Kohler RXT Automatic Transfer Switch (100-400 Amps)

Introduction

The Kohler Model RXT Automatic Transfer Switch is designed for seamless integration with Kohler® generator sets equipped with RDC2 or DC2 generator set/transfer switch controls. The transfer switch operation is managed by the RDC2/DC2 controller, ensuring reliable automatic power transfer.

An illustration shows the Kohler RXT Automatic Transfer Switch with its covers removed, revealing the internal components and wiring.

Available Models Overview

  • 100, 200, and 400 amp standard and service entrance models are available.
  • 150 and 300 amp service entrance models are also available.
  • A combined interface/load management board is available on single-phase standard and service entrance models (not available on 3-phase or load center models).
  • 100 amp standard single-phase models are offered with or without a 16-space load center. Up to 8 tandem breakers can be used for a total of 24 circuits.
  • A 100 amp standard single-phase model with a 12-space load center and a NEMA 1 enclosure is available as a standalone non-configurable specification (GM85273-SA_).

See page 7 for more detailed model information.

Standard Features

  • Allows utility voltage display on the RDC2/DC2 generator set/transfer switch controller, exclusively available on Kohler® residential and light commercial generator sets.
  • UL listed.
  • Models with load centers are UL 67 listed (file #E251086).
  • Models without load centers are UL 1008 listed (file #E58962).
  • CSA certification (file #LR58301) is available for:
    • Standard ATS without load center (single and three-phase).
    • Service entrance ATS 100 and 200 amp models.
  • Corrosion-resistant NEMA 3R aluminum enclosure.
  • Padlockable.
  • Approved for indoor or outdoor installation.
  • ANSI 49 gray finish.
  • NEMA 1 enclosure available on 100 amp load center models.
  • Contactor electrically and mechanically interlocked.
  • Double throw inherently interlocked design.
  • Contactor manually operable for maintenance purposes.
  • Silver alloy main contacts.
  • Transfer switches are 100% equipment rated and can be applied at the rated current without derating (non-service entrance models).
  • Service entrance models include a disconnect circuit breaker on the utility (normal) source side (80% rated).
  • Five-year limited warranty.

Interface Boards

Standard Interface Board

The standard interface board connects to the Model RDC2 or DC2 generator set/transfer switch controller. It includes a load control contact that provides a 5-minute time delay for startup of selected loads after transfer to the emergency source, suitable for large motor loads.

Optional Combined Interface/Load Management Board

This optional board replaces the standard interface board and connects to the Model RDC2 or DC2 generator set/transfer switch controller. It is available on single-phase standard and service entrance models (not available on 3-phase or load center models).

Load Management

  • Disconnects non-critical loads to prevent generator overload, in compliance with NEC.
  • Monitors generator current and frequency to determine when to add or shed loads, preventing frequency drops that can damage electronics.
  • Allows the use of a smaller generator set.

Operation

  • Loads are automatically added or shed based on generator capacity.
  • Uses dynamic logic to prevent shedding important loads unnecessarily when air conditioning, refrigerator, or water pump motors start (patent pending).
  • Communicates with the generator for smart power management, reducing the time to shed loads to adapt to critical power requirements.
  • Load shed power level and frequency setpoints can be adjusted using Kohler® Site Tech™ software (available to authorized distributors and dealers).

Priority Setting

  • Loads are added and shed according to their priority (Load 1 is highest, Load 6 is lowest).
  • Less critical loads can be turned off automatically when essential appliances are running.
  • Load priorities are hard-wired at installation.

Viewing Load Shed Outputs with OnCue® Plus

  • Use Kohler's OnCue® Plus Generator Management System (sold separately) to view load status (On or Off) for loads connected to the load shed relays.
  • Remotely monitor when loads are shed or added.
  • Load shed outputs can be labeled in OnCue® Plus.

Current Transformer

  • The combined load management board option includes a 400 amp current transformer (CT) for load monitoring.
  • A larger diameter CT is available for applications requiring larger cables.
  • A 500 amp CT is available for use with a 60RCL generator.

