CAME ZM3E, ZM3EC, ZM3EP Control Panel Installation Manual
For 230 V Gearmotors
Model Numbers: ZM3E, ZM3EC, ZM3EP
General Precautions for Installers
[Warning Symbol] Important safety instructions. Please follow all of these instructions. Improper installation may cause serious bodily harm.
Before continuing, please also read the general precautions for users.
- Only use this product for its intended purpose. Any other use is hazardous.
- The manufacturer cannot be held liable for any damage caused by improper, unreasonable or erroneous use.
- This product has been designed to be assembled to partly completed machinery and/or equipment so as to build machinery as regulated by the Machinery Directive 2006/42/EC.
- The final installation must comply with the Machinery Directive (2006/42/EC) and the European reference standards in force.
- The manufacturer declines any liability for using non-original products, which would also void the warranty.
- All operations indicated in this manual must be carried out exclusively by skilled and qualified personnel and in full compliance with the regulations in force.
- The device must be installed, wired, connected and tested according to good professional practice, in compliance with the standards and laws in force.
- Make sure the mains power supply is disconnected during all installation procedures.
- All the components (e.g. actuators, photocells and sensitive edges) needed for the final installation to comply with the Machinery Directive (2006/42/EC) and with the reference harmonised technical standards are specified in the general CAME product catalogue or on the website www.came.com.
- Check that the temperature ranges given are suitable for the installation site.
- Make sure that no direct jets of water can wet the product at the installation site (sprinklers, water cleaners, etc.).
- Make sure you have set up a suitable dual-pole cut-off device along the power supply that is compliant with the installation rules. It should completely cut off the power supply according to category III surcharge conditions.
- Demarcate the entire site properly to prevent unauthorised personnel from entering, especially minors.
Further Safety and Installation Guidelines
- Use suitable protection to prevent any mechanical hazards due to persons loitering within the operating range of the operator.
- The electrical cables must pass through special pipes, ducts and cable glands to guarantee adequate protection against mechanical damage.
- The electrical cables must not touch any parts that may overheat during use (such as the motor and transformer).
- Before installation, check that the guided part is in good mechanical condition, and that it opens and closes correctly.
- The product cannot be used to automate any guided part that includes a pedestrian gate, unless it can only be enabled when the pedestrian gate is secured.
- Make sure that nobody can become trapped between the guided and fixed parts, when the guided part is set in motion.
- All fixed controls must be clearly visible after installation, in a position that allows the guided part to be directly visible, but far away from moving parts.
- In the case of a hold-to-run control, this must be installed at a minimum height of 1.5 m from the ground and must not be accessible to the public.
- If not already present, apply a permanent tag that describes how to use the manual release mechanism close to it.
- Make sure that the operator has been properly adjusted and that the safety and protection devices and the manual release are working properly.
- Before handing over to the final user, check that the system complies with the harmonised standards and the essential requirements of the Machinery Directive (2006/42/EC).
- Any residual risks must be indicated clearly with proper signage affixed in visible areas, and explained to end users.
- Put the machine's ID plate in a visible place when the installation is complete.
- If the power supply cable is damaged, it must be immediately replaced by the manufacturer or by an authorised technical assistance centre, or in any case, by qualified staff, to prevent any risk.
- Keep this manual inside the technical folder along with the manuals of all the other devices used for your automation system.
- Make sure to hand over to the end user all the operating manuals of the products that make up the final machinery.
Product Handling, Dismantling, and Disposal
- The product, in its original packaging supplied by the manufacturer, must only be transported in a closed environment (railway carriage, containers, closed vehicles).
- If the product malfunctions, stop using it and contact customer services at https://www.came.com/global/en/contact-us or via the telephone number on the website.
- The manufacture date is provided in the production batch printed on the product label. If necessary, contact CAME at https://www.came.com/global/en/contact-us.
- The general conditions of sale are given in the official CAME price lists.
