Product Overview
The Kohler Model RXT automatic transfer switch is designed for use with Kohler® generator sets equipped with the RDC2 generator set/transfer switch controller. The transfer switch operation is controlled by the RDC2 controller.
Available Models
A range of RXT models are available, including:
- 100, 200, and 400 amp standard and service entrance models.
- 150 and 300 amp service entrance models.
- Single-phase standard and service entrance models with an optional combined interface/load management board (not available on 3-phase or load center models).
- 100 amp standard single-phase models with or without a 16-space load center (up to 8 tandem breakers for 24 circuits).
- A 100 amp standard single-phase model with a 12-space load center and a NEMA 1 enclosure (GM85273-SA_).
Refer to page 7 for a comprehensive list of available models.
Standard Features
- Allows utility voltage display on the RDC2 generator set/transfer switch controller (exclusive to Kohler® residential and light commercial generator sets).
- UL listed (UL 1008 listed, file #E58962).
- Models with load centers use UL 67 listed components.
- CSA certification (file #LR58301) available for standard ATS without load center (single and three-phase) and service entrance ATS (100, 200, 300, 400 amp models).
- Corrosion-resistant NEMA 3R aluminum enclosure.
- Padlockable.
- Approved for indoor or outdoor installation.
- ANSI 49 gray finish.
- NEMA 1 enclosure available on 100 amp load center models.
- Electrically and mechanically interlocked contactor.
- Double throw inherently interlocked design.
- Manually operable contactor for maintenance.
- Silver alloy main contacts.
- Transfer switches are 100% equipment rated for application at rated current without derating (non-service entrance models).
- Service entrance models include a disconnect circuit breaker on the utility (normal) source side (80% rated).
- Five-year limited warranty.
Interface Boards
Standard Interface Board
Connects to the Model RDC2 generator set/transfer switch controller. Includes a load control contact with a 5-minute time delay for starting selected loads after transfer to the emergency source, suitable for large motor loads.
Combined Interface/Load Management Board
An optional board that replaces the standard interface board. Available on single-phase standard and service entrance models (not on 3-phase or load center models). This board automatically manages up to six residential loads:
- Up to four customer-supplied power relay modules can be connected for management of non-essential secondary loads.
- Two HVAC relays are included for control of two independent air conditioner loads.
Load Management Features:
- Disconnects non-critical loads to prevent generator overload (complies with NEC).
- Monitors generator current and frequency to add or shed loads, preventing frequency drops that can damage electronics.
- Allows the use of a smaller generator set.
- Loads are added/shed based on generator capacity.
- Dynamic logic prevents unnecessary shedding of important loads during startup of air conditioning, refrigerators, or water pumps (patent pending).
- Smart power management through communication between the load management board and generator.
- Load shed power level and frequency setpoints are adjustable via Kohler® SiteTech™ software (available to authorized distributors/dealers).
Priority Setting:
- Loads are added and shed according to priority (Load 1 is highest, Load 6 is lowest).
- Less critical loads can be automatically turned off when essential appliances are running.
- Load priorities are hard-wired at installation.
Viewing Load Shed Outputs with OnCue® Plus:
- Use Kohler's OnCue® Plus Generator Management System (sold separately) to view load status (On/Off) and remotely monitor load shedding/adding.
- Load shed outputs can be labeled in OnCue® Plus.
Current Transformer (CT):
The combined load management board option includes a 400 amp CT for load monitoring. Larger diameter CTs (400A or 500A) are available for specific applications. See the table below for specifications.
