Version: 1.0 - 09/11/2020 5 PLSED310106EN. Feature guide ION9000 ION9000T General Use on LV, MV, and HV systems b b Current accuracy: 0.1 % reading b b Voltage accuracy: 0.1 % reading b b Active energy accuracy: 0.1 Class b b Number of samples/cycle or sample frequency: 1024 b b

PowerLogic ION9000 Technical Datasheet Technický katalogový list | Schneider Electric

PDF preview unavailable. Download the PDF instead.

PLSED310106EN (web)
ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

ION9000 Series
The PowerLogicTM ION9000 is your 24/7 power quality expert, providing information, not just data.
With a comprehensive, industry-leading Power Quality Instrument (PQI) performance designation according to IEC 625861/-2, the PowerLogic ION9000 is third-party certified ANSI C12.20 Class 0.1 and IEC 62053-22 Class 0.1S accurate, the most accurate power meter available today. Lab-verified power quality and safety ensure reliable, precision performance that is perfect for supply- or demand-side applications. Its patented Disturbance Direction Detection also helps you pinpoint the source of power quality issues faster. Capable of sampling at 10 MHz, the ION9000T captures extremely fast voltage events that are missed by most other power meters, enabling advanced diagnostics and high-resolution event associations for fast, conclusive diagnosis and resolution to transient voltages. Highly customizable and modular, the ION9000's field programmability can adapt to satisfy any solution, protecting your investment now and in the future. All designed to align with your comprehensive grid cybersecurity policies and backed by Schneider Electric's global services and support.
Applications Ideal for critical power and large energy users who cannot afford to be shut down, the ION9000T has High-Speed Transient Capture (HSTC) to detect and record transient events that exceed the voltage withstand of sensitive equipment.

PB115917

Version: 1.0 - 09/11/2020 PLSED310106EN

METSEION92040
1

ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

The market solution for
Markets that benefit from a solution that includes PowerLogic ION9000 series meters: · Data centers · Healthcare facilities · Semiconductor · Pharmaceutical & chemical · Energy industries · Mining, Minerals, & Metals · Renewable energy interconnects · Medium voltage distribution & energy automation
Benefits
· Makes understanding power quality simple which helps operations personnel avoid downtime and increase productivity and equipment life
· Makes energy and power quality data immediately actionable and relevant to operational and sustainability goals

Power management solutions
Schneider Electric provides innovative power management solutions to increase your energy efficiency and cost savings. Maximize electrical network reliability and availability, and optimize electrical asset performance.

Conformity of standards

· ANSI C12.20 · IEC 62052-11

· ANSI C37.90.1 · IEC 62052-31

· IEC 61000-4-15 · IEC 62053-22

· IEC 61000-4-30 · IEC 62053-23

· IEC 61010-1

· IEC 62053-24

· IEC 61326-1

· IEC 62586

· IEC 61557-12 · UL 61010-1

· IEC 61850

Competitive advantages
· Modular, flexible, patented IONTM programmable technology · Utility grade energy accuracy · Patented Disturbance Direction Detection · Third-party, lab-verified compliance with latest PQ standards · Onboard pass/fail PQ characterization and assessment
according to EN50160 and IEEE519 · Cybersecurity event logging, Syslog protocol, HTTPS, SFTP,
and full control of each communication port · High-speed impulsive and oscillatory transient detection

2

Version: 1.0 - 09/11/2020

PLSED310106EN

PB115917

PB115914

ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

PowerLogicTM ION9000 series meter with RD192 display PowerLogicTM ION9000 RD192 remote display

