1) #14 - 1/0 AWG (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al)
1 (12- or 16-space load center (NEMA 1)) (1) #14 - 1/0 AWG Emerg: (1) #14 – 1/0 AWG
Load: per customer-supplied circuit breaker
(26) #4 - 14 AWG or (2) #14 - 1/0 AWG or (1) #6 - 2/0 AWG (9) #6-#14 AWG or (4) #14 - 1/0 AWG
1 (16-space load center (NEMA 3R)) (1) #14 - 1/0 AWG (1) #14 - 1/0 AWG (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al)
100 Service Entrance 1 (1) #12 - 2/0 AWG (1) #14 - 1/0 AWG (26) #4 - 14 AWG or (2) #14 - 1/0 AWG or (1) 2/0 AWG
150 Service Entrance 1 (1) #14 - 4/0 AWG (1) #14 - 4/0 AWG (3) #14 - 1/0 AWG
200 Service Entrance 1 (1) #4 - 300 KCMIL (1) #6 - 250 KCMIL (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al)
200 Standard 1 (1) #6 AWG - 250 KCMIL (1) #6 - 250 KCMIL (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al)
3 (3-Phase) (1) #14 - 4/0 AWG (1) #14 - 4/0 AWG (3) #14 - 1/0 AWG
300 Service Entrance 1 (1) #1 - 600 KCMIL or (2) #1 - 250 KCMIL (2) 1/0 - 250 KCMIL or (1) #4 - 600 KCMIL (12) 1/0 - 250 KCMIL or (6) #4 AWG - 600 KCMIL (6) #6 - 3/0 AWG
400 Standard 1 (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL (3) #4 AWG – 600 KCMIL or (6) 1/0 AWG – 250 KCMIL
3 (3-Phase) (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL (3) #4 AWG – 600 KCMIL or (6) 1/0 AWG – 250 KCMIL

Note: Data is subject to change. Refer to transfer switch dimension drawings and wiring diagrams for planning and installation.

Withstand and Close-On Ratings (WCR)

Service Entrance Transfer Switch Ratings

The service entrance transfer switch is factory-equipped with a normal source disconnect circuit breaker. Suitable for controlling motors, electric discharge lamps, tungsten filament lamps, and electric heating equipment, provided the sum of motor full-load ampere ratings and other load ampere ratings does not exceed the switch rating, and tungsten load does not exceed 30% of switch rating.

Switch Rating, Amps * WCR, RMS Symmetrical Amps at 240 VAC
100, 150, 200 22,000
300, 400 35,000

* Continuous load current not to exceed 80% of switch rating.

Contactor Ratings with Coordinated Circuit Breakers

Single-phase transfer switches are UL listed at 240 VAC maximum. Three-phase transfer switches are rated at 480 VAC maximum. The following tables list contactor withstand current ratings (WCR) for 100-400 ampere non-service entrance rated switches with specific manufacturer's circuit breakers per UL and Canadian safety standards. These are suitable for controlling motors, electric discharge lamps, tungsten filament lamps, and electric heating equipment, provided the sum of motor full-load ampere ratings and other load ampere ratings does not exceed the switch rating, and tungsten load does not exceed 30% of switch rating.

The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes maximum shown in the tables below, but no greater than the interrupting capacity of the selected breaker.

WCR Ratings with Specific Manufacturer's Molded-Case Circuit Breakers (100-200 Amps)

Switch Rating, Amps Voltage, max. Number of Poles/ Phases WCR, RMS Symmetrical Amps Manufacturer Type or Class Maximum Size, Amps
100 240 2 pole/ 1 phase 10,000 Any Breaker * Any Breaker (0.025 seconds max.)
150,000 Square D HR 250
125,000 HL 150
100,000 BJ, HJ 125
65,000 BG, HG 125
240 3 phase 42,000 QG, QJ 125
25,000 HD 150
22,000 GE BD 125
85,000 THED 150
100 480 3 phase 50,000 Square D HL, HR 150
35,000 BJ 125
18,000 HG, HJ 150
BG 125
BD, HD 125
150 / 200 240 2 pole/ 1 phase 10,000 Any Breaker * Any Breaker (0.025 seconds max.)
200,000 Square D JR 250
125,000 JL 250
100,000 JJ 250
65,000 JG 250
240 3 phase 42,000 QG, QJ 225
25,000 JD 250
85,000 Square D JL, JR 250
30,000 JG, JJ 250
18,000 JD 250

* For higher WCR values, contact the factory for additional specific breaker ratings.