Ratio (Amps:VAC) | Outer Diameter mm (in.) | Inner Diameter mm (in.) | Service Part Number | Sales Kit Part Number | CT Availability |
---|---|---|---|---|---|
400:3 | 63.5 (2.5) | 28.7 (1.13) | GM83929 | N/A | Included with combined board |
400:3 | 111.8 (4.4) | 57.2 (2.25) | GM17250 | GM17250-KP1-QS | Sold Separately |
500:3 | 171.5 (6.75) | 108.0 (4.25) | GM60264 | GM17250-KP2-QS | Sold Separately (use with 60RCL) |
Load Shed Specifications:
Connection | Rating | Connection Type |
---|---|---|
Pilot Relays* | 125VAC, 10 A total (general purpose) 120VAC, 125VA (pilot duty) |
#12-20 AWG |
HVAC Relays (qty. 2) | 125VAC, 10 A (general purpose) 120VAC, 125VA (pilot duty) |
#12-20 AWG |
RBUS Communication and Power Connections to the RDC2 controller | 0.5 A @ 12 VDC | Use Belden #9402 or equivalent 20 AWG shielded, twisted-pair communications cable † |
* Four (4) pilot relays for customer-supplied normally closed load-switching contactors/relays. Total current draw for four relays cannot exceed 10 amps. Kohler® power relay modules recommended.
† For long distances, use equivalent shielded, twisted-pair cable for RBUS and individual 12-20 AWG wires (qty. 2) for power connections.
Codes and Standards
The ATS meets or exceeds the requirements of the following specifications:
- Underwriters Laboratories UL 1008, Standard for Automatic Transfer Switches for Use in Emergency Systems, file #E58962.
- Underwriters Laboratories UL 508, Standard for Industrial Control Equipment.
- CSA certification (file #LR58301) available for select models (not for 150, 300, or 400 amp service entrance or 100 amp load center models). Must be selected at order.
- NFPA 70, National Electrical Code.
- NFPA 110, Emergency and Standby Power Systems.
- NEMA Standard IC10-1993, AC Automatic Transfer Switches.
Specifications
Standard Interface Board Specifications
Description | Details |
---|---|
Controller interface connections A and B | #20 AWG shielded twisted-pair, Belden 9402 or 8762 or equivalent |
Controller interface connections PWR and COM | #12-20 AWG (see ATS Installation Manual) |
Load control contact rating | 10 A @ 250 VAC |
Load control connections | #12-18 AWG |
For combined interface/load management board specifications, see page 3.
Environmental Specifications
Parameter | Value |
---|---|
Operating temperature | -20°C to 70°C (-4°F to 158°F) |
Storage temperature | -40°C to 85°C (-40°F to 185°F) |
Humidity | 5 to 95% noncondensing |
Contact Ratings
Parameter | Rating |
---|---|
Engine start | 10 A @ 32 VDC (SPST normally closed) |
Load control | 10 A @ 125 VAC (SPST normally open) |
Auxiliary Position-Indicating Contacts
Model | Number of contacts (Normal, Emergency) | Contact Rating |
---|---|---|
100-200A 1 Ph | 1, 1 Optional | 15 A @ 250VAC |
100-200 A 1 Ph SE | 1, 1 Optional | 15 A @ 250VAC |
300-400 A 1 Ph SE | 2, 2 Standard 1, 1 Optional |
10 A @ 480 VAC |
400 A 1 Ph and 3Ph/3P | 2, 2 Standard 1, 1 Optional |
10 A @ 480 VAC |
400 A 3Ph/4P | 8, 8 Standard | 10 A @ 480 VAC |
Cable Sizes (AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections)
Switch Size, Amps | Switch Ph. | Range of Wire Sizes, Cu/Al (per phase) | Neutral | Ground | |
---|---|---|---|---|---|
Normal | Emergency and Load | ||||
100 | 1 (Standard) | (1) #14 - 1/0 AWG | (1) #14 - 1/0 AWG | (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al) | |
1 (12- or 16-space load center (NEMA 1)) | (1) #14 - 1/0 AWG | Emerg: (1) #14 – 1/0 AWG Load: per customer-supplied circuit breaker |
(26) #4 - 14 AWG or (2) #14 - 1/0 AWG or (1) #6 - 2/0 AWG | (9) #6-#14 AWG or (4) #14 - 1/0 AWG | |
1 (16-space load center (NEMA 3R)) | (1) #14 - 1/0 AWG | (1) #14 - 1/0 AWG | (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al) | ||
100 Service Entrance | 1 | (1) #12 - 2/0 AWG | (1) #14 - 1/0 AWG | (26) #4 - 14 AWG or (2) #14 - 1/0 AWG or (1) 2/0 AWG | |
