AIRMASTER AM 1200 V with Ø315 Top Hat Module

Technical Characteristics

Characteristic Filter Class 30 dB(A) 33 dB(A) 35 dB(A)
Max. Capacity 1
Vertical, right/left model 2
ePM10 50% 820 m³/h 940 m³/h 1060 m³/h
ePM1 55% 738 m³/h 846 m³/h 954 m³/h
ePM1 80% 656 m³/h 752 m³/h 848 m³/h
Max. Capacity 1
Vertical, center model 2
ePM10 50% 920 m³/h 1045 m³/h 1170 m³/h
ePM1 55% 828 m³/h 941 m³/h 1053 m³/h
ePM1 80% 736 m³/h 836 m³/h 936 m³/h
Airflow (0.2 m/s) 1 - right/left: min. 4 m @ 1000 m³/h 9 m @ 1000 m³/h 5.5 m @ 1300 m³/h
max. 11 m @ 1300 m³/h
Airflow (0.2 m/s) 1 - center: min. 3 m @ 1000 m³/h 6.5 m @ 1000 m³/h 4 m @ 1300 m³/h
max. 8 m @ 1300 m³/h
Fresh Air Filter ePM10 50%, ePM1 55% or ePM1 80%
Return Air Filter ePM10 50%
Dimensions (WxHxD) Horizontal: 496 x 2098 x 2427 mm
Vertical: 496 x 2406 x 2427 mm
Weight Right/left version: 565 kg
Central version: 630 kg
Casing Color RAL 7024
Counter-current Exchanger 4 x Aluminium
Density Class (air leakage) EN1886/EN13141-7 Class L2 / A2
Damper Density Class EN1751 Class 3
IP Code 10
Duct Connection Ø400 mm
Condensate Pump (Capacity; Head at 5 l/h) 10 l/h; 6 m
Internal / External Condenser Ø4 mm / Ø6 mm
Power Supply Voltage 3 220-240V/50Hz, ~1N+PE
220-240V/50Hz, ~3N+PE
Nominal Power 1 254 W
Nominal Current 1 1.4 A
Power Factor 0.6
Max. Current 16 A (1 phase, type B) / 3 x 16 A (3 phases, type B)
(For heating surface selection, a three-phase connection must be used)
Leakage Current AC / DC ≤ 9 mA
Recommended Fault Current Relay Type B

1 All measurements are performed under normal operating conditions in a standard installation situation with top hat modules recommended by AIRMASTER.

2 With top hat module.

3 Possibility to limit the single-phase supply, connected to L1. Only for units without electric heating battery.

Heating Batteries

Electric Heating Battery

Characteristic Pre-heating Battery Post-heating Battery
Heat Output 2500 W 1670 W
Nominal Current 10.9 A 7.3 A
Thermal Protection, manual reset 100 °C 100 °C

Hot Water Battery

Nominal Heat Output 4 2454 W
Connection Dimension 1/2" (DN 15)
Pipe/Fin Material Copper/aluminium
Motorized Valve Open/Close Time 60 s
Max. Operating Temperature 90 °C
Optimal Operating Pressure 5 bar

4 Heat output at maximum capacity of 35 dB(A), flow temperature/return temperature 60/40°C and liquid flow of 107 l/h.

Performance Data

Airflow Capacity vs. Pressure

The following graphs illustrate the airflow capacity (m³/h) on the x-axis versus pressure (Pa) on the y-axis, for different filter types (ePM10 50%, ePM1 55%, ePM1 80%) and sound pressure levels (30, 33, 35 dB(A)).

Sound Pressure Level (LpA,eq)

This graph shows the sound pressure level (LpA,eq in dB(A)) on the y-axis against airflow (m³/h) on the x-axis, for 'Right/Left' and 'Center' configurations. Measurements are taken at 1.2m height, 1m horizontal distance from the unit, in a 200 m³ room with T=0.6s reverberation time and 7.5 dB sound insulation.

Temperature Efficiency (EN 308)

This graph displays the temperature efficiency (%) on the y-axis as a function of airflow (m³/h) on the x-axis. Operating conditions are balanced air: 25°C, 28% RH; outside air: 5°C.

Power Consumption

This graph shows the power consumption (W) on the y-axis versus airflow (m³/h) on the x-axis, for the ePM10 50% / ePM10 50% filter configuration.

Specific Fan Power (SFP)

This graph shows Specific Fan Power (Ws/m³) on the y-axis against airflow (m³/h) on the x-axis, for the ePM10 50% / ePM10 50% filter configuration.