Specifications

Standard Interface Board Specifications

DescriptionRatingConnection
Controller interface connections A and B#20 AWG shielded twisted-pair Belden 9402 or 8762 or equivalent
Controller interface connections PWR and COM#12-20 AWG (see ATS Installation Manual)
Load control contact rating10 A @ 250 VAC
Load control connections#12-18 AWG

For combined interface/load management board specifications, see page 3.

Environmental Specifications

ParameterValue
Operating temperature-20°C to 70°C (-4°F to 158°F)
Storage temperature-40°C to 85°C (-40°F to 185°F)
Humidity5 to 95% noncondensing

Codes and Standards

The ATS meets or exceeds the requirements of the following specifications:

  • Underwriters Laboratories UL 67, Enclosed Panel Boards (load center models) file #E251086
  • Underwriters Laboratories UL 1008, Standard for Automatic Transfer Switches for Use in Emergency Systems, file #E58962
  • Underwriters Laboratories UL 508, Standard for Industrial Control Equipment
  • CSA certification available, file #LR58301 (not available for 150, 300, or 400 amp service entrance or 100 amp load center models). Must be selected when the transfer switch is ordered.
  • NFPA 70, National Electrical Code
  • NFPA 110, Emergency and Standby Power Systems
  • NEMA Standard IC10-1993, AC Automatic Transfer Switches

Cable Sizes (AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections)

Switch Size, AmpsSwitchPhasesRange of Wire Sizes, Cu/Al
Normal and EmergencyLoadNeutralGround
100Standard1(1) #14 - 1/0 AWG(1) #14 - 1/0 AWG(5) #12 to 250 KCMIL (Cu) or (5) #10 to 250 KCMIL (AI)(9) #6-#14 AWG (4) #14 - 1/0 AWG
12-space load center (NEMA 1)1(1) #14 - 1/0 AWGper customer-supplied circuit breaker(13) #4 - 14 AWG or (1) #6 - 2/0 AWG
16-space load center (NEMA 3R)1(1) #14 - 1/0 AWGper customer-supplied circuit breaker(27) #4 - 14 AWG or (3) #4 - 1/0 AWG or (1) #6 - 2/0 AWG
Service Entrance1Normal: (1) #12 – 2/0 AWG
Emerg: (1) #14 – 1/0 AWG
(1) #14 - 1/0 AWG(5) #12 to 250 KCMIL (Cu) or (5) #10 to 250 KCMIL (AI)
1503-Phase3(1) #14 - 1/0 AWG(1) #14 - 1/0 AWG(3) #4 AWG - 600 KCMIL
(6) 1/0 AWG - 250 KCMIL
(4) #14 - 1/0 AWG
(9) #14 - #6 AWG
Service Entrance1Normal: (1) #4 – 300 KCMIL
Emerg: (1) #6 - 250 KCMIL
(1) #6 - 250 KCMIL(5) #12 to 250 KCMIL (Cu) or (5) #10 to 250 KCMIL (AI)
200Standard1(1) #6 AWG - 250 KCMIL(1) #6 - 250 KCMIL(5) #12 to 250 KCMIL (Cu) or (5) #10 to 250 KCMIL (AI)(9) #14 – #4 AWG
(4) #14 - 1/0 AWG
3-Phase3(1) #14 - 1/0 AWG(1) #14 - 1/0 AWG(3) #4 AWG - 600 KCMIL
(6) 1/0 AWG - 250 KCMIL
(4) #14 - 1/0 AWG
(9) #14 - #6 AWG
300Service Entrance1Normal:: (1) #1 - 600 KCMIL or (2) #1250 KCMIL
Emerg: (2) #6 - 250 KCMIL
(2) #6 - 250 KCMIL(3) #4 AWG - 600 KCMIL
(6) 1/0 AWG - 250 KCMIL
(6) #6 - 3/0 AWG
Standard1(2) #6 - 250 KCMIL(2) #6-250 KCMIL(3) #4 AWG - 600 KCMIL
(6) 1/0 AWG – 250 KCMIL
(6) #6 - 3/0 AWG
4003-pole 208-240 V3(1) #4-600 KCMIL
(2) 1/0 – 250 KCMIL
(1) #4 - 600 KCMIL
(2) 1/0 - 250 KCMIL
(3) #4 AWG - 600 KCMIL
(6) 1/0 AWG – 250 KCMIL
(6) #6 - 3/0 AWG
3 or 4 pole 480 V3(1) #4-600 KCMIL
(2) 1/0 – 250 KCMIL
(1) #4 - 600 KCMIL
(2) 1/0 - 250 KCMIL
(3) #4 AWG - 600 KCMIL
(6) 1/0 AWG – 250 KCMIL
(6) #6 - 3/0 AWG