150 Service Entrance | 1 | (1) #14 - 4/0 AWG | (1) #14 - 4/0 AWG | (3) #14 - 1/0 AWG | |
200 Service Entrance | 1 | (1) #4 - 300 KCMIL | (1) #6 - 250 KCMIL | (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al) | |
200 Standard | 1 | (1) #6 AWG - 250 KCMIL | (1) #6 - 250 KCMIL | (5) #12 - 250 KCMIL (Cu) or (5) #10 - 250 KCMIL (Al) | |
3 (3-Phase) | (1) #14 - 4/0 AWG | (1) #14 - 4/0 AWG | (3) #14 - 1/0 AWG | ||
300 Service Entrance | 1 | (1) #1 - 600 KCMIL or (2) #1 - 250 KCMIL | (2) 1/0 - 250 KCMIL or (1) #4 - 600 KCMIL | (12) 1/0 - 250 KCMIL or (6) #4 AWG - 600 KCMIL | (6) #6 - 3/0 AWG |
400 Standard | 1 | (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL | (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL | (3) #4 AWG – 600 KCMIL or (6) 1/0 AWG – 250 KCMIL | |
3 (3-Phase) | (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL | (1) #4 - 600 KCMIL or (2) 1/0 – 250 KCMIL | (3) #4 AWG – 600 KCMIL or (6) 1/0 AWG – 250 KCMIL |
Note: Data is subject to change. Refer to transfer switch dimension drawings and wiring diagrams for planning and installation.
Withstand and Close-On Ratings (WCR)
Service Entrance Transfer Switch Ratings
The service entrance transfer switch is factory-equipped with a normal source disconnect circuit breaker. Suitable for controlling motors, electric discharge lamps, tungsten filament lamps, and electric heating equipment, provided the sum of motor full-load ampere ratings and other load ampere ratings does not exceed the switch rating, and tungsten load does not exceed 30% of switch rating.
Switch Rating, Amps * | WCR, RMS Symmetrical Amps at 240 VAC |
---|---|
100, 150, 200 | 22,000 |
300, 400 | 35,000 |
* Continuous load current not to exceed 80% of switch rating.
Contactor Ratings with Coordinated Circuit Breakers
Single-phase transfer switches are UL listed at 240 VAC maximum. Three-phase transfer switches are rated at 480 VAC maximum. The following tables list contactor withstand current ratings (WCR) for 100-400 ampere non-service entrance rated switches with specific manufacturer's circuit breakers per UL and Canadian safety standards. These are suitable for controlling motors, electric discharge lamps, tungsten filament lamps, and electric heating equipment, provided the sum of motor full-load ampere ratings and other load ampere ratings does not exceed the switch rating, and tungsten load does not exceed 30% of switch rating.
The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes maximum shown in the tables below, but no greater than the interrupting capacity of the selected breaker.
WCR Ratings with Specific Manufacturer's Molded-Case Circuit Breakers (100-200 Amps)
Switch Rating, Amps | Voltage, max. | Number of Poles/ Phases | WCR, RMS Symmetrical Amps | Manufacturer | Type or Class | Maximum Size, Amps |
---|---|---|---|---|---|---|
100 | 240 | 2 pole/ 1 phase | 10,000 | Any Breaker * | Any Breaker (0.025 seconds max.) | — |
150,000 | Square D | HR | 250 | |||
125,000 | HL | 150 | ||||
100,000 | BJ, HJ | 125 | ||||
65,000 | BG, HG | 125 | ||||
240 | 3 phase | 42,000 | QG, QJ | 125 | ||
25,000 | HD | 150 | ||||
22,000 | GE | BD | 125 | |||
85,000 | THED | 150 | ||||
100 | 480 | 3 phase | 50,000 | Square D | HL, HR | 150 |
35,000 | BJ | 125 | ||||
18,000 | HG, HJ | 150 | ||||
BG | 125 | |||||
BD, HD | 125 | |||||
150 / 200 | 240 | 2 pole/ 1 phase | 10,000 | Any Breaker * | Any Breaker (0.025 seconds max.) | — |
200,000 | Square D | JR | 250 | |||
125,000 | JL | 250 | ||||
100,000 | JJ | 250 | ||||
65,000 | JG | 250 | ||||
240 | 3 phase | 42,000 | QG, QJ | 225 | ||
25,000 | JD | 250 | ||||
85,000 | Square D | JL, JR | 250 | |||
30,000 | JG, JJ | 250 | ||||
18,000 | JD | 250 |
* For higher WCR values, contact the factory for additional specific breaker ratings.