Static Pressure - Fresh Air

This graph illustrates static pressure (Pa) on the y-axis versus airflow (m³/h) on the x-axis for fresh air, showing data for 'Center' and 'Right/Left' configurations with 30 dB(A) and 35 dB(A) sound levels, and ePM10 50% filters.

Static Pressure - Return Air

This graph illustrates static pressure (Pa) on the y-axis versus airflow (m³/h) on the x-axis for return air, showing data for 'Center' and 'Right/Left' configurations with 30 dB(A) and 35 dB(A) sound levels, and ePM10 50% filters.

Airflow Range and Mounting Types

Airflow Range (0.2 m/s)

The airflow range of the AM 1200 units varies with airflow rate. The blue zones in the diagram illustrate the jet throw range based on airflow.

Mounting Types

The AM 1200 units are available in various configurations:

Standard and Options

The following table details the standard features and available options for the AIRMASTER AM 1200 V unit.

Feature Status
Counter-current Exchanger (aluminium) Standard (X)
Enthalpic counter-current exchanger (Polymer membrane) Option (•)
Combined counter-current exchanger (Polymer membrane) Special Article (o)
By-pass motorized Standard (X)
Fresh air damper with spring return Standard (X)
Return air damper with spring return Standard (X)
Electric pre-heating battery Option (•)
Electric post-heating battery Option (•)
Hot water battery Option (•)
Condensate pump Standard (X)
PIR/motion sensor (wall-mounted) Option (•)
CO2 sensor (wall-mounted) Standard (X)
CO2 sensor (integrated) Option (•)
TVOC sensor (integrated) Option (•)
CO2/TVOC sensor (integrated) Standard (X)
Hygrostat (wall-mounted) Special Article (o)
Energy meter Option (•)
Fresh air filter ePM10 50% Standard (X)
Fresh air filter ePM1 55% Option (•)
Fresh air filter ePM1 80% Special Article (o)
Return air filter ePM10 50% Standard (X)
Control panel Airling Viva Option (•)
Control panel Airling Orbit Option (•)
Airmaster Airlinq® Online Option (•)
Airlinq® Online API Option (•)
Airlinq® BMS Option (•)
LON® Module Special Article (o)
KNX® Module Special Article (o)
MODBUS® RTU RS485 Module Option (•)
BACnet™ MS/TP Module Option (•)
BACnet™ /IP Module Option (•)

Principle Diagram

The principle diagram illustrates the airflow path and components of the AIRMASTER AM 1200 unit:

PDF preview unavailable. Download the PDF instead.

15939 ds am1200v-oe315 fr rev04 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Windows)

Related Documents

Preview Airmaster AM 150 Data Sheet: Technical Specifications and Performance
Detailed data sheet for the Airmaster AM 150 air handling unit, covering technical specifications, performance charts, filter classes, sound pressure levels, temperature efficiency, power consumption, and version overviews.
Preview Airmaster CC150 Ventilation Unit Technical Drawings and Specifications
Detailed technical drawings and contact information for Airmaster ventilation units, including the CC150 model. Provides an overview of components and multilingual terminology for ventilation functions.
Preview AIRMASTER AM 950 C / AM 950 F Installation and Mounting Manual
A comprehensive guide for the installation and mounting of AIRMASTER AM 950 C and AM 950 F ventilation units. This manual provides detailed instructions, safety precautions, technical specifications, and step-by-step procedures for a correct and safe setup.
Preview AirMaster AM 950 F SSL Technical Specifications and Dimensions
Detailed technical specifications, dimensions, and connection information for the AirMaster AM 950 F SSL ventilation unit. Includes multilingual terminology for key components.
Preview Air Handling Unit AM 950 F HH + VV - Technical Overview
Detailed technical overview and specifications for the AIRMASTER AM 950 F HH + VV air handling unit, including dimensions, connection points, and mounting options.
Preview Airmaster AM 950 C / AM 950 F Installation and Mounting Guide
Comprehensive guide for the correct and safe installation and mounting of Airmaster AM 950 C and AM 950 F ventilation units. Includes safety instructions, product specifications, and step-by-step mounting procedures.
Preview Airmaster AMX4: Advanced All-in-One Ventilation, Heating, and Cooling System
Discover the Airmaster AMX4, a revolutionary all-in-one indoor climate solution that integrates ventilation, heating, and cooling. Learn about its energy efficiency, advanced control features, quiet operation, and seamless integration for optimal comfort.
Preview Airmaster AM 950 C & AM 950 F Mounting Guide
Detailed mounting instructions for Airmaster AM 950 C and AM 950 F air handling units, covering safety, installation procedures, specifications, and handling.