Main characteristics
· PQ compliance reporting and basic PQ analysis: ­ Monitors and logs parameters according to IEC 61000-4-30 Class A international PQ standards (test methods as per IEC 62586-2). ­ High resolution waveform capture: triggered manually or by event. Captured waveforms available directly from the meter via SFTP in a COMTRADE format, and viewable in the meter's web interface. ­ Generates onboard PQ compliance reports accessible via onboard web pages: ­ Pass/fail report for IEEE 519 for voltage and current harmonic limits. ­ ITIC (CBEMA) and SEMI curves, with alarm categorization to support further analyses. ­ NEMA Motor Derating curve. ­ Harmonic analysis: ­ THD and TDD per phase, min/max, custom alarming. ­ Individual harmonic magnitudes and angles on voltage and current, up to the 63rd harmonic. ­ Disturbance detection and capture: sag/swell on any current and voltage channel, alarm on disturbance event, and waveform capture. ­ Patented Disturbance Direction Detection: provides indication of the captured disturbance occurring upstream or downstream of the meter; timestamped results provided in the event log, with degree of certainty of disturbance direction.
· Transient detection and capture: events 20 microseconds or longer in duration on any voltage channel with alarm, event log, and waveform capture.
· PowerLogic ION9000T also provides High-Speed Transient Capture (HSTC) of voltage events 100 nanoseconds or longer in duration and up to 10,000 V in magnitude with high-speed and disturbance waveform captures, as well as per-event statistics on each transient.
· Metering precision: ­ IEC 61557-12 PMD/SD/K70/0.2 and PMD/SS/K70/0.2 3000m (Performance Measuring and Monitoring devices (PMD)). ­ Class 0.1S accuracy IEC 62053-22, ANSI C12.20 Class 0.1 (active energy). ­ Industry leading Class 0.5S accuracy for reactive energy (IEC 62053-24). ­ Cycle-by-cycle RMS measurements updated every ½ cycle. ­ Full `multi-utility' WAGES metering support. ­ Net metering. ­ Anti-tamper protection seals and hardware metrology lock.
· Cybersecurity: ­ Security events logging with Syslog protocol support. ­ HTTPS and SFTP secure protocols. ­ Ability to enable or disable any communication port and any protocol per port. ­ Anti-tamper protection seals and hardware metrology lock. ­ User accounts with strong passwords.

PowerLogicTM ION9000 front view

PB115918

Version: 1.0 - 09/11/2020

3

PLSED310106EN

ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

PB115916

PB115919

PowerLogic ION9000 with panel mounting adapter PowerLogic ION9000 front with two option modules PowerLogic ION9000 bottom with two option modules

· Used with Schneider Electric's advanced software tools, provides detailed PQ reporting across entire network:
­ EN 50160 compliance report. ­ IEEE 519 harmonic compliance report. ­ IEC 61000-4-30 report. ­ Power quality compliance summary. ­ Energy reports for consumption analysis and cost management. ­ WAGES dashboards and reports. ­ Display of waveforms and PQ data from all connected meters. ­ Onboard web-based waveform viewer. ­ EcoStruxure Power Events Analysis, including alarm management,
sequence of events, and root cause analysis.
· Data and event logging: ­ Onboard data and event logging. ­ 2 GB of standard non-volatile memory. ­ No data gaps due to network outages or server downtime. ­ Min/max log for standard values. ­ 100 user-definable data logs, recording up to 16 parameters at a 1/2 cycle or other user definable interval. ­ Continuous logging or snapshot, triggered by setpoint and stopped after defined duration. ­ Trend energy, demand and other measured parameters. ­ Forecasting via web pages: average, minimum and maximum for the next four hours and next four days. ­ Advanced time-of-use capability. ­ Security/event log: alarm conditions, metering configuration changes, power outages, firmware download, and user login/logout with timestamp.
· Alarming and control: ­ 50+ definable alarms to log critical event data, trigger waveform recording, or perform control function. ­ Trigger on any condition, with 1/2-cycle and 1-second response time. ­ Combine alarms using Boolean logic enabling customization of alarms. ­ Alarm notification via email. ­ In conjunction with Schneider Electric's EcoStruxure software, alarms, software alarms, and alarm frequency are categorized and trended enabling sequence of events and root cause analyses.
Usability
· Auto-discovery using DPWS (Device Profile Web Services). · DHCP for automatic IP address configuration. · Full function web server enables simple web commissioning. · Free setup wizard simplifies meter configuration. · Front panel:
­ Easy to read color graphic display. ­ Simple and intuitive menu navigation with multiple language
interface and support. · DIN rail mounting options. · Remote display option. · Pluggable connectors. · Low Voltage Current Sensors Input option.

PB115920

(1) For 50 Hz line frequency; 17µs for 60 Hz line frequency.