Note: Data is subject to change. Refer to the transfer switch dimension drawings and wiring diagrams for planning and installation.

Load Shed Specifications

ConnectionRatingConnection
Pilot Relays*125VAC, 10 A total (general purpose)
120VAC, 125VA (pilot duty)
#12-20 AWG
HVAC Relays (qty. 2)125VAC, 10 A (general purpose)
120VAC, 125VA (pilot duty)
#12-20 AWG
RBUS Communication and Power Connections to the RDC2/DC2 controller0.5 A @ 12 VDCUse Belden #9402 or equivalent 20 AWG shielded, twisted-pair communications cable †

* Four (4) pilot relays are provided for customer-supplied normally closed load-switching contactors/relays. The combination of four load relay outputs cannot exceed 10 amps total current draw. Kohler® power relay modules are recommended.

† For long distances, use an equivalent shielded, twisted-pair cable for RBUS connections and individual 12-20 AWG wires (qty. 2) for power connections.

Current Transformer Specifications

Ratio (Amps:VAC)Outer Diameter mm (in.)Inner Diameter mm (in.)Service Part NumberSales Kit Part NumberCT Availability
400:363.5 (2.5)28.7 (1.13)GM83929N/AIncluded with combined board
400:3111.8 (4.4)57.2 (2.25)GM17250GM17250-KP1-QSSold Separately
500:3171.5 (6.75)108.0 (4.25)GM60264GM17250-KP2-QSSold Separately (use with 60RCL)

Ratings

Service Entrance Transfer Switch Ratings

The service entrance transfer switch is factory-equipped with a normal source disconnect circuit breaker.

Suitable for the control of motors, electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum of motor full-load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of switch rating.

Switch Rating, Amps *WCR, RMS Symmetrical Amps at 240 VAC
100, 150, 20022,000
300, 40035,000

* Continuous load current not to exceed 80% of switch rating.

Contactor Ratings with Coordinated Circuit Breakers

Single-phase transfer switches are UL listed at 240 VAC maximum. Three-phase transfer switches are rated at 480 VAC maximum. The following table lists contactor withstand current ratings (WCR) for 100-400 ampere non-service entrance rated switches with specific manufacturer's circuit breakers per UL and Canadian safety standards. Suitable for the control of motors, electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum of motor full-load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of switch rating.

The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes maximum as shown in the tables below, but no greater than the interrupting capacity of the selected breaker.

WCR Ratings with Specific Manufacturer's Molded-Case Circuit Breakers (Part 1)

Switch Rating, AmpsVoltage, max.Number of Poles/ PhasesWCR, RMS Symmetrical AmpsManufacturerType or ClassMaximum Size, Amps
1002402 pole/ 1 phase10,000Any Breaker *Any Breaker (0.025 seconds max.)--
1502402 pole/ 1 phase10,000Any Breaker *Any Breaker (0.025 seconds max.)--
2002402 pole/ 1 phase10,000EatonFCL
JGS, JGH, JGC, JGU, JGX, JBD, JD, HJD, JDC, LCL, LCLA
LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD
100
250
400
ITE/SiemensCED6, HED4, HED6
CFD6, FD6A, FXD6, HFD6, HFXD6, HHFD6, HHFXD6
CJD6
125
250
400
1004803 pole/ 3 phase30,000General ElectricSEL, SEP, THLC1, PE E, PE N, PE H, PE L
THLC2
150
225
2004804 pole/ 3 phase30,000General ElectricSFH, SFL, SFP, PE E, PE N, PE H, PE L
SGH, SGL, SGP, FGN, FGH, FGL, FGP, PG_E, PG_N, PG_H, PG_L, PG_P
250
400
SchneiderHG, HJ, HL, HR
JJ, JL, JR
LG, LJ, LL, LR
150
250
400

* For higher WCR values, contact the factory for additional specific breaker ratings.