WCR Ratings with Specific Manufacturer's Molded-Case Circuit Breakers (300-400 Amps)
Switch Rating, Amps | Voltage, max. | Number of Poles/ Phases | WCR, RMS Symmetrical Amps | Manufacturer | Type or Class | Maximum Size, Amps |
---|---|---|---|---|---|---|
300 / 400 | 240 | 1 phase | 65,000 | GE | THLC4 | 350 |
42,000 | Eaton/Cutler Hammer | HMC | 800 | |||
300 / 400 | 480 | 3 pole/ 3 phase | 65,000 | GE | THLC4 | 350 |
42,000 | Eaton/Cutler Hammer | HMC | 800 | |||
400 | 240 | 4 pole/ 3 phase | 65,000 | GE | THKM3F | 1200 |
GE | THQMV | 225 | ||||
GE | SGL1, SGL4, SGL6, SGP1, SGP4, SGP6 | 600 | ||||
Eaton/Cutler Hammer | LDC, CLDC, HLD, CHLD | 600 | ||||
Square D | LJ, LL, LR | 600 | ||||
Square D | QG, QJ | 250 | ||||
Siemens/ITE | HLD6, HLXD6 | 600 | ||||
Siemens/ITE | JGH, JGC, NHH | 250 | ||||
Eaton/Cutler Hammer | HKD, CHKD, KDC, HKDB, CHKDB, LHH | 400 | ||||
Eaton/Cutler Hammer | CHLD, LDC, CLDC, LGH*, LGC*, LGU*, LGX* | 600 | ||||
Eaton/Cutler Hammer | MDL, CMDL, HMDL, CHMDL, NGS, NGH, NGC, MDLB, CMDLB, HMDLB, CHMDLB | 800 | ||||
Eaton/Cutler Hammer | NGU | 1600 | ||||
GE | TBC4 | 400 | ||||
GE | TBC6, TJL4V, TJL1S-6S, SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGN, FGH, FGL, FGP | 600 | ||||
GE | TBC8, TKL4V, TKH8S-12S, TKL8S-12S, SKH8, SKL8, SKP8, TB8 | 800 | ||||
Siemens/ITE | HFD6, HFXD6, HFG, LFG | 250 | ||||
400 | 480 | 4 pole/ 3 phase | 50,000 | Siemens/ITE | HJD6, HJXD6, SHJD6, HHJD6, HHJXD6, CJD6, SCJD6, HJG, LLG, LJG | 400 |
Siemens/ITE | HLD6, HLXD6, SHLD6, HHLD6, HHLXD6, CLD6, SCLD6, HLG | 600 | ||||
Eaton/Cutler Hammer | LMD6, LMXD6, HLMD6, HLMXD6, MD6, MXD6, HMD6, HMXD6, SMD6, SHMD6, CMD6, SCMD6, HMG, LMG | 800 | ||||
Square D | CK400N, CK400NN, CK400H, CK400HH, CJ400L, NSJ400 | 400 | ||||
Square D | LC, DJ, DL, LJ, LL, LR, LI, NSJ600 | 600 | ||||
Square D | CK800N, CK800NN, CK800H, CK800HH, MJ | 800 | ||||
Square D | CK1000HH | 1000 | ||||
Square D | PK, PJ, PL, MH, MasterPact STR 28D, CK1200HH | 1200 |
* With Digitrip 310+ LS or LSG Inst. Override set to 12X.