4

Version: 1.0 - 09/11/2020

PLSED310106EN

PB115915

ADVANCED METERING PowerLogic ION9000 Harmonics display
Version: 1.0 - 09/11/2020 PLSED310106EN

FUNCTIONS AND CHARACTERISTICS
· Flexible remote communications: ­ Multiple simultaneously operating communication ports and protocols allow interfacing with other automation systems, e.g. waveforms, alarms, billing data, etc. Data can be uploaded for viewing/analysis while other systems access real-time information. ­ Supports: Modbus, ION, DNP3, DLMS/COSEM, SNMP, and IEC 61850. ­ Dual port Ethernet: 2x 10/100BASE-TX; supports IPV4 and IPV6; daisychaining capability removes need for additional switches. ­ Create redundant network loop using Rapid Spanning Tree Protocol (RSTP) and managed Ethernet switches. ­ Secure web interface with HTTPS and TLS 1.2 with support for userprovided certificates. ­ Customize TCP/IP port numbers and enable/disable individual ports. ­ RS-485 2-wire connection, up to 115,200 baud, Modbus RTU, ION and DNP3 protocols. ­ Ethernet to serial gateway with Modbus Master functionality, connecting to 31 unit loads of downstream serial Modbus devices. Also supports Modbus Mastering over TCP/IP (Ethernet) network. ­ Full function web server with factory and customizable pages to access real-time and PQ compliance data. ­ Push historical data via email. ­ Advanced network security: Up to 50 configurable user accounts.
· Time synchronization via: ­ Precision network time protocol (PTP) based on IEEE 1588 / IEC 61588. ­ GPS clock (RS-485) or IRIG-B (digital input) to ±1 millisecond. ­ Network Time Protocol (NTP/SNTP). ­ Automatic time synchronization available through Schneider Electric software server.
Adaptability
· IONTM frameworks are customizable, scalable applications with objectoriented programming that compartmentalizes functions, and increases flexibility and adaptability.
· Applications include: access and aggregate data from Modbus devices on serial port or across the network (Modbus TCP/IP), logging and/or processing data by totaling, unit conversion or other calculations, applying complex logic for alarming or control operations, data visualization via web pages.
Standard meter I/O
· 8 digital status/counter inputs with ±1 millisecond timestamp. · 4 solid state digital outputs (Form A) for energy pulsing, interfacing with other
systems or control. · 2 Form C relay outputs for control applications.
Modular I/O options
· Optional expansion modules. · Up to 4 modules per meter.
Option modules include: · Digital module:
­ 6 digital status/counter inputs. ­ 2 Form C relay outputs, 250 V AC, 8 A. · Analog module: ­ 4 analog inputs (0-20 mA, 4-20 mA; 0-30 V). ­ 2 analog outputs (0-20 mA, 4-20 mA; 0-10 V) for interfacing with building
management sensors and systems.
5

ADVANCED METERING
ION9000 series

FUNCTIONS AND CHARACTERISTICS

Feature guide

General Use on LV, MV, and HV systems Current accuracy: 0.1 % reading Voltage accuracy: 0.1 % reading Active energy accuracy: 0.1 Class Number of samples/cycle or sample frequency: 1024 High-Speed Transient Capture: 10 MHz (200 k for 50 Hz, 167 k for 60 Hz)
Instantaneous rms values Current, voltage, frequency Active, reactive, apparent power: Total and per phase Power factor: Total and per phase
Energy values Active, reactive, apparent energy Settable accumulation modes
Demand values Current: Present and max. values Active, reactive, apparent power: Present and max. values Predicted active, reactive, apparent power Synchronization of the measurement window Setting of calculation mode: Block, sliding
Power Quality measurements Harmonic distortion: Current and voltage Individual harmonics: via front panel and web page: 63
via EcoStruxureTM software: 511 Waveform capture Detection of voltage swells and sags Fast acquisition: 1/2 cycle data EN 50160 compliance checking Customizable data outputs (using logic and math functions) IEEE 519 compliance checking
Data recording Min/max of instantaneous values Data logs Event logs Trending/forecasting SER (Sequence of event recording) Time stamping GPS synchronization (± 1ms) Memory: 2000 MB
Display and I/O
Front panel display, 2 options: 96 mm & 192 mm Pulse output: 2 Digital or analog inputs(max): 32 digital, 16 analog
Digital or analog outputs (max, including pulse output): 4 digital, 10 relay, 8 analog
Communication RS-485 port(s): 2 Ethernet port(s): 2x 10/100BASE-TX, RJ45 connector, CAT5/5e/6/6a cable Serial port protocols (Modbus, ION, DNP3, DLMS/COSEM) Ethernet port protocols (Modbus, ION, DNP3, DLMS/COSEM, IEC 61850) Ethernet gateway Alarm notification via email HTTP/HTTPS web server with waveform viewer SNMP with custom MIB and traps for alarms
SMTP email PTP and NTP time synchronization SFTP file transfer

ION9000
b b b b b
b b b
b b
b b b b b
b b
b b b b b b
b b b b b b b b
b b b b
b b
b b
b b b b b b b