Dismantling and Disposal
CAME S.p.A. employs an Environmental Management System at its premises. This system is certified and compliant with the UNI EN ISO 14001 standard to ensure that the environment is respected and safeguarded. Please continue safeguarding the environment. At CAME, this is considered one of the fundamentals of our operating and market strategies. Simply follow these brief disposal guidelines:
Disposing of the Packaging
The packaging materials (cardboard, plastic, etc.) can be disposed of easily as solid urban waste, separated for recycling. Before dismantling and disposing of the product, please always check the local laws in force. DISPOSE OF THE PRODUCT RESPONSIBLY.
Disposing of the Product
Our products are made of various materials. Most of these materials (aluminium, plastic, iron and electrical cables) are classified as solid urban waste. They can be separated for recycling and disposed of at authorised waste treatment plants. Other components (electronic boards, transmitter batteries, etc.) may contain pollutants. These must be removed and disposed of by an authorised waste disposal and recycling firm. It is always advisable to check the specific laws that apply in your area. DISPOSE OF THE PRODUCT RESPONSIBLY.
Product Data and Information
Key
- This symbol shows which parts to read carefully.
- This symbol shows which parts describe safety issues.
- This symbol shows what to tell users.
- The measurements, unless otherwise stated, are in millimetres.
Description
002ZM3E: Multifunction control panel for swing gates with two leaves. Features a graphic signalling display, self-diagnosing safety devices, and built-in radio decoding.
002ZM3EC: Multifunction control panel for swing doors with two leaves, complete with safety lock and buttons. Features graphic programming and signalling display, plus self-diagnosing safety devices.
002ZM3EP: Multifunction control panel for swing gates with two leaves. Features graphic programming and signalling display, self-diagnosing safety devices, and built-in radio decoding.
Technical Data
MODELS | ZM3E | ZM3EC | ZM3EP |
---|---|---|---|
Power supply (V - 50/60 Hz) | 230 AC | 230 AC | 230 AC |
Motor power supply (V) | 230 AC | 230 AC | 230 AC |
Standby consumption (W) | 4,7 | 4,7 | 4,7 |
Standby consumption with the RGP1 (W) module | 0,75 | 0,75 | 0,75 |
Power (W) | 750 | 750 | 2400 |
Colour | RAL 7040 | RAL 7040 | RAL 7040 |
Operating temperature (°C) | -20 ÷ +55 | -20 ÷ +55 | -20 ÷ +55 |
Protection rating (IP) | 54 | 54 | 54 |
Insulation class | II | II | II |
Storage temperature (°C) * | -25 ÷ +70 | -25 ÷ +70 | -25 ÷ +70 |
Average life (hours) ** | 100.000 | 100.000 | 100.000 |
(*) Before installing the product, keep it at room temperature where it has previously been stored or transported at a very high or very low temperature.
(**) The average product life is a purely indicative estimate. It applies to compliant usage, installation and maintenance conditions. It is also influenced by other factors, such as climatic and environmental conditions.
Fuse Table
MODELS | ZM3E | ZM3EC | ZM3EP |
---|---|---|---|
Line fuse | 5 A F | 5 A F | 10 A F |
Control-board fuse | 1 A F | 1 A F | 1 A F |
Accessory fuse | 1.6 A F | 1.6 A F | 1.6 A F |
Description of Parts
The following lists the components identified in the control panel diagrams:
- 1 Transformer
- 2 Capacitors * (Only for 230 V Frog gearmotors)
- 3 Control board fuse
- 4 Accessories fuse
- 5 Terminal board for connecting the RGP1 module
- 6 Electric-lock fuse
- 7 Display
- 8 Trimmer to adjust the display lighting
- 9 Memory Roll card connector
- 10 Programming buttons
- 11 Power LED
- 12 Programming status warning LED
- 13 Connector for the R700 or R800 decoding card
- 14 Connector for plug-in radio frequency card (AF)
- 15 Terminal board for connecting the keypad selector
- 16 Terminal board for connecting the antenna
- 17 Terminal board for B1-B2 output
- 18 Terminal board for connecting the limit switches
- 19 Terminal board for connecting the transponder selector switch
- 20 Terminal board for connecting control and safety devices
- 21 Terminal board for connecting the encoder
- 22 Terminal boards for gearmotors
- 23 Terminal board for CRP connection
- 24 RSE card connector
- 25 Power supply terminal block
- 26 Line fuse
* Only for 230 V Frog gearmotors. Use the black cables to connect M1 and the red cables to connect M2.