WCR Ratings with Specific Manufacturer's Molded-Case Circuit Breakers (300-400 Amps)

Switch Rating, Amps Voltage, max. Number of Poles/ Phases WCR, RMS Symmetrical Amps Manufacturer Type or Class Maximum Size, Amps
300 / 400 240 1 phase 65,000 GE THLC4 350
42,000 Eaton/Cutler Hammer HMC 800
300 / 400 480 3 pole/ 3 phase 65,000 GE THLC4 350
42,000 Eaton/Cutler Hammer HMC 800
400 240 4 pole/ 3 phase 65,000 GE THKM3F 1200
GE THQMV 225
GE SGL1, SGL4, SGL6, SGP1, SGP4, SGP6 600
Eaton/Cutler Hammer LDC, CLDC, HLD, CHLD 600
Square D LJ, LL, LR 600
Square D QG, QJ 250
Siemens/ITE HLD6, HLXD6 600
Siemens/ITE JGH, JGC, NHH 250
Eaton/Cutler Hammer HKD, CHKD, KDC, HKDB, CHKDB, LHH 400
Eaton/Cutler Hammer CHLD, LDC, CLDC, LGH*, LGC*, LGU*, LGX* 600
Eaton/Cutler Hammer MDL, CMDL, HMDL, CHMDL, NGS, NGH, NGC, MDLB, CMDLB, HMDLB, CHMDLB 800
Eaton/Cutler Hammer NGU 1600
GE TBC4 400
GE TBC6, TJL4V, TJL1S-6S, SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGN, FGH, FGL, FGP 600
GE TBC8, TKL4V, TKH8S-12S, TKL8S-12S, SKH8, SKL8, SKP8, TB8 800
Siemens/ITE HFD6, HFXD6, HFG, LFG 250
400 480 4 pole/ 3 phase 50,000 Siemens/ITE HJD6, HJXD6, SHJD6, HHJD6, HHJXD6, CJD6, SCJD6, HJG, LLG, LJG 400
Siemens/ITE HLD6, HLXD6, SHLD6, HHLD6, HHLXD6, CLD6, SCLD6, HLG 600
Eaton/Cutler Hammer LMD6, LMXD6, HLMD6, HLMXD6, MD6, MXD6, HMD6, HMXD6, SMD6, SHMD6, CMD6, SCMD6, HMG, LMG 800
Square D CK400N, CK400NN, CK400H, CK400HH, CJ400L, NSJ400 400
Square D LC, DJ, DL, LJ, LL, LR, LI, NSJ600 600
Square D CK800N, CK800NN, CK800H, CK800HH, MJ 800
Square D CK1000HH 1000
Square D PK, PJ, PL, MH, MasterPact STR 28D, CK1200HH 1200

* With Digitrip 310+ LS or LSG Inst. Override set to 12X.

Dimensions and Weights

Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See the Operation/Installation Manual or your local distributor for dimension drawings. Transfer switch weights and dimensions shown in the table do not include packaging. To estimate the shipping weight, add 3 kg (5 lbs.) or 10% (whichever is larger) to the weight shown.

A diagram illustrating the H (Height), W (Width), and D (Depth) dimensions is shown above the table.

Amps Description Dimensions, H x W x D, mm (in.) † Weight ‡ kg (lb.) Dimension Drawing
100 Single phase 623 x 335 x 180 (24.5 x 13.2 x 7.1) 7 (15) ADV-8688
With 12-space load center (NEMA 1) 610 x 330 x 154 (24.0 x 13.0 x 6.0) 12 (26) ADV-9186
With 16-space load center (NEMA 1) 610 x 330 x 154 (24.0 x 13.0 x 6.0) 12 (26) ADV-9187
With 16-space load center 614 x 335 x 180 (24.2 x 13.2 x 7.1) 8 (18) ADV-9188
100 Three phase 3-pole 673 x 462 x 228 (26.5 x 18.2 x 9.0) 15 (33) ADV-9755
Three phase 4-pole 673 x 462 x 228 (26.5 x 18.2 x 9.0) 15 (33) ADV-9755
Service entrance (ASE) 734 x 416 x 175 (28.9 x 16.4 x 6.9) 10 (22) ADV-9046
Service entrance (CSE) 754 x 416 x 175 (29.7 x 16.4 x 6.9) 14 (30) ADV-8797
150 Service entrance (ASE) 734 x 416 x 175 (28.9 x 16.4 x 6.9) 12 (26) ADV-9046
Service entrance (ASE) 734 x 416 x 175 (28.9 x 16.4 x 6.9) 12 (26) ADV-9046
200 Service entrance (CSE) 754 x 416 x 175 (29.7 x 16.4 x 6.9) 16 (36) ADV-8798
Single phase 623 x 335 x 180 (24.5 x 13.2 x 7.1) 7 (15) ADV-8688
Three phase 673 x 462 x 228 (26.5 x 18.2 x 9.0) 15 (33) ADV-9755
300 Service entrance 1452 x 629 x 329 (57.2 x 24.8 x 12.9) 59 (130) ADV-9768
400 Single phase 1222 x 610 x 343 (48.1 x 24.0 x 13.5) 45 (100) ADV-9756
3-Pole 1222 x 610 x 343 (48.1 x 24.0 x 13.5) 47 (104) ADV-9756
4-Pole 1702x 610 x 514 (67.0 x 24.0 x 20.2) 188 (414) ADV-9757
Service entrance 1452 x 629 x 329 (57.2 x 24.8 x 12.9) 59 (130) ADV-9768

† Depth does not include the padlock hasp on the front of the enclosure.

‡ Transfer switch weights are approximate and do not include packaging.

Note: Enclosures are type NEMA 3R except as noted.