ION9000T
b b b b b b
b b b
b b
b b b b b
b b
b b b b b b
b b b b b b b b
b b b b
b b
b b
b b b b b b b

6

Version: 1.0 - 09/11/2020

PLSED310106EN

ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

ION9000 series

Technical specifications

Electrical characteristics Type of measurement

Measurement accuracy Current & voltage Active Power Power factor Frequency Active energy

Display refresh rate Input-voltage characteristics
Input-current characteristics
LV Input-current characteristics
Power supply AC/DC
Input/outputs

Reactive Energy
Specified accuracy voltage Impedance Specified accuracy frequency Limit range of operation - frequency Rated nominal current Specified accuracy current range Permissible overload Impedance Burden Input voltage range Minimum signal Withstand Input impedance Safety AC DC Ride-through time (Values for meters with no optional accessories) Burden
Meter base Only

Optional

True rms to 1,024 samples per cycle
High-speed transient detection, 10 MHz, 10 kV
Class 0.1 as per IEC 61557-12
Class 0.1 as per IEC 61557-12
Class 0.5 as per IEC 61557-12
Class 0.02 as per IEC 61557-12
Class 0.1S IEC 62053-22 Class 0.1 IEC 61557-12 Class 0.1 ANSI C12.20 Class 0.5S IEC 62053-24
HMI display updated once per second; data refresh rate 1/2 cycle or 1 second 57 - 400 V L-N / 100 - 690 V L-L
5 MW per phase
42 to 69 Hz (50/60 Hz nominal) 20 to 450 Hz
1 A (0.1S), 5 A (0.1S); current class 2, 10, 20 A (0.1 ANSI)
Starting Current: 1 mA (no accuracy) Accurate Range: 10 mA - 20 A 500 A rms for 1.0s
0.0003 W per phase 0.01 VA max at 5 A
±5.5 V pk
1 mV
30 V pk continuous
200 k W For use with listed Energy Monitoring current transformers
90-480 V AC ±10 % (50/60 Hz ±10 %) 90-120 V AC ±10% (400 Hz)
110-480 V DC ±15 %
100 ms (5 cycles at 50/60 Hz) typ., 120 V AC 400 ms (20 cycles at 50/60 Hz) typ., 240 V AC 1,200 ms (60 cycles at 50/60 Hz) typ., 480 V AC Typical: 16.5 W / 38 VA at 480 V (50/60 Hz) Fully optioned: max. 40 W / 80 VA at 480 V (50/60 Hz). 8 digital inputs (30 V AC/60 V DC) 4 Form A (KY) solid state digital output (30 V AC/60 V DC, 75 mA) 2 Form C relays (8 A at 250 V AC, 5 A at 24 V DC) Digital - 6 digital inputs (30 V AC / 60 V DC) wetted + 2 Form C relay outputs (250 V AC, 8 A) Analog - 4 analog inputs (0-20 mA, 4-20 mA, 0-30 V DC) + 2 analog outputs (0-20 mA, 4-20 mA, 0-10 V DC).

ION9000
b
b b b b b
b b
b
b b
b
b b
b b b b 1 b 1 b 1 b 1 b 1 b b b
b
b
b
b

ION9000T
b b b b b b b
b b
b
b b
b
b b
b b b b b b
b
b
b
b

1 The LV Input-current option replaces standard CT inputs

(1) Consult the ION7550 / ION7650 installation guide for complete specifications. (2) IEC 62051-22B with serial ports only.

Version: 1.0 - 09/11/2020

7

PLSED310106EN

ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

ION9000 series

Mechanical characteristics Weight
IP degree of protection Excellent quality Dimensions

Panel mount
DIN rail mount meter

ION9000

DIN rail mount meter 1.5 kg

b

IO modules 0.140 kg

Touchscreen display 0.300 kg

IP 65, UL type 12: Panel mount and touchscreen display, front.

b

IP 30: Panel mount rear, DIN rail mount, I/O modules.