WCR Ratings with Specific Manufacturer's Molded-Case Circuit Breakers (Part 2)

Switch Rating, AmpsVoltage, max.Number of Poles/ PhasesWCR, RMS Symmetrical AmpsManufacturerType or ClassMaximum Size, Amps
3002402 pole/ 1 phase35,000ABBT5, T6600
EatonCHKD, CKD, DK, HKD, KD, KDB, KDC, LA TRIPAC, LCL
CHLD, CLD, CLDC, HLD, LD, LDB, LDC
HMDL, MDL, NB TRI-PAC
400
600
800
SiemensCMD, HLMD, HLMXD, HMD, HMG, HMXD, LMD, LMG, LMXD, MD, MXD, NMG, SCMD, SHMD, SMD800
2402 pole/ 1 phase35,000Square DLA, LC, LE, LH, LI, LX, LXI
DG, DJ, DL, LC, LE, LI, LX, LXI
400
600
Merlin GerinCJ400H, CJ400L, CJ400N
CJ600H, CJ600N
400
600
3002403 pole/ 3 phase35,000Any BreakerAny Breaker (0.017 seconds max.)600
EatonLD
HJD, JDC, JGC, JGH, JGU, JGX
600
250
4004803 pole/ 3 phase50,000EatonCHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD, CHMDL4, CMDL4
CHLD6, HDL6, CHMDL6, CMDL6, CLDC, CLD6, LDC6, CLDC6
CHMDL8, HMDL8, MDL8, CMDL8
400
600
800
ITE/SiemensCFD6, HFD6, HFXD6, HHFD6, HHFXD6
CJD6
CLD6, HHLD6, HHLXD6, HLD6, HLXD6
250
400
600
General ElectricCMD6, MD6, HMD6, HMXD6, MXD6
SEL, SEP, PE_N, PE_H, PE_L
SFL, SFP, PE_N, PE_H, PE_L
SGL, SGP
800
150
250
400
General ElectricFGL, FGP, SGL, SGP, PG_H, PG_L, PG_N, PG_P600
SchneiderHG, HL, HR
JJ, JL, JR
LJ, LL, LR
150
250
600
SchneiderMJ800

Dimensions and Weights

Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See the Operation/Installation Manual or your local distributor for dimension drawings.

Transfer switch weights and dimensions shown in the table do not include packaging. To estimate the shipping weight, add 3 kg (5 lbs.) or 10% (whichever is larger) to the weight shown.

AmpsDescriptionDimensions, H x W x D, mm (in.) †Shipping Weight kg (lb.)Dimension Drawing
100Single phase623 x 335 x 180 (24.5 x 13.2 x 7.1)7 (15)ADV-8688
With 12- or 16-space load center (NEMA 1)610 x 330 x 154 (24.0 x 13.0 x 6.0)12 (26)ADV-8487
With 16-space load center614 x 335 x 180 (24.2 x 13.2 x 7.1)8 (18)ADV-8690
Three phase682 x 462 x 228 (26.8 x 18.2 x 9.0)14 (30)ADV-8689
150Service entrance (ASE)734 x 416 x 175 (28.9 x 16.4 x 6.9)10 (22)ADV-9046
Service entrance (CSE)754 x 416 x 175 (29.7 x 16.4 x 6.9)14 (30)ADV-8797
200Service entrance (ASE)734 x 416 x 175 (28.9 x 16.4 x 6.9)12 (26)ADV-9046
Service entrance (CSE)754 x 416 x 175 (29.7 x 16.4 x 6.9)16 (36)ADV-8798
100Single phase623 x 335 x 180 (24.5 x 13.2 x 7.1)7 (15)ADV-8688
Three phase682 x 462 x 228 (26.8 x 18.2 x 9.0)14 (30)ADV-8689
300Service entrance1075 x 559 x 329 (42.3 x 22.0 x 12.9)46 (101)ADV-8694
400Single phase1067 x 559 x 329 (42.0 x 22.0 x 12.9)55 (120)ADV-8691
3-Pole/208-240 volts1067 x 559 x 329 (42.0 x 22.0 x 12.9)41 (90)ADV-8692
3-Pole/480 volts1222 x 610 x 343 (48.1 x 24.0 x 13.5)59 (130)ADV-8693
4004-Pole1222 x 610 x 343 (48.1 x 24.0 x 13.5)59 (130)ADV-8693
400Service entrance1075 x 559 x 329 (42.3 x 22.0 x 12.9)46 (101)ADV-8694

