METSEPM2120
EasyLogic PM2120, Power & Energy meter, up to the 15th harmonic, LED display, RS485, class 1
Main Specifications
Range | EasyLogic |
Product name | EasyLogic PM2100 |
Device short name | PM2120 |
Product or Component Type | Power meter |
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Complementary Features
Device application | Power quality analysis |
Type of measurement | Sub billing, Power monitoring |
Measurement Details
Metering Type
- Total harmonic distortion: Up to the 15th harmonic
- Apparent power min/max, total
- Active and reactive power min/max, total
- Current min/max, avg
- Voltage min/max, avg
- Frequency min/max, avg
- Total current harmonic distortion THD (I) per phase
- Total voltage harmonic distortion THD (U) per phase
- Power factor min/max, avg
- Apparent energy total
- Active and reactive energy total
- Current I, I1, I2, I3
- Peak demand power PM, QM, SM
- Active, reactive, apparent energy (signed, four quadrant)
- Peak demand currents
- Active power P, P1, P2, P3
- Calculated neutral current
- Voltage U, U21, U32, U13, V, V1, V2, V3
- Unbalance current
- Reactive power Q, Q1, Q2, Q3
- Demand power P, Q, S
- Apparent power S, S1, S2, S3
Accuracy Class
- Class 1 active energy IEC 62053-21
- Class 1 reactive energy IEC 62053-24
- Class 5 harmonic distortion (I THD & U THD)
Measurement Accuracy
Parameter | Accuracy |
Apparent power | ± 1% |
Active energy | ± 1% |
Reactive energy | ± 1% |
Active power | ± 1% |
Voltage | ± 0.5% |
Power factor | ± 0.01 |
Current | ± 0.5% |
Frequency | ± 0.05% |
Measurement Ranges
Measurement current | 5...6000 mA |
Measurement voltage | 35...480 V AC 50/60 Hz (phase-phase) 20...277 V AC 50/60 Hz (phase-neutral) 480...999000 V AC 50/60 Hz (with external VT) |
Frequency measurement range | 45...65 Hz |
[Us] rated supply voltage | 44...277 V AC 45...65 Hz ± 10% 44...277 V DC ± 10% |
Technical Specifications
Network Frequency | 50 Hz, 60 Hz |
Ride-through time | 100 Ms 120 V AC typical 400 Ms 230 V AC typical 50 ms 125 V DC typical |
Line Rated Current | 1 A, 5 A |
Maximum power consumption in VA | 6 VA @ 277 V AC |
Maximum power consumption in W | 3.3 W (AC lines) 2 W (DC lines) |
Input impedance | Current ≤ 0.3 mΩ Voltage > 5 MΩ |
Tamperproof of settings | Protected by access code |
Display type | 7 segments LED |
Display colour | Red |
Messages display capacity | 3 fields of 4 characters |
Display digits | 12 - 0.56 in (14.2 mm) |
Demand intervals | Configurable from 1 to 60 min |
Information displayed | Demand current (past/present value), Demand power (past/present value), Voltage, Current, Frequency, Energy consumption, Harmonic distortion, Power factor, Active power, Apparent power, Reactive power, Unbalanced in % |
Control type | 3 x button |
Local signalling | Red LED output signal (1...9999000 pulse/k_h) Green LED module operation and integrated communication |
Number of inputs | 0 |
Number of Outputs | 0 |
Communication port protocol | Modbus RTU (4800, 9600, 19200, 38.4 Kbps, even/odd or none - 2 wires, 2500 V) |
Communication port support | Screw terminal block RS485 |
Data recording | Time stamping, Min/max for 8 parameters |
Function Available | Real time clock, 64 samples/cycle |
Cybersecurity | Enable/disable communication ports |
Communication service | Remote monitoring |
Product certifications | CE IEC 61010-1, CULus UL 61010-1, CULUS CSA C22.2 No 61010-1, RCM, EAC, C-tick |
Mounting Mode | Clip-on |
Mounting position | Vertical |
Mounting support | Framework |
Provided equipment | 1 x Installation guide |
Measurement category | Category III 480 V, Category II 480...600 V |
Electrical insulation class | Double insulation, Class II |
Flame retardance | V-0 conforming to UL 94 |
Connections - terminals | Current transformer screw connection (bottom): 6 Voltage inputs screw connection (top): 4 |
Material | Polycarbonate |
Width | 3.78 in (96 mm) |
Dimensions and Environment
Dimensions
Depth | Total 3.00 in (76.09 mm) Embedded 2.43 in (61.64 mm) |
Height | 3.78 in (96 mm) |
Net Weight | 10.58 oz (300 g) |
Compatibility code | PM2120 |
Environment
Service Life | 7 year(s) |
IP degree of protection | Front IP54 IEC 60529 Body IP30 IEC 60529 |
Relative humidity | 5...95 % @ 122 °F (50 °C) |
Pollution degree | 2 |
Ambient air temperature for operation | 14...140 °F (-10...60 °C) |
Ambient Air Temperature for Storage | -13...158 °F (-25...70 °C) |
Operating altitude | ≤ 6561.68 ft (2000 m) |