ISO 9001 and ISO 14000 certified manufacturing.

b

160 x 160 x 135.3 mm

b

160 x 160 x 135.3 mm

b

Color remote

197 x 175 x 27.5 mm touchscreen

b

display

(2 options)

I/O modules

90.5 x 90.5 x 22 mm

b

Touchscreen

192 mm and 96 mm

b

display(s)

Environmental conditions

Operating temperature

-25 to 70 ºC

b

Remote Display Unit

-25 to 60 ºC

b

Storage temperature

-40 to 85 ºC

b

Humidity rating

5 to 95 % non-condensing

b

Installation category

III

b

Operating altitude (maximum)

3,000 m above sea-level

b

Electromagnetic compatibility

EMC standards

IEC 62052-11, IEC 61326-1, IEC 61000-6-5

b

Immunity to electrostatic discharge IEC 61000-4-2

b

Immunity to radiated fields

IEC 61000-4-3

b

Immunity to fast transients

IEC 61000-4-4

b

Immunity to surges

IEC 61000-4-5

b

Immunity to conducted

IEC 61000-4-6

b

disturbances

Immunity to power frequency

IEC 61000-4-8

b

magnetic fields

Immunity to conducted

CLC/TR 50579

b

disturbances, 2-150kHz

Immunity to voltage dips &

IEC 61000-4-11

b

interruptions

Immunity to ring waves

IEC 61000-4-12

b

Conducted and radiated emissions EN 55011 and EN 55032 Class B, FCC part 15 Class B, ICES-003 Class B

b

Surge withstand Capability (SWC) IEEE/ANSI C37.90.1

b

Safety

Safety Construction

IEC/EN 61010-1 ed.3, CAT III, 400 V L-N / 690 V L-L, UL 61010-1 ed.3 and CSA-C22.2 No.

b

61010-1 ed.3, CAT III, 347 V L-N / 600 V L-L, IEC/EN 62052-31, protective class II.

Communication

Ethernet to serial line gateway

Communicates directly with up to 31 serial devices.

b

Web server

Customizable pages, new page creation capabilities, HTML/XML compatible.

b

Serial port RS-485

2x, Baud rates of 2,400 to 115,200, pluggable screw terminal connector.

b

Ethernet port(s)

2x 10/100BASE-TX, RJ45 connector, CAT5/5e/6/6a cable.

b

Protocol

HTTPS, SFTP, SNMP, SMTP, DPWS, RSTP, PTP, NTP/SNTP, GPS, Syslog, DHCP, IPv4, IPv6.

b

Firmware characteristics

High-speed data recording

Down to 1/2 cycle interval recording, stores detailed characteristics of disturbances

b

or outages. Trigger recording by a user-defined setpoint, or from external equipment.

Harmonic distortion

Up to 63rd harmonic (511th via Schneider Electric EcoStruxure software) for all

b

voltage and current inputs.

Sag/swell detection

Analyze severity/potential impact of sags and swells: magnitude and duration data suitable for

b

plotting on voltage tolerance curves per phase triggers for waveform recording.

ION9000T b
b b b b
b
b b
b b b b b b
b b b b b b b b b b b b
b
b b b b b
b b b

8

Version: 1.0 - 09/11/2020

PLSED310106EN

ADVANCED METERING

FUNCTIONS AND CHARACTERISTICS

ION9000 series

Firmware characteristics (cont.)

ION9000

Disturbance direction detection Determine the location of a disturbance more quickly and accurately by determining the

b

direction of the disturbance relative to the meter. Results are captured in the event log,

along with a timestamp and confidence level indicating level of certainty.

Detection & capture of transients

As short as 20 s at 50 Hz (17 s at 60 Hz)

b

High-speed transient capture

Detection and capture of high-speed impulsive and oscillatory transients as short as 100 ns in

b

duration and up to 10 kV in magnitude. (PowerLogic ION9000T).

Instantaneous

High accuracy of standard speed (1s) and high-speed (1/2 cycle) measurements,

b

including true rms per phase and total for: voltage, current, active power (kW),reactive

power (kvar), apparent power (kVA), power factor, frequency, voltage and current

unbalance, phase reversal.

Load profiling

Channel assignments (1600 channels via 100 recorders) configurable for any

b

measurable parameter, including historical trend recording of energy, demand, voltage,

current, power quality, or any measured parameter. Trigger recorders based on time

interval, calendar schedule, alarm/event condition, or manually.

Trend curves

Historical trends and future forecasts to better manage demand, circuit loading, and other

b

parameters. Provides average, min, max, and standard deviation every hour for last 24 hours, every

day for last month, every week for last 8 weeks and every month for last 12 months.

Waveform captures

Simultaneous capture of voltage and current channels, sub-cycle disturbance captures of

b

180-cycles @ 1,024 samples/cycle to 7,200-cycles @ 16 sample/cycle, retriggerable.

High-speed transient waveform captures

Simultaneous capture of voltage channels, impulsive and oscillatory transient capture of up to 1-cycle @ 200 k samples per cycle (50 Hz) along with coincidence disturbance waveform capture (PowerLogic ION9000T).