Diagram illustrating the main components of the control panel.
Control Panel Layout and Dimensions
Control Panel Buttons (Specific to ZM3EC):
- 27 STOP button
- 28 CLOSING button
- 29 OPENING button
- 30 SAFETY LOCK knob
Diagram showing the layout of buttons and the safety lock knob on the ZM3EC model.
Dimensions
Diagram showing the physical dimensions of the ZM3E, ZM3EP, and ZM3EC models. The ZM3E/ZM3EP dimensions are 215mm width, 295mm height, and 120mm depth. The ZM3EC dimensions are 215mm width, 295mm height, and 145mm depth (front) / 165mm depth (rear).
Cable Types and Minimum Thicknesses
Cable Type | Length up to 20 m | Length from 20 to 30 m |
---|---|---|
Power supply 230 V AC | 3G x 1.5 mm² | 3G x 2.5 mm² |
24 V AC/DC flashing beacon | 2 x 0.5 mm² | 2 x 0.5 mm² |
TX Photocells | 2 x 0.5 mm² | 2 x 0.5 mm² |
RX photocells | 4 x 0.5 mm² | 4 x 0.5 mm² |
12 V DC electric lock | 2 x 1 mm² | 2 x 1.5 mm² |
Command and control devices | *no. x 0.5 mm² | *no. x 0.5 mm² |
* no. = see product assembly instructions
Warning: The cable cross-section is indicative and varies according to the motor power and cable length.
- When operating at 230 V and outdoors, use H05RN-F cables compliant with 60245 IEC 57 (IEC); when indoors, use H05VV-F cables compliant with 60227 IEC 53 (IEC).
- For power supplies up to 48 V, use FROR 20-22 II cables compliant with standard EN 50267-2-1 (CEI).
- To connect the antenna, use RG58 cable (up to 5 m).
- To connect to the CRP, use a UTP CAT5 cable (up to 1,000 m long).
- If the cable lengths differ from those specified in the table, define the cable cross-sections according to the actual power draw of the connected devices and in line with regulation CEI EN 60204-1.
- For multiple, sequential loads along the same line, recalculate the values in the table according to the actual power draw and distances. For information on connecting products not covered in this manual, please see the documentation accompanying the products themselves.
- To connect the encoder, use a FRORPU 3 x 0.5 mm² cable or a cable supplied by CAME on request (item code 801XA-0020). The maximum cable length is 30 m.
Installation
Preparing the Control Panel
- Separate the parts of the control panel.
- Assemble the pressure hinges.
- Insert the hinges into the box (either on the left or the right) and fasten them using the screws and washers supplied. The hinges slide to rotate.
- Drill the pre-marked holes. The diameter of the holes is 20 mm.
Diagrams illustrating the steps for preparing the control panel, including hinge assembly and drilling holes.
Fastening the Control Panel
- Drill the fixing points in the control panel in a protected area.
- Fasten the base using screws and plugs. Use Phillips round head screws (maximum diameter 6 mm).
- Insert the cable gland with the corrugated tubes for threading the electrical cables.
Diagrams showing the process of drilling fixing points, fastening the base, and inserting cable glands.
Electrical Connections
Preparing the Electrical Cables
- Connect all wires and cables in compliance with the law.
- Use cable glands to connect the devices to the control panel. One of these must be used exclusively for the power supply cable.
Diagram showing the preparation of electrical cables and their connection via cable glands.
Power Supply
- Connecting to the mains (230/120 V AC - 50/60 Hz): Diagram shows connection to L and N terminals.
- Power supply output for accessories: The output normally delivers 24 V AC. The output delivers 24 V DC when batteries start operating (if installed). The sum of the power draw for connected accessories must not exceed 50 W.
- Connection for the 12 V AC electric lock - 15 W max.: Diagram shows connection for a 12V AC electric lock.
Diagrams illustrating mains connection, accessory power output, and electric lock connection.