Dimensions and Weights
Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See the Operation/Installation Manual or your local distributor for dimension drawings. Transfer switch weights and dimensions shown in the table do not include packaging. To estimate the shipping weight, add 3 kg (5 lbs.) or 10% (whichever is larger) to the weight shown.
A diagram illustrating the H (Height), W (Width), and D (Depth) dimensions is shown above the table.
Amps | Description | Dimensions, H x W x D, mm (in.) † | Weight ‡ kg (lb.) | Dimension Drawing |
---|---|---|---|---|
100 | Single phase | 623 x 335 x 180 (24.5 x 13.2 x 7.1) | 7 (15) | ADV-8688 |
With 12-space load center (NEMA 1) | 610 x 330 x 154 (24.0 x 13.0 x 6.0) | 12 (26) | ADV-9186 | |
With 16-space load center (NEMA 1) | 610 x 330 x 154 (24.0 x 13.0 x 6.0) | 12 (26) | ADV-9187 | |
With 16-space load center | 614 x 335 x 180 (24.2 x 13.2 x 7.1) | 8 (18) | ADV-9188 | |
100 | Three phase 3-pole | 673 x 462 x 228 (26.5 x 18.2 x 9.0) | 15 (33) | ADV-9755 |
Three phase 4-pole | 673 x 462 x 228 (26.5 x 18.2 x 9.0) | 15 (33) | ADV-9755 | |
Service entrance (ASE) | 734 x 416 x 175 (28.9 x 16.4 x 6.9) | 10 (22) | ADV-9046 | |
Service entrance (CSE) | 754 x 416 x 175 (29.7 x 16.4 x 6.9) | 14 (30) | ADV-8797 | |
150 | Service entrance (ASE) | 734 x 416 x 175 (28.9 x 16.4 x 6.9) | 12 (26) | ADV-9046 |
Service entrance (ASE) | 734 x 416 x 175 (28.9 x 16.4 x 6.9) | 12 (26) | ADV-9046 | |
200 | Service entrance (CSE) | 754 x 416 x 175 (29.7 x 16.4 x 6.9) | 16 (36) | ADV-8798 |
Single phase | 623 x 335 x 180 (24.5 x 13.2 x 7.1) | 7 (15) | ADV-8688 | |
Three phase | 673 x 462 x 228 (26.5 x 18.2 x 9.0) | 15 (33) | ADV-9755 | |
300 | Service entrance | 1452 x 629 x 329 (57.2 x 24.8 x 12.9) | 59 (130) | ADV-9768 |
400 | Single phase | 1222 x 610 x 343 (48.1 x 24.0 x 13.5) | 45 (100) | ADV-9756 |
3-Pole | 1222 x 610 x 343 (48.1 x 24.0 x 13.5) | 47 (104) | ADV-9756 | |
4-Pole | 1702x 610 x 514 (67.0 x 24.0 x 20.2) | 188 (414) | ADV-9757 | |
Service entrance | 1452 x 629 x 329 (57.2 x 24.8 x 12.9) | 59 (130) | ADV-9768 |
† Depth does not include the padlock hasp on the front of the enclosure.
‡ Transfer switch weights are approximate and do not include packaging.
Note: Enclosures are type NEMA 3R except as noted.
Accessories
- Auxiliary position-indicating contacts: Standard on 300-400 amp models, optional for others. Features one closed on normal position and one closed on emergency position. Form C contacts rated 15 A @ 250 VAC.
- Power relay modules: 50 amp DPST power relay mounted in a NEMA type 3R enclosure. Use up to four modules with the combined interface/load management board. UL/cUL listed. Dimensions: 172 x 233 x 92 mm (6.8 x 9.2 x 3.6 in.). For more information, see specification sheet G6-143.
- Status indicator kit for standard interface board: LEDs indicate normal and emergency source availability and contactor position. Mounts on the outside of the RXT enclosure, allowing status viewing without removing the cover. Features an overhang to protect the indicator panel and ribbon cable. Dimensions: 92 mm x 42 mm (3.62 in. x 1.65 in.). Connects to the standard interface board only. Not available for 400 amp/4 pole model. For more information, see specification sheet G11-123.