† Depth does not include the padlock hasp on the front of the enclosure.

Transfer switch weights are approximate and do not include packaging.

Note: Enclosures are type NEMA 3R except as noted.

Accessories

  • Auxiliary position-indicating contacts:
    • One closed on normal position and one closed on emergency position.
    • Form C contacts rated 15 A @ 250 VAC.
  • Power relay modules:
    • 50 amp DPST power relay mounted in a NEMA type 3R enclosure.
    • Use up to four modules with the combined interface/load management board.
    • UL/cUL listed.
    • Dimensions: 172 x 233 x 92 mm (6.8 x 9.2 x 3.6 in.).
    • For more information, see specification sheet G6-143.
  • Status indicator kit for standard interface board:
    • LEDs indicate normal and emergency source availability and contactor position.
    • Mounts on the outside of the RXT enclosure.
    • View transfer switch status without removing enclosure cover.
    • An overhang on the enclosure protects the indicator panel and ribbon cable opening.
    • Dimensions: 92 mm x 42 mm (3.62 in. x 1.65 in.).
    • Connects to the standard interface board only.
    • For more information on the status indicator kit, see specification sheet G11-123.
  • Status indicator kit for combined interface/load management board:
    • LEDs indicate normal and emergency source availability and contactor position.
    • Dual color LEDs for each load indicate load status (powered or shed) and flash during a test.
    • Load shed test button allows the operator to cycle the load shed relays in order of priority (when generator is in RUN mode).
    • Mounts on the outside of the RXT enclosure.
    • View transfer switch and load status without removing enclosure cover.
    • An overhang on the enclosure protects the indicator panel and ribbon cable opening.
    • Dimensions: 183 mm x 42 mm (7.20 in. x 1.65 in.).
    • Connects to the combined interface/load management board only.
    • For more information on the status indicator kit, see specification sheet G11-123.
  • Auxiliary circuit breaker (service entrance models only):
    • 15 amp single-pole type QO circuit breaker.
    • Mounts on a bracket inside the enclosure.

Available Models

All Model RXT transfer switches are standard-transition 60 Hz automatic transfer switches. Letters in parentheses refer to the model designation code described on the last page.

AmpsDescription (Connections)VoltagesPolesPhasesWCR § RMS Symmetrical Amps
100Standard (A)208 (C) •
240 (F) •
2 (N)110,000
Standard, with 16-space load center (B)240 (F) •2 (N)110,000
Standard, with 12-space load center **240 (F) •2 (N)110,000
Service entrance (ASE, CSE)208 (C) •
240 (F) •
2 (N)122,000
150Standard, 3-phase (A)208 (C) •
240 (F) •
480 (M) •
3 (T) or 4 (V)330,000
Service entrance (ASE)240 (F) •2 (N)122,000
200Standard (A)240 (F) •2 (N)110,000
Service entrance (ASE, CSE)208 (C) •
240 (F) •
2 (N)122,000
300Standard, 3-phase (A)208 (C) •
240 (F) •
480 (M) •
3 (T) or 4 (V)330,000
Service entrance (ASE)240 (F) •2 (N)135,000
400Standard (A)240 (F) •2 (N)150,000
Service entrance (ASE)240 (F) •2 (N)135,000
Standard, 3-phase (A)208 (C) •
240 (F) •
480 (M) •
3 (T) or 4 (V)350,000

§ Withstand and close-on rating. See pages 3-5 for WCR information and specific breaker ratings.

W With 16-space load center and NEMA 1 or NEMA 3R enclosure. Up to 8 tandem breakers can be used, for a maximum of 24 circuits.