Maximum Capacity of Contacts
Device | Output | Power supply (V) | Power (W) |
---|---|---|---|
Accessories | 10 - 11 | 24 AC | 20 |
Additional light | E - E3 | 230 AC | 60 |
Flashing beacon | W - E | 230 AC | 25 |
Operator status warning light | 10 - 5 | 24 AC | 3 |
Gearmotor Wiring Configurations
Gearmotor without Limit Switch
Diagrams showing wiring for gearmotors delayed while opening and closing, connecting to terminals U, V, W, X, Y, E, E3.
Gearmotor with Limit Switch
Diagrams showing wiring for gearmotors with limit switches, including connections for FC, FA, F terminals.
Gearmotor with Encoder
Diagrams showing wiring for gearmotors with encoders, including connections for E+, E-, M1, M2, and specific encoder terminals. Also indicates cable colors (Green, Brown, White).
Command and Control Devices
STOP button (NC contact): Stops the gate and excludes automatic closing. Use a control device to resume movement. If the contact is not used, it must be deactivated during programming.
Control device (NO contact) - OPEN ONLY function: When the [HOLD-TO-RUN] function is active, the control device must be connected during OPENING.
Control device (NO contact) - PARTIAL OPENING function / PEDESTRIAN OPENING function: See Command 2-3P function.
Control device (NO contact) - CLOSE ONLY function: When the [HOLD-TO-RUN] function is active, the control device must be connected during CLOSING.
Control device (NO contact) - OPEN-CLOSE function / OPEN-STOP-CLOSE-STOP function: See control function 2-7.
- 6 Card reader
- 7 Transponder selector switch
- 8 Keypad selector
- 9 Antenna with RG58 cable
Diagrams illustrating connections for various control devices, including buttons, card readers, transponder switches, keypads, and antennas to terminal blocks.
Signalling Devices
- Flashing beacon: Flashes when the operator opens and closes.
- Additional light: Increases light in the manoeuvring area.
- Operator status warning light: Notifies the user of the operator status.
Diagrams showing the wiring for flashing beacons, additional lights, and operator status warning lights.
Safety Devices
During programming, configure the type of action for devices connected to inputs. Connect safety devices to the CX, CY, and/or CZ inputs (NC contacts). If contacts CX, CY, and CZ are not used, they must be deactivated during programming.
DELTA photocells
- Standard connection: Diagram shows standard connection.
- Connection with safety test: See [Safety devices test] function. Diagram shows connection with safety test.
Diagrams illustrating DELTA photocell connections.
DIR / DELTA-S photocells
- Standard connection: Diagram shows standard connection.
- Connection with safety test: See [Safety devices test] function. Diagram shows connection with safety test.
Diagrams illustrating DIR / DELTA-S photocell connections.
DFWN sensitive edge
Diagram showing the connection for a DFWN sensitive edge.
Programming
Programming Button Functions
- ESC button: Used to exit the menu, delete changes, or go back to the previous screen.
- < > buttons: Used to navigate the menu and increase/decrease values.
- ENTER button: Used to access menus and confirm choices.
Diagram showing the control panel with ESC, <, >, ENTER buttons labeled.
Getting Started
Once electrical connections are made, proceed with commissioning. This operation should only be performed by skilled and qualified staff. Ensure there are no obstacles. Power up and proceed with the indicated operations:
- Motor type
- Number of motors
- Total stop
- Travel calibration
After powering up, the first manoeuvre is always to open the gate. Wait for it to complete. Press the ESC or STOP button immediately in case of faults, malfunctions, strange noises, vibrations, or unexpected behaviour. At the end of commissioning, check the device operation using the buttons near the display and verify accessories.
Functions Menu
LANGUAGE
Choose the display language. Options include: [Italiano] (Default), [English], [Français], [Deutsch], [Español], [Português euro], [Português bras].
Automatic closure
Activate automatic closing. Options: [Deactivated], [Activated] (Default).
Hold-to-run
With this function active, opening (command 2-3) or closing (command 2-4) movement is interrupted when the control device is released. It excludes all other control devices.
Options: [Deactivated] (Default), [Activated], [Closing].