Accessories

Available Models Summary

All Model RXT transfer switches are standard-transition 60 Hz automatic transfer switches. Letters in parentheses refer to the model designation code described on the last page.

Amps Description (Connections) Voltages Poles Phases WCR § RMS Symmetrical Amps
100 Standard (A) 240 (F) 2 (N) 1 10,000
Standard, with 16-space load center (B) 240 (F) 2 (N) 1 10,000
Standard, with 12-space load center ** 240 (F) 2 (N) 1 10,000
Service entrance (ASE, CSE) 240 (F) 2 (N) 1 22,000
150 Standard, 3-phase (A) 208 (C), 240 (F), 480 (M) 3 (T) or 4 (V) 3 10,000
Service entrance (ASE) 240 (F) 2 (N) 1 22,000
200 Standard (A) 240 (F) 2 (N) 1 10,000
Service entrance (ASE, CSE) 240 (F) 2 (N) 1 22,000
300 Standard, 3-phase (A) 208 (C), 240 (F), 480 (M) 3 (T) or 4 (V) 3 10,000
Service entrance (ASE, CSE) 240 (F) 2 (N) 1 35,000
400 Standard (A) 240 (F) 2 (N) 1 35,000
Service entrance (ASE, CSE) 240 (F) 2 (N) 1 35,000
Standard, 3-phase (A) 208 (C), 240 (F), 480 (M) 3 (T) or 4 (V) 3 42,000 @ 480V
65,000 @ 240 V

§ Withstand and close-on rating. See pages 3-5 for WCR information and specific breaker ratings.

W With 16-space load center and NEMA 1 or NEMA 3R enclosure. Up to 8 tandem breakers can be used, for a maximum of 24 circuits.

** GM85273-SA_ with 12-space load center and NEMA 1 enclosure.

Note: Combined interface board is available on single-phase standard or service entrance models. (Not available on 3-phase or load center models.)

Model Designation

The transfer switch model designation defines ratings and characteristics. Below is an explanation of the components:

Sample Model Designation: RXT-JFNC-0200A

Component Description
Model
RXT
Kohler Automatic Transfer Switch
Controls
J
Interface for RDC2 Controller (standard or combined interface/load management)
Voltage/Frequency
C
F
M
208 Volts/60 Hz (3-phase only)
240 Volts/60 Hz
480 Volts/60 Hz (3-phase only)
Number of Poles/Wires
N
T
V
2-pole, 3-wire, solid neutral (120/240 V only)
3-pole, 4-wire, solid neutral
4-pole, 4-wire, switched neutral
Enclosure
A
C
NEMA 1 *
NEMA 3R
* NEMA 1 enclosure is available on 100 amp load center models only.
Current Rating
0100
0150
0200
0300
0400
100 amps
150 amps
200 amps
300 amps
400 amps
Connections
A
B
ASE
CSE
No load center
With load center (100 amp single-phase only)
Service entrance rated
Service entrance rated with CSA certification (not available for 150 amp models)

Contact Information

KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444
KOHLERPower.com

Disclaimer

Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler® generator distributor for availability.

©2021 Kohler Co. All rights reserved.

PDF preview unavailable. Download the PDF instead.

Spec Sheet RXT-JFNC-0100A-QS2 Acrobat Distiller 21.0 (Windows)

Related Documents

Preview Kohler RXT Automatic Transfer Switch: Features, Specifications, and Ratings
Comprehensive details on the Kohler RXT Automatic Transfer Switch (100-400 Amps), including features, technical specifications, environmental and interface module data, cable sizing, withstand and close-on ratings, dimensions, weights, and model designation.
Preview Kohler RXT Automatic Transfer Switch: Features, Specifications, and Models
Comprehensive overview of the Kohler RXT Automatic Transfer Switch (100-400 Amps), detailing standard features, available models, interface boards, specifications, dimensions, and model designation for standby power systems.
Preview Kohler RXT Automatic Transfer Switch: Features, Specs, and Models (100-400 Amps)
Explore the Kohler RXT Automatic Transfer Switch, a reliable solution for automatic power transfer. This document details features, specifications, available models, dimensions, and ratings for the 100-400 Amp range.
Preview Kohler Automatic Transfer Switches Product Guide
A comprehensive product guide detailing Kohler's Automatic Transfer Switches (ATS), including custom configuration options, controller features (MPAC1200, MPAC1500), and different ATS types like Standard, Bypass-Isolation, and Service-Entrance.
Preview Kohler RXT Automatic Transfer Switch: Features, Specifications, and Ratings
Detailed information on the Kohler RXT Automatic Transfer Switch, including standard features, technical specifications, environmental conditions, cable sizes, withstand and close-on ratings, dimensions, weights, and available models. Designed for use with Kohler RDC2/DC2 generator sets.
Preview Kohler RDT Automatic Transfer Switch: Features, Specifications, and Model Guide
Comprehensive guide to Kohler RDT Series Automatic Transfer Switches (100-400 Amps), detailing features, environmental specifications, contact ratings, time delays, cable sizes, withstand ratings, codes, dimensions, accessories, and model designation.