Electromagnetic compatibility | Electrostatic discharge IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test IEC 61000-4-3 Electrical fast transient/burst immunity test IEC 61000-4-4 Surge immunity test IEC 61000-4-5 Conducted RF disturbances IEC 61000-4-6 Magnetic field at power frequency IEC 61000-4-8 Voltage dips and interruptions immunity test IEC 61000-4-11 Emission tests FCC Part 15 class A |
Overvoltage category | III |
Ordering and Shipping Details
Ordering Information
Category | 09734-EASYLOGIC METERS AND ACCESSORIES |
Discount Schedule | PL1 |
GTIN | 3606480800146 |
Nbr. of units in pkg. | 1 |
Package weight(Lbs) | 10.67 oz (302.5 g) |
Returnability | Yes |
Country of origin | US |
Packing Units
Unit Type of Package 1 (PCE)
Package 1 Height | 3.78 in (9.6 cm) |
Package 1 width | 2.65 in (6.72 cm) |
Package 1 Length | 4.00 in (10.16 cm) |
Unit Type of Package 2 (BB1)
Number of Units in Package 2 | 1 |
Package 2 Weight | 14.25 oz (404.0 g) |
Package 2 Height | 4.53 in (11.5 cm) |
Package 2 width | 3.43 in (8.7 cm) |
Package 2 Length | 4.72 in (12 cm) |
Unit Type of Package 3 (S03)
Number of Units in Package 3 | 18 |
Package 3 Weight | 17.04 lb(US) (7.73 kg) |
Package 3 Height | 11.81 in (30 cm) |
Package 3 width | 11.81 in (30 cm) |
Package 3 Length | 15.75 in (40 cm) |
Offer Sustainability
Sustainable offer status | Green Premium product |
REACH Regulation | REACH Declaration |
EU RoHS Directive | Compliant EU RoHS Declaration |
Mercury free | Yes |
RoHS exemption information | Yes |
China RoHS Regulation | China RoHS Declaration |
Environmental Disclosure | Product Environmental Profile |
Circularity Profile | End Of Life Information |
File Info : application/pdf, 4 Pages, 132.63KB
DocumentDocumentReferences
download.schneider-electric.com/files?p_Doc_Ref=ENVEOLI1510002EN
download.schneider-electric.com/files?p_Doc_Ref=ENVPEP1510002
Related Documents
![]() |
Schneider Electric PM1200 Power Meter: Features and Specifications Discover the capabilities of the Schneider Electric PM1200 power meter, designed for energy and demand monitoring with communication features. This document details its technical specifications, environmental compatibility, and offer sustainability. |
![]() |
Schneider Electric EasyLogic™ Power Metering Range Catalog Explore the comprehensive EasyLogic™ power metering range from Schneider Electric. This catalog details various multi-function power and energy meters designed for essential electrical system measurement, including the PM2000, PM1000H, and DM series. |
![]() |
Schneider Electric EasyLogic DM6000H/DM6200H Series Power Meter User Manual Comprehensive user manual for Schneider Electric's EasyLogic DM6000H and DM6200H series power meters, covering installation, operation, features, and specifications for advanced electrical monitoring and load management in industrial and commercial applications. |
![]() |
Schneider Electric PowerLogic ION8650: Advanced Power Monitoring Unit Technical Specifications Detailed technical specifications and characteristics of the Schneider Electric PowerLogic ION8650 power-monitoring unit, covering its functions, applications, electrical and mechanical features, communication options, and part numbers. |
![]() |
Schneider Electric ION9000 Series Power Meter: Functions, Characteristics, and Specifications Detailed overview of the Schneider Electric ION9000 Series power meter, covering its advanced functions, technical specifications, applications, competitive advantages, and conformity to industry standards. Ideal for critical power monitoring and energy management. |
![]() |
EasyLogic PM2200 Series User Manual | Schneider Electric Comprehensive user manual for Schneider Electric's EasyLogic PM2200 series power and energy meters (PM2210, PM2220, PM2230). Details features, installation, operation, safety, specifications, and troubleshooting for industrial electrical monitoring. |
![]() |
Schneider Electric PowerTag M630 Wireless Energy Sensor Installation and Technical Data Instruction sheet and technical data for the Schneider Electric PowerTag M630 wireless energy sensor, covering installation, safety, status LEDs, and technical specifications. |
![]() |
Schneider Electric Power and Energy Meters: PM, ION, and iEM Series Overview Comprehensive overview of Schneider Electric's PowerLogic and Acti 9 energy and power quality meters, including PM2000, PM5000, PM8000, ION9000, and iEM3000 series. Features, specifications, applications, and software integration are detailed. |