Detecting obstacles
With this function active, the gate remains idle if safety devices detect an obstacle. The function is active when the gate is closed, open, or after a complete stop.
Options: [Deactivated] (Default), [Activated].
Safety devices test
Check that photocells connected to inputs are operating correctly after each opening and closing command. Options: [Deactivated] (Default), [CX], [CY], [CZ], [CX+CY], [CX+CZ], [CY+CZ], [CX+CY+CZ].
Pre-flashing
The flashing beacon is activated before each manoeuvre. The pre-flashing duration is set with the [Pre-flashing T.] function.
Options: [Deactivated] (Default), [Activated].
Thrust
Before every opening or closing manoeuvre, the leaves thrust inwards to release the electric lock. The thrust time is set with the [Thrust T.] function.
Options: [Deactivated] (Default), [Close], [Open], [Open-Close].
Total stop
Stop the gate and exclude automatic closing. Use a control device to resume movement.
Options: [Deactivated], [Activated] (Default).
CX input
Associate a function with the CX input. Options: [Deactivated], [C1] = Reopen while closing (Photocells) (Default), [C2] = Reclose while opening (Photocells), [C3] = Partial stop Only with [Automatic close] activated, [C4] = Obstacle standby (Photocells), [C7] = Reopen while closing (sensitive edges), [C8] = Reclose while opening (sensitive edges).
CY input
Associate a function with the CY input. Options: [Deactivated], [C1] = Reopen while closing (photocells), [C2] = Reclose while opening (Photocells), [C3] = Partial stop (Default) Only with [Automatic close] activated, [C4] = Obstacle standby (Photocells), [C7] = Reopen while closing (sensitive edges), [C8] = Reclose while opening (sensitive edges).
CZ input
Associate a function with the CZ input. Options: [Deactivated] (Default), [C1] = Reopen while closing (photocells), [C2] = Reclose while opening (Photocells), [C3] = Partial stop Only with [Automatic close] activated, [C4] = Obstacle standby (Photocells), [C7] = Reopen while closing (sensitive edges), [C8] = Reclose while opening (sensitive edges).
Closing thrust
When the leaves reach the closing limit-switch, the operator performs a closing thrust for a few seconds.
Options: [Deactivated] (Default), [Activated].
Lock
Associate the electric lock release with a command. Options: [Deactivated] (Default), [Close], [Open], [Open-Close].
Configurations
Configure slowdowns and limit switches. [Slow.] and [Op.LS-CI.Slow.] must be configured with the [Slow. T.].
Options: [Slow.] = Slowdown during opening and closing, [Op.LS-CI.Slow.] = Opening limit-switch and closing slowdown, [ENCODER] = Encoder (Default), [Time LS] = Time limit switch, [Limit switch] = Opening and closing limit-switches.
Limit switch
Configure the limit switch contacts as NO or NC. This function only appears when one of the following parameters is selected from the [Config] function: [Limit switch], [Op.LS-CI.Slow.], [Slow.].
Options: [N.C.] (Default), [N.O.].
Command 2-7
Associate a command with the device connected to 2-7. Options: [Open-Close](Default), [Op. Stop Cl.].
Command 2-3P
Associate a command to the connected device on 2-3P. Options: [Partial] (The degree of opening of the leaf is set with the [Part. open] function in the [SET TIME] menu.), [Pedestrian] (Default).
Additional light
Choose the operating mode of the lighting device connected to the output. Options: [Courtesy] (The light stays on for 5 minutes.), [Cycle] (Default) (The lamp stays on during the manoeuvre. The light remains off if an automatic closing time is not set.).
B1-B2 output
Configure the contact. Options: [Monostable] (Button), [Bistable] (Switch) (Default).
Slowdown speed
Set the slowdown speed.
Number of motors
Set the number of motors that control the gate. Options: [M1+M2] (Default), [M2].
Motor type
Set the type of gearmotor installed. Options: [FROG] (Default), [AXO], [FAST], [FERNI], [FROG-PLUS].
Sleep Mode
This reduces the consumption of the photocells when they are in standby.
Options: [Deactivated] (Default), [Activated].