Alarms

Threshold alarms: adjustable pickup and dropout setpoints and time delays, numerous activation

b

levels possible for a given type of alarm, user-defined or automatic alarm threshold settings, user-

defined priority levels (optional automatic alarm setting).

Advanced Time of Use (TOU)

4 seasons; 5 different day types: weekend, weekday, and holiday; up to 4 tariffs per day type.

b

Advanced network security

Up to 50 users with unique access rights. Perform resets, time sync, or meter

b

configurations based on user privileges.

Memory

2,000 MB.

b

Firmware update

Update via the communication ports.

b

Display characteristics

96 mm pushbutton display

320 x 240 (1/4 VGA) color LCD, configurable screens, 5 buttons and 2 LED indicators

b

(alarm and meter status).

192 mm touchscreen display

800 x 480 pixels, 177.8 mm (7") Color LCD, +/- 85 degree view angle, sunlight readable,

b

dual capacitive touch, usable when wet or through Class 0 lineman gloves, impact

resistant to 5 joules, IP65 rating.

Languages

English, French, Spanish, Russian, Portugese, German, Italian, Chinese.

b

Notations

IEC, IEEE.

b

ION9000T b
b b b
b
b
b b
b
b b b b
b b
b b

ION9000 Commercial reference numbers

Comm ref number METSEION92030 METSEION92040 METSEION92043 METSEION92044 METSEION93030 METSEION93040 METSEION95030 METSEION95040 METSEPM89RD96 METSERD192 METSEPM89M2600 METSEPM89M0024 METSE9HWK METSE9CTHWK METSERD192HWK METSE9B2BMA METSE9HWKLVCS METSE9USBK METSE7X4MAK

Description ION9000 meter, DIN mount, no display, hardware kit ION9000 meter, DIN mount, 192 mm display, B2B adapter, hardware kit ION9000 meter, DIN mount, 192 mm display, B2B adapter, hardware kit, Measurement Canada Ready (Canada only) ION9000 meter, DIN mount, 192 mm display, B2B adapter, hardware kit, Measurement Canada Sealed (Canada only) ION9000 meter, LVCS, DIN mount, no display, hardware kit ION9000 meter, LVCS, DIN mount, 192 mm display, B2B adapter, hardware kit ION9000T meter, HSTC, DIN mount, no display, hardware kit ION9000T meter, HSTC, DIN mount, 192 mm display, B2B adapter, hardware kit Remote display, color LCD, 96 x 96 mm Remote display, color touchscreen, 192 x 192 mm I/O module, 2 relay outputs, 6 digital inputs I/O module, 2 analog outputs, 4 analog inputs ION9000 meter hardware kit ­ plugs, terminal guards, spare grounding screw, DIN clips ION9000 Current Input hardware kit - terminal screws, CT covers RD192 remote display hardware kit ION9000 B2B (back to back) mounting adapter ION9000 hardware kit for LVCS ION9000 USB cover hardware kit ION7X50 mounting adapter kit

Contact your Schneider Electric representative for complete ordering information.

Version: 1.0 - 09/11/2020

9

PLSED310106EN

ADVANCED METERING
ION9000 series
ION9000 meter dimensions

DIMENSIONS AND CONNECTION
ION9000 mounting template

PB119714_m

PB119707

PB120537

PB119712_m

PB119705

ION9000 back-to-back (B2B) dimensions
LVCS Input-current option
ION9000 192 mm display dimensions

ION9000 96 mm display dimensions

Please refer to ION9000 Series Meter Installation Sheet for accurate and complete information on the installation of this product.

10

Version: 1.0 - 09/11/2020

PLSED310106EN

PB119713_m

PB119706

ADVANCED METERING
ION9000 series
ION9000 meter DIN rail dimensions

DIMENSIONS AND CONNECTION
ION7x50 mounting adapter dimensions

PB119714

ION9000 LV Current Input wiring options

PB120533

Version: 1.0 - 09/11/2020

11

PLSED310106EN

Schneider Electric Industries SAS 35, Rue Joseph Monier, CS 30323 F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com
November 2020 ION9000 Series PLSED310106EN

As standards, specifications and designs develop from time to time, please ask for confirmation of the information given in this document.
Design: Schneider Electric Photos: Schneider Electric
Over 75 % of Schneider Electric products have been awarded the Green Premium ecolabel.
© 2020 - Schneider Electric - All rights reserved


Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)