- Status indicator kit for combined interface/load management board: LEDs indicate normal and emergency source availability and contactor position. Dual color LEDs for each load indicate load status (powered or shed) and flash during a test. Includes a load shed test button. Mounts on the outside of the RXT enclosure, allowing status viewing without removing the cover. Features an overhang to protect the indicator panel and ribbon cable. Dimensions: 183 mm x 42 mm (7.20 in. x 1.65 in.). Connects to the combined interface/load management board only. Not available for 400 amp/4 pole model. For more information, see specification sheet G11-123.
- Auxiliary circuit breaker (service entrance models only): Single-pole type QO circuit breaker. Mounts on a bracket inside the enclosure. 15 amp and 20 amp circuit breakers are available.
Available Models Summary
All Model RXT transfer switches are standard-transition 60 Hz automatic transfer switches. Letters in parentheses refer to the model designation code described on the last page.
Amps | Description (Connections) | Voltages | Poles | Phases | WCR § RMS Symmetrical Amps |
---|---|---|---|---|---|
100 | Standard (A) | 240 (F) | 2 (N) | 1 | 10,000 |
Standard, with 16-space load center (B) | 240 (F) | 2 (N) | 1 | 10,000 | |
Standard, with 12-space load center ** | 240 (F) | 2 (N) | 1 | 10,000 | |
Service entrance (ASE, CSE) | 240 (F) | 2 (N) | 1 | 22,000 | |
150 | Standard, 3-phase (A) | 208 (C), 240 (F), 480 (M) | 3 (T) or 4 (V) | 3 | 10,000 |
Service entrance (ASE) | 240 (F) | 2 (N) | 1 | 22,000 | |
200 | Standard (A) | 240 (F) | 2 (N) | 1 | 10,000 |
Service entrance (ASE, CSE) | 240 (F) | 2 (N) | 1 | 22,000 | |
300 | Standard, 3-phase (A) | 208 (C), 240 (F), 480 (M) | 3 (T) or 4 (V) | 3 | 10,000 |
Service entrance (ASE, CSE) | 240 (F) | 2 (N) | 1 | 35,000 | |
400 | Standard (A) | 240 (F) | 2 (N) | 1 | 35,000 |
Service entrance (ASE, CSE) | 240 (F) | 2 (N) | 1 | 35,000 | |
Standard, 3-phase (A) | 208 (C), 240 (F), 480 (M) | 3 (T) or 4 (V) | 3 | 42,000 @ 480V 65,000 @ 240 V |
§ Withstand and close-on rating. See pages 3-5 for WCR information and specific breaker ratings.
W With 16-space load center and NEMA 1 or NEMA 3R enclosure. Up to 8 tandem breakers can be used, for a maximum of 24 circuits.
** GM85273-SA_ with 12-space load center and NEMA 1 enclosure.
Note: Combined interface board is available on single-phase standard or service entrance models. (Not available on 3-phase or load center models.)
Model Designation
The transfer switch model designation defines ratings and characteristics. Below is an explanation of the components:
Sample Model Designation: RXT-JFNC-0200A
Component | Description |
---|---|
Model RXT |
Kohler Automatic Transfer Switch |
Controls J |
Interface for RDC2 Controller (standard or combined interface/load management) |
Voltage/Frequency C F M |
208 Volts/60 Hz (3-phase only) 240 Volts/60 Hz 480 Volts/60 Hz (3-phase only) |
Number of Poles/Wires N T V |
2-pole, 3-wire, solid neutral (120/240 V only) 3-pole, 4-wire, solid neutral 4-pole, 4-wire, switched neutral |
Enclosure A C |
NEMA 1 * NEMA 3R * NEMA 1 enclosure is available on 100 amp load center models only. |
Current Rating 0100 0150 0200 0300 0400 |
100 amps 150 amps 200 amps 300 amps 400 amps |
Connections A B ASE CSE |
No load center With load center (100 amp single-phase only) Service entrance rated Service entrance rated with CSA certification (not available for 150 amp models) |
Contact Information
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444
KOHLERPower.com