CRP address
Set the peripheral number. This function is needed where there are multiple operators in the same system. Options: from [1] to [32].
CRP Baud rate
Set the communication speed of the remote connection system. Options: [1200], [2400], [4800], [9600], [19200], [38400] (Default), [57600], [115200].
Removing obstacles
If an obstacle is detected by the sensitive edge or by the electronic board, the motion is inverted to create sufficient space to clear the obstacle. If this function is deactivated, the motion is inverted until the limit-switch is reached.
Options: [Deactivated] (Default), [Activated].
Sensitivity
Activate the obstacle-detection sensitivity. Options: [Activated] (Default), [Deactivated]. This function appears only if the [ENCODER] parameter is activated from the [Config] function.
Travel sensitivity
Adjust the obstruction detection sensitivity during boom travel. This function appears only if the [Sensitivity] function is active.
Slowdown sensitivity
Adjust the obstruction detection sensitivity during slowdown. This function appears only if the [Sensitivity] and [Enc. Slow.] functions are active.
Encoder slowdown
Activate the opening and closing slowdown starting points. Options: [ON] (Default), [OFF]. This function appears only if the [ENCODER] parameter is activated from the [Config] function.
Opening slowdown point for M1
Set the opening slowdown starting point for M1 (percentage of the total travel). Options: From 1% to 60% (Default 10%). This function appears only if the [Enc. Slow.] function is active.
M1 closing slowdown point
Set the closing slowdown starting point for M1 (percentage of the total travel). Options: From 1% to 60% (Default 10%). This function appears only if the [Enc. Slow.] function is active.
Opening slowdown point for M2
Set the opening slowdown starting point for M2 (percentage of the total travel). Options: From 1% to 60% (Default 10%). This function appears only if the [Enc. Slow.] function is active.
M2 closing slowdown point
Set the closing slowdown starting point for M2 (percentage of the total travel). Options: From 1% to 60% (Default 10%). This function appears only if the [Enc. Slow.] function is active.
M1 closing approach point
Set the closing approach starting point for M1 (percentage of the total travel). Options: From 1% to 15% (Default 15%). This function appears only if the [ENCODER] parameter is activated from the [Config] function.
Closing approach point for M2
Set the closing approach starting point for M2 (percentage of the total travel). Options: From 1% to 15% (Default 15%). This function appears only if the [ENCODER] parameter is activated from the [Config] function.
M1 opening approach point
Set the opening approach starting point for M1 (percentage of the total travel). Options: From 1% to 15% (Default 15%). This function appears only if the [ENCODER] parameter is activated from the [Config] function.
M2 opening approach point
Set the opening approach starting point for M2 (percentage of the total travel). Options: From 1% to 15% (Default 15%). This function appears only if the [ENCODER] parameter is activated from the [Config] function.
Travel calibration
Start the travel self-learning. Options: [Confirm? (No)], [Confirm? (Yes)]. This function appears only if the [ENCODER] parameter is activated from the [Config] function.
Automatic closing time
Set the time before automatic closure is activated, once the opening travel end point has been reached. The function does not work if any of the safety devices are triggered when an obstacle is detected, or after a complete stop, or during a power outage.
Options: from 0 to 300 seconds (Default 10 seconds).
Pedestrian automatic closing time
Set the time that must pass before automatic closing is activated, once the limit switch has been reached for a pedestrian opening (complete opening of only one of the two leaves) or partial opening (partial opening of only one of the two leaves).
Options: from 0 to 300 seconds (Default 10 seconds).
Operating time
Set the gearmotor working time during opening and closing.
Options: from 10 to 150 seconds (Default 90 seconds).
M1 opening delay
Adjust the delay in starting the opening manoeuvre for M1 with respect to M2.
Options: from 0 to 10 seconds (Default 2 seconds).
M2 closing delay
Adjust the delay in starting the closing manoeuvre for M2 with respect to M1.
Options: from 0 to 60 seconds (Default 2 seconds).
Pre-flashing time
Set the time for which the beacon is activated before each manoeuvre.
Options: from 1 to 60 seconds (Default 5 seconds).