** GM85273-SA_ with 12-space load center and NEMA 1 enclosure.

Note: Combined interface board is available on single-phase standard or service entrance models. (Not available on 3-phase or load center models.)

Model Designation

The transfer switch model designation defines ratings and characteristics. Record the transfer switch model designation in the boxes provided.

Sample Model Designation: RXT-JFNC-0200A

Model Breakdown:

  • Model: RXT: Kohler Automatic Transfer Switch
  • Controls: J: Interface for RDC2/DC2 Controller (standard or combined interface/load management)
  • Voltage/Frequency:
    • C: 208 Volts/60 Hz (3-phase only)
    • F: 240 Volts/60 Hz
    • M: 480 Volts/60 Hz (3-phase only)
  • Number of Poles/Wires:
    • N: 2-pole, 3-wire, solid neutral (120/240 V only)
    • T: 3-pole, 4-wire, solid neutral
    • V: 4-pole, 4-wire, switched neutral
  • Enclosure:
    • A: NEMA 1 *
    • C: NEMA 3R

    * NEMA 1 enclosure is available on 100 amp load center models only.

  • Current Rating:
    • 0100: 100 amps
    • 0150: 150 amps
    • 0200: 200 amps
    • 0300: 300 amps
    • 0400: 400 amps
  • Connections:
    • A: No load center
    • B: With load center (100 amp single-phase only)
    • ASE: Service entrance rated
    • CSE: Service entrance rated with CSA certification (100/200 amps only)

PDF preview unavailable. Download the PDF instead.

kohler-2115a9b17ab5f33b7de0b2ab6aa2098b Acrobat Distiller 18.0 (Windows)

Related Documents

PreviewKohler RXT Automatic Transfer Switch: Features, Specifications, and Ratings
Detailed information on the Kohler RXT Automatic Transfer Switch, including standard features, technical specifications, environmental conditions, cable sizes, withstand and close-on ratings, dimensions, weights, and available models. Designed for use with Kohler RDC2/DC2 generator sets.
PreviewKohler RDT Automatic Transfer Switch: Features, Specifications, and Model Guide
Comprehensive guide to Kohler RDT Series Automatic Transfer Switches (100-400 Amps), detailing features, environmental specifications, contact ratings, time delays, cable sizes, withstand ratings, codes, dimensions, accessories, and model designation.
PreviewKohler RDT Automatic Transfer Switch: 100-400 Amps Technical Specifications
Explore the features and specifications of the Kohler RDT Automatic Transfer Switch, available in 100-400 Amp models. Details on MPAC 500 controller, standard and service entrance configurations, and compliance with industry standards.
PreviewKohler RDT Automatic Transfer Switch: Features, Specifications, and Models
Comprehensive guide to Kohler RDT Automatic Transfer Switches (100-400 Amps), detailing features, specifications, ratings, codes, dimensions, and available accessories for reliable power backup solutions.
PreviewKohler RXT Automatic Transfer Switch: Features, Specifications, and Models
Comprehensive overview of the Kohler RXT Automatic Transfer Switch (100-400 Amps), detailing standard features, available models, interface boards, specifications, dimensions, and model designation for standby power systems.
PreviewKohler RXT Automatic Transfer Switch: Features, Specifications, and Models
Detailed information on the Kohler RXT Automatic Transfer Switch (100-400 Amps), including standard features, interface board options, codes and standards, technical specifications, dimensions, weights, accessories, and model designations. Designed for use with Kohler RDC2 controllers for reliable backup power management.
PreviewKohler RSB Intelligent Transfer Switch Operation Manual
Comprehensive operation manual for the Kohler RSB Intelligent Transfer Switch (150-225 Amps) with MPACTM 550 electrical controls. Covers installation, operation, safety, maintenance, and accessories.
PreviewKohler RXT Automatic Transfer Switch: Features, Specifications, and Ratings
Comprehensive details on the Kohler RXT Automatic Transfer Switch (100-400 Amps), including features, technical specifications, environmental and interface module data, cable sizing, withstand and close-on ratings, dimensions, weights, and model designation.