Thermokon SRG02 Wireless Window Handle

Data Sheet with revisions

Publication Date: 23.07.2025

Product Overview

The SRG02 is a wireless window handle with EnOcean communication technology, designed for monitoring window opening status. It can be optionally equipped with a lock.

Upon activation, the handle transmits a radio signal indicating its position to an actuator or central control unit. This enables energy-saving measures, such as automatically switching off heating or ventilation when windows are open.

This product is intended for use within functional building automation systems. It transmits sensor data wirelessly over short distances to designated receivers. No personal or location-specific data is transmitted. The product is not designed for direct internet communication or applications that rely on internet transmission of raw sensor data. Building automation stations transmitting data via the internet must ensure data encryption according to legal requirements.

Safety Information – Warning

Installation and assembly should only be performed by authorized personnel.

The product must be used only for its intended purpose. Unauthorized modifications are prohibited.

The product must not be used in conjunction with any equipment that could directly or indirectly endanger human health or life, or cause damage to people, animals, or property in the event of a malfunction. Ensure all power is disconnected before installation. Do not connect to live equipment.

Please observe the following:

Disposal Information

The crossed-out wheeled bin symbol indicates that the product and its batteries must not be disposed of with household or commercial waste. Within the EU, there is a legal obligation to dispose of the product separately and appropriately according to country-specific regulations. If in doubt, contact your supplier or Thermokon Sensortechnik GmbH. More information can be found at: www.thermokon.pl

Product Research and Certification

CE Declaration of Conformity

Declarations of conformity for products can be found on our website: https://www.thermokon.de/direct/en-gb/categories/srg02

Technical Data

Parameter Specification
Radio Technology EnOcean (IEC 14543-3-10), transmission power <10 mW, EEP F6-10-00
Frequency 868 MHz
Antenna Internal transmitting antenna
Power Supply Maintenance-free, electrodynamic energy generator
Signal Transmission Interval Upon change of handle position
Enclosure Aluminum, pure white - lacquered, aluminum steel gray, stainless steel
Operating Environment +5..+40 °C, max. 80% RH non-condensing
Mounting Square spindle, variable lengths (up to thread depth 32..42 mm), special lengths available upon request
Notes Additional lock (optional)

Information on EasySens® (Radio) / General AirConfig Usage

EasySens® - airConfig

Basic information on EasySens® technology and general usage of our airConfig software can be downloaded from our website: https://www.thermokon.de/direct/files/airconfig-software-manual-en.pdf

Radio Telegram Overview

The data structure contained in the telegram can be found in the EEP list (EnOcean Equipment Profile) provided by the EnOcean Alliance.

Mounting Instructions

First, remove the old window handle. Then, turn the window handle to the "open" position. Unscrew the mounting screws and remove the window handle.

Proceed with the following steps:

  1. Turn the handle to the 90° position and rotate the cover by 90°.
  2. Place the handle into the window profile and tighten with the provided screws to the window profile. Then, rotate the cover back to the closed position.

Diagrams:

Step 1: Showing handle at 90° and cover rotated 90°.

Step 2: Showing handle insertion into profile and tightening screws with a maximum torque of 2 Nm.

Operating Principle

For the window handles to function correctly, they must be set precisely to the vertical or horizontal position.

Note: Window handle with cylinder lock (optional)

In the closed position (0° position), the window handle can be locked with a key, providing an additional anti-burglary function. Only after unlocking (turning the key) can the handle be moved to the tilted position (90° position).

Diagrams:

Diagram 1: Handle in closed (0°) position.

Diagram 2: Handle in tilted (90°) position, showing key lock.

Diagram 3: Handle in open (180°) position.

Teach-In Process

Ideally, the teach-in process for the window handle should be performed before mounting it in the window. Mounting is done only after the programming process.

To perform the teach-in process, the corresponding receiver is put into learn mode. Then, the window handle should be turned from the closed position to the open position and back.

More information on programming can be found in the data sheet of the respective receiver.

Diagrams:

Diagram 1: Handle in closed (0°) position.

Diagram 2: Handle in open (90°) position.

Dimensions (mm)

Diagram:

Drawing showing dimensions of the window handle:

Overall length: 104 mm

Handle length: 85 mm

Spindle length: 37 mm

Spindle diameter: Ø9.5 mm

Cover diameter: 37 mm

Distance between screws: 21 mm

Distance from profile edge to handle center: 21 mm

PDF preview unavailable. Download the PDF instead.

8d18680b705e15c55 Adobe PDF Library 25.1.97

Related Documents

Preview Thermokon SR65 rH 902 MHz Wireless Sensor Datasheet
Technical datasheet for the Thermokon SR65 rH 902 MHz wireless sensor, detailing its application, technical specifications, guidelines for solar energy storage, humidity sensor notices, and configuration with airConfig.
Preview Thermokon SAB05 EasySens Datasheet: Wireless Radiator Valve Actuator
Detailed datasheet for the Thermokon SAB05 EasySens wireless radiator valve actuator. Learn about its application in building automation, technical specifications, mounting, configuration, and operational features for room temperature control.
Preview Thermokon SRW03 | SRW03 BAT Wireless Window Contact Datasheet
Datasheet for the Thermokon SRW03 and SRW03 BAT wireless window contact sensors. Includes technical specifications, application details, installation instructions, and operating modes.
Preview Thermokon SRW03 Dual BAT Wireless Window Contact Datasheet
Datasheet for the Thermokon SRW03 Dual BAT wireless window contact, detailing its application, technical specifications, and installation instructions for building automation.
Preview SR06 LCD (868 MHz) Room Operating Unit Datasheet
Datasheet for the Thermokon SR06 LCD (868 MHz) wireless surface-mounted room operating unit with display, temperature sensor, and optional humidity sensor. Learn about its features, technical specifications, application, and installation.
Preview Thermokon SR65 868 MHz Wireless Outdoor Temperature Sensor Datasheet
Datasheet for the Thermokon SR65 868 MHz Wireless Outdoor Temperature Sensor, detailing its application, security advice, disposal notes, technical specifications, and configuration with airConfig.
Preview Thermokon SAB05 EasySens Radiator Valve Actuator - Technical Data
Detailed technical data, installation, operation, and configuration guide for the Thermokon SAB05 EasySens wireless radiator valve actuator. Covers features, specifications, safety precautions, and airConfig setup.
Preview EasySens Radio Switch 55x55: Versatile Wireless Control
Discover the EasySens Radio Switch 55x55, a battery-less, self-powered wireless switch for lighting and blind control in buildings. Learn about its features, available types, technical specifications, and installation guidelines.