Electric lock time
Adjust the electric lock release time after an opening or closing command.
Options: from 1 to 5 seconds (Default 2 seconds).
Thrust time
Adjust the gearmotor closing thrust time after an opening or closing command.
Options: from 1 to 10 seconds (Default 1 second).
Partial opening time
Adjust M2 opening time.
Options: from 5 to 60 seconds (Default 10 seconds).
Slowdown time
Set the slowdown time before each limit switch. This function appears only with the [Op.LS-CI.Slow.] or [Slow.] parameters from the [Config] function.
Options: [OFF], from [0 s] to [30 s] (Default 5 s).
User Management
New user
Register up to a maximum of 250 users and assign a function to each one. The operation can be carried out by using a transmitter or another control device. The boards that manage the control devices (AF - R700 - R800) must be inserted into the connectors.
Options: [Deactivated], [2-7] (Step-by-step or sequential control), [Open], [B1-B2], [2-3P] (Pedestrian or partial opening).
Edit name
Change the username or associated number.
Edit code
Modify the code of a command associated to a user.
Associated function
Associate a function with the user. Options: [2-7] (Step-by-step or sequential control) (Default), [Open], [B1-B2], [2-3P] (Pedestrian or partial opening).
Remove user
Remove one of the registered users.
Remove all
Remove all registered users.
Sensor type
Set the type of control device. Options: [Keypad] (Default), [Transponder].
Save memory
Save the system users and settings in the Memory Roll. Options: [Confirm? (No)], [Confirm? (Yes)]. Press ENTER to confirm.
Load the memory
Load the users and system settings from the Memory Roll. The boards must be the same version, otherwise only the users can be loaded. Options: [Confirm? (No)], [Confirm? (Yes)].
Radio decoding
Choose the type of radio coding for the transmitters enabled to control the operator. If you choose [Rolling code] or [TW key block], any transmitters with a different type of radio coding saved previously will be deleted.
Options: [All decoding], [Rolling code], [TW Key block].
Self-Learning
Save a new transmitter by copying an existing one without following the add new user procedure [New User]. Options: [Deactivated] (Default), [Activated].
Version
Display the firmware version number.
No. runs
Display the number of completed manoeuvres.
Initial message
Change the initial message. Options: [WWW.CAME.COM] (Default). Process: Press ENTER to change the initial message. Use ENTER to move cursor forwards, ESC to move backwards. Use arrows to select a letter or number. Press and hold ENTER for a few seconds to confirm.
Resetting the system
Restore factory settings. Options: [Confirm? (No)], [Confirm? (Yes)]. Press ENTER to confirm.
Motor test
Check the gate leaves open in the right direction. Press and hold the '<' button: Check that M1 performs opening. Press and hold the '>' button: Check that M2 performs opening. If the leaf does not move in the correct direction, invert the motor phases.
Password
Set a 4-digit password to access the main menu. Options: [Confirm? (No)], [Confirm? (Yes)]. Use the arrows to select a number. Press ENTER to confirm. Enter the password again.
Change password
Change the password. Options: [Confirm? (No)], [Confirm? (Yes)]. Use the arrows to select a number. Press ENTER to confirm. Enter the password again.
Remove password
Remove the password. Options: [Confirm? (No)], [Confirm? (Yes)].
Error Messages
Error Type | Description |
---|---|
Encoder - ERROR | The Encoder is disconnected. The Encoder is broken. |
Error! | The Encoder is disconnected. The Encoder is broken. |
Safety test - ERROR | The photocells are not correctly connected or configured. |
Limit-switch - ERROR | Malfunctioning limit-switch contacts. |
Operating time - ERROR | Finished the maximum work time set. |
Safety devices - STOP | Contact 1-2 (NC) is open. |
C1 | The (NC) contacts are open. |
C3 | The (NC) contacts are open. |
C4 | The (NC) contacts are open. |
C7 | The (NC) contacts are open. |
C8 | The (NC) contacts are open. |
Final Operations
Before closing up the casing, check that the cable inlets are sealed to stop insects getting in and to prevent damp.
Diagrams illustrating the final operations of sealing cable inlets.