USER MANUAL
3.5KW/5.5KW PLUS
INVERTER / MPPT SCC / AC CHARGER
VERSION: 1.0
1 ABOUT THIS MANUAL
This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
This manual provides safety and installation guidelines as well as information on tools and wiring.
2 SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3 INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
3.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:
- Generator or Utility
- PV modules
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.
Diagram: A hybrid power system diagram showing solar panels connected to the inverter, a generator/utility connection to the inverter, external battery packs connected to the inverter, and home appliances connected to the inverter's output.
3.3 Product Overview
Diagram: Figure 1 Hybrid Power System showing the inverter unit with numbered components.
Component List:
- 1. LCD display
- 2. Status indicator
- 3. Charging indicator
- 4. Fault indicator
- 5. Function buttons
- 6. Power on/off switch
- 7. AC input
- 8. AC output
- 9. PV input
- 10. Battery input
- 11. Circuit breaker
- 12. USB communication port
- 13. RS-232 communication port
4 INSTALLATION
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
- The unit x 1
- User manual x 1
- Communication cable x 1
- Software CD x 1
- DC Fuse x 1
- Ring terminal x 1
- Strain relief plate x 1
- PV wire cover x 1
- Screws x 4
4.2 Preparation
Before connecting all wirings, please take off the bottom cover by removing two screws as shown below.
Diagram: Illustration showing how to remove the bottom cover by unscrewing two screws.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
Diagram: Illustration showing the unit with recommended clearance dimensions: 20cm side, 50cm top/bottom.
NOTICE: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
Model | Wire Size | Cable (mm²) | Torque value (max) |
---|---|---|---|
3.5KW/5.5KW | 1 x 2AWG | 35 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix strain relief plate to the inverter by supplied screws as shown in below chart.
Diagram: Illustration showing insulation removal and ferrule application.
Diagram: Illustration showing strain relief plate attachment.
Diagram: Battery connection diagrams for 3.5KW (two 12V batteries in series) and 5.5KW (four 12V batteries in series).
5. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver
6. To firmly secure wire connection, you may fix the wires to strain relief with cable tie.
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 3.5KW and 50A for 5.5KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model | Gauge | Cable (mm²) | Torque Value |
---|---|---|---|
3.5KW | 12 AWG | 4 | 1.2 Nm |
5.5KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (Ground: yellow-green) first.
- Diagram: Illustration showing AC input terminal block wiring with Ground, Line, and Neutral connections.
- WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor (Ground: yellow-green) first.
- Diagram: Illustration showing AC output terminal block wiring with Ground, Line, and Neutral connections.
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
PV Module Connection Cable Requirement:
Model | Wire Size | Cable (mm²) | Torque value (max) |
---|---|---|---|
3.5KW/5.5KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL | 3.5KW | 5.5KW |
---|---|---|
Max. PV Array Open Circuit Voltage | 500Vdc | 500Vdc |
PV Array MPPT Voltage Range | 120Vdc~450Vdc | 120Vdc~450Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power | |
---|---|---|---|---|
250Wp Vmp: 30.1Vdc Imp: 8.3A Voc: 37.7Vdc Isc: 8.4A Cells: 60 |
6 pcs in serial | 6 pcs | 1500W | |
8 pcs in serial | 8 pcs | 2000W | ||
12 pcs in serial | 12 pcs | 3000W | ||
13 pcs in serial | 13 pcs | 3250W | ||
8 pieces in serial and 2 sets in parallel | 16 pcs | 4000W | ||
10 pieces in serial and 2 sets in parallel | 20 pcs | 5000W |
PV Module Wire Connection
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix PV wire cover to the inverter with supplied screws as shown in below chart.
Diagram: Illustration showing PV wire connection and cover attachment.
4. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Screw two wires tightly in clockwise direction.
Recommended tool: 4mm blade screwdriver
4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
Diagram: Illustration showing the unit with the bottom cover re-attached.
4.8 Communication Connection
- Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and follow on-screen instruction to install the monitoring software. For the detailed software operation, please check user manual of software inside of CD.
- Wi-Fi cloud communication (option): Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and install from APP store, and Refer to “Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
- GPRS cloud communication (option): Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and install from APP store, and Refer to “GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
5 OPERATION
5.1 Power ON/OFF
Diagram: Side view of the unit showing the power on/off switch.
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys, and a LCD display, indicating the operating status and input/output power information.
Diagram: Front panel of the inverter showing LCD Display and LED Indicators.
LED Indicator
LED Indicator | Color | Messages |
---|---|---|
AC/INV | Green | Solid On: Output is powered by utility in Line mode. Flashing: Output is powered by battery or PV in battery mode. |
CHG | Green | Solid On: Battery is fully charged. Flashing: Battery is charging. |
FAULT | Red | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
Input Source Information:
- AC: Indicates the AC input.
- PV: Indicates the PV input.
Input/Battery/Output Information:
- INPUTBATTTEMP: Indicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.5K models), charger power, battery voltage.
- OUTPUTBATTLOAD: Indicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Configuration Program and Fault Information:
- 88 (with gear icon): Indicates the setting programs.
- 8.8 (with warning icon): Indicates the warning and fault codes. (Warning: 8.8 flashing with warning code. Fault: 8.8 lighting with fault code)
Battery Information:
- CHARGING: Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.
In AC mode, it will present battery charging status.
Status | Battery voltage | LCD Display |
---|---|---|
Constant | <2V/cell | 4 bars will flash in turns. |
Constant | 2 ~ 2.083V/cell | Bottom bar will be on and the other three bars will flash in turns. |
Current mode / Voltage mode | 2.083 ~ 2.167V/cell | Bottom two bars will be on and the other two bars will flash in turns. |
> 2.167 V/cell | Bottom three bars will be on and the top bar will flash. |
Floating mode. Batteries are fully charged. 4 bars will be on.
In battery mode, it will present battery capacity.
Load Percentage | Battery Voltage | LCD Display |
---|---|---|
Load >50% | < 1.85V/cell | Diagram: Battery icon with 1 bar filled. |
1.85V/cell ~ 1.933V/cell | Diagram: Battery icon with 2 bars filled. | |
1.933V/cell ~ 2.017V/cell | Diagram: Battery icon with 3 bars filled. | |
> 2.017V/cell | Diagram: Battery icon with 4 bars filled. | |
Load < 50% | < 1.892V/cell | Diagram: Battery icon with 1 bar filled. |
1.892V/cell ~ 1.975V/cell | Diagram: Battery icon with 2 bars filled. | |
1.975V/cell ~ 2.058V/cell | Diagram: Battery icon with 3 bars filled. | |
> 2.058V/cell | Diagram: Battery icon with 4 bars filled. |
Load Information
- OVER LOAD: Indicates overload.
- Diagram: Load level indicators showing 0%-24%, 25%-49%, 50%-74%, 75%-100%.
Mode Operation Information:
- Diagram: Icon indicating unit connects to the mains.
- Diagram: Icon indicating unit connects to the PV panel.
- BYPASS: Indicates load is supplied by utility power.
- Diagram: Icon indicating the utility charger circuit is working.
- Diagram: Icon indicating the DC/AC inverter circuit is working.
Mute Operation
- Indicates unit alarm is disabled.
5.4 LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP" or “DOWN" button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to exit.
Setting Programs:
Program | Description | Selectable option | Explanation |
---|---|---|---|
00 | Exit setting mode | ESC | |
01 | Output source priority: To configure load power source priority |
Utility first (default) | Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available. |
Solar first | Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time. |
||
SBU priority | Battery provides power to the loads only when any one condition happens: - Solar energy and utility is not available. - Solar energy is not sufficient and utility is not available. |
||
Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12. |
|||
02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) |
10A | |
20A | |||
30A | |||
40A | |||
50A | |||
60A (default) | |||
70A | |||
80A | |||
90A | |||
100A | |||
03 | AC input voltage range | Appliances (default) | If selected, acceptable AC input voltage range will be within 90-280VAC. |
UPS | If selected, acceptable AC input voltage range will be within 170-280VAC. | ||
05 | Battery type | AGM (default) | If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. |
Flooded | |||
06 | Auto restart when overload occurs | Restart disable (default) | Restart enable |
Restart enable | |||
07 | Auto restart when over temperature occurs | Restart disable (default) | Restart enable |
Restart enable | |||
09 | Output frequency | 50Hz (default) | 60Hz |
60Hz | |||
10 | Output voltage | 220V | 230V (default) |
240V | 230V | ||
11 | Maximum utility charging current | 2A | 10A |
20A | 20A | ||
40A | 50A | ||
60A | 80A | ||
12 | Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01. | 22.0V | 22.5V |
23.0V (default) | 23.5V | ||
24.0V | 24.5V | ||
25.0V | 25.5V | ||
Available options in 5.5KW model: | |||
44V | 45V | ||
46V (default) | 47V | ||
48V | 49V | ||
50V | 51V | ||
52V | 53V | ||
13 | Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" in program 01. | Battery fully charged | 24V |
24.5V | 25V | ||
25.5V | 26V | ||
26.5V | 27V (default) | ||
27.5V | 28V | ||
28.5V | 29V | ||
Available options in 5.5KW model: | |||
Battery fully charged | 48V | ||
49V | 50V | ||
51V | 52V | ||
53V | 54V (default) | ||
55V | 56V | ||
57V | 58V | ||
16 | Charger source priority: To configure charger source priority |
Utility first | Utility will charge battery as first priority. Solar energy will charge battery only when utility power is not available. |
Solar first | Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available. |
||
Solar and Utility (default) | Solar energy and utility will charge battery at the same time. | ||
Only Solar | Solar energy will be the only charger source no matter utility is available or not. If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient. |
||
18 | Alarm control | Alarm on (default) | Alarm off |
Alarm off | |||
19 | Auto return to default display screen | Return to default display screen (default) | If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute. |
Stay at latest screen | If selected, the display screen will stay at latest screen user finally switches. | ||
20 | Backlight control | Backlight on (default) | Backlight off |
Backlight off | |||
22 | Beeps while primary source is interrupted | Alarm on (default) | Alarm off |
Alarm off | |||
23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. |
Bypass disable (default) | Bypass enable |
Bypass enable | |||
25 | Record Fault code | Record enable (default) | Record disable |
Record disable | |||
26 | Bulk charging voltage (C.V voltage) |
3.5KW default setting: 28.2V | 5.5KW default setting: 56.4V |
If self-defined is selected in program 5, this program can be set up. Setting range is from 25.0V to 31.5V for 3.5KW model and 48.0V to 61.0V for 5.5KW model. Increment of each click is 0.1V. | |||
27 | Floating charging voltage | 3.5KW default setting: 27.0V | 5.5KW default setting: 54.0V |
If self-defined is selected in program 5, this program can be set up. Setting range is from 25.0V to 31.5V for 3.5KW model and 48.0V to 61.0V for 5.5KW model. Increment of each click is 0.1V. | |||
29 | Low DC cut-off voltage | 3.5KW default setting: 20.0V | 5.5KW default setting: 40.0V |
If self-defined is selected in program 5, this program can be set up. Setting range is from 21.0V to 24.0V for 3.5KW model and 42.0V to 48.0V for 5.5KW model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. | |||
30 | Battery equalization | Battery equalization enable (default) | Battery equalization disable (default) |
Battery equalization disable | |||
31 | Battery equalization voltage | 3.5KW default setting: 29.2V | 5.5KW default setting: 58.4V |
Setting range is from 25.0V to 31.5V for 3.5KW model and 48.0V to 61.0V for 5.5KW model. Increment of each click is 0.1V. | |||
33 | Battery equalized time | 60min (default) | Setting range is from 5min to 900min. Increment of each click is 5min. |
34 | Battery equalized timeout | 120min (default) | Setting range is from 5min to 900 min. Increment of each click is 5 min. |
35 | Equalization interval | 30days (default) | Setting range is from 0 to 90 days. Increment of each click is 1 day |
36 | Equalization activated immediately | Enable | Disable (default) |
Disable | If equalization function is enabled in program 30, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows "E9". If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 35 setting. At this time, "E9" will not be shown in LCD main page. | ||
50 | AC charger ON timer | AC charger start from 00:00 to 23:00. (Default 00:00) | |
51 | AC charger OFF timer | AC charger stops from 00:00 to 23:00. (Default 00:00) | |
52 | AC output ON timer | AC output on from 00:00 to 23:00. (Default 00:00) | |
53 | AC output OFF timer | AC output off from 00:00 to 23:00. (Default 00:00) | |
54 | Real time setting---Minute | Default 00, range 00~59 | |
55 | Real time setting---Hour | Default 00, range 00~23 | |
56 | Real time setting---Date | Default 01, range 01~31 | |
57 | Real time setting---Month | Default 01, range 01~12 | |
58 | Real time setting---Year | Default 16, range 16~99 | |
5.5 Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.
Selectable information
LCD display
Input voltage/Output voltage (Default Display Screen) |
Diagram: LCD showing Input Voltage=230V, Output voltage=230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Input frequency | Diagram: LCD showing Input frequency=50Hz. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
PV voltage | Diagram: LCD showing PV voltage=260V, Output=230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
PV current | Diagram: LCD showing PV current = 2.5A, Output=230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
PV power | Diagram: LCD showing PV power = 500W, Output=230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Charging current | AC and PV charging current=50A Diagram: LCD showing BATT current 50A, OUTPUT 230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
PV charging current=50A Diagram: LCD showing BATT current 50A, OUTPUT 230V. Includes PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
|
AC charging current=50A Diagram: LCD showing BATT current 50A, OUTPUT 230V. Includes AC, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
|
Charging power | AC and PV charging power=500W Diagram: LCD showing BATT 500W, OUTPUT 230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
PV charging power=500W Diagram: LCD showing BATT 500W, OUTPUT 230V. Includes PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
|
AC charging power=500W Diagram: LCD showing BATT 500W, OUTPUT 230V. Includes AC, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
|
Battery voltage and output voltage | Battery voltage=25.5V, output voltage=230V Diagram: LCD showing BATT 25.5V, OUTPUT 230V. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Output frequency | Output frequency=50Hz Diagram: LCD showing BATT 25.5V, OUTPUT 50.0Hz. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Load percentage | Load percent=70% Diagram: LCD showing BATT 25.5V, LOAD 70%. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Load in VA | When connected load is lower than 1kVA, load in VA will present xxxVA like below chart. Diagram: LCD showing BATT 25.5V, LOAD 350VA. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). When load is larger than 1kVA (≥ 1KVA), load in VA will present x.xkVA like below chart. Diagram: LCD showing BATT 25.5V, LOAD 1.50kVA. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Load in Watt | When load is lower than 1kW, load in W will present xxxW like below chart. Diagram: LCD showing BATT 25.5V, LOAD 270W. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). When load is larger than 1kW (≥1KW), load in W will present x.xkW like below chart. Diagram: LCD showing BATT 25.5V, LOAD 1.20kW. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Battery voltage/DC discharging current | Battery voltage=25.5V, discharging current=1A Diagram: LCD showing BATT 25.5V, BATT 1A. Includes AC, PV, BYPASS, CHARGING icons and load percentage indicators (100%, 25%). |
Main CPU version checking:
Diagram: LCD showing Main CPU version 20 09.
5.6 Operating Mode Description
Operation mode | Description | LCD display |
---|---|---|
Standby mode / Power saving mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output. *Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected. |
No output is supplied by the unit but it still can charge batteries. | Diagram: LCD showing Charging by utility and PV energy. Diagram: LCD showing Charging by utility. Diagram: LCD showing Charging by PV energy. Diagram: LCD showing No charging. |
Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on. |
PV energy and utility can charge batteries. | Diagram: LCD showing Charging by utility and PV energy. Diagram: LCD showing Charging by utility. Diagram: LCD showing Charging by PV energy. Diagram: LCD showing No charging. |
Line Mode | The unit will provide output power from the mains. It will also charge the battery at line mode. | Diagram: LCD showing Charging by utility and PV energy. Diagram: LCD showing Charging by utility. |
The unit will provide output power from the mains. It will also charge the battery at line mode. | If "solar first" is selected as output source priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time. If "solar first" is selected as output source priority and battery is not connected, solar energy and the utility will provide the loads. |
|
Diagram: LCD showing Power from utility. | ||
Battery Mode | The unit will provide output power from battery and PV power. | Diagram: LCD showing Power from battery and PV energy. PV energy will supply power to the loads and charge battery at the same time. |
The unit will provide output power from battery and PV power. | Diagram: LCD showing Power from battery only. Diagram: LCD showing Power from PV energy only. |
5.7 Battery Equalization Description
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
Diagram: Graph showing battery charging stages (BULK, ABSORPTION, FLOAT, EQUALIZE, FLOAT) with voltage progression over time.
Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
Diagram: Graph showing battery charging stages with equalization timeout, illustrating voltage progression over time.
5.8 Fault Reference Code
Fault Code | Fault Event | Icon on |
---|---|---|
01 | Fan is locked when inverter is off. | Diagram: Icon 01. |
02 | Over temperature | Diagram: Icon 02. |
03 | Battery voltage is too high | Diagram: Icon 03. |
04 | Battery voltage is too low | Diagram: Icon 04. |
05 | Output short circuited or over temperature is detected by internal converter components. | Diagram: Icon 05. |
06 | Output voltage is too high. | Diagram: Icon 06. |
07 | Overload time out | Diagram: Icon 07. |
08 | Bus voltage is too high | Diagram: Icon 08. |
09 | Bus soft start failed | Diagram: Icon 09. |
51 | Over current or surge | Diagram: Icon 51. |
52 | Bus voltage is too low | Diagram: Icon 52. |
53 | Inverter soft start failed | Diagram: Icon 53. |
55 | Over DC voltage in AC output | Diagram: Icon 55. |
57 | Current sensor failed | Diagram: Icon 57. |
58 | Output voltage is too low | Diagram: Icon 58. |
59 | PV voltage is over limitation | Diagram: Icon 59. |
5.9 Warning Indicator
Warning Code | Warning Event | Audible Alarm | Icon flashing |
---|---|---|---|
01 | Fan is locked when inverter is on. | Beep three times every second | Diagram: Icon 01 flashing. |
03 | Battery is over-charged | Beep once every second | Diagram: Icon 03 flashing. |
04 | Low battery | Beep once every second | Diagram: Icon 04 flashing. |
07 | Overload | Beep once every 0.5 second | Diagram: Icon OVER LOAD flashing. |
10 | Output power derating | Beep twice every 3 seconds | Diagram: Icon 10 flashing. |
15 | PV energy is low. | Beep twice every 3 seconds | Diagram: Icon 15 flashing. |
E9 | Battery equalization | None | Diagram: Icon E9 flashing. |
6P | Battery is not connected | None | Diagram: Icon 6P flashing. |
6 CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT
6.1 Overview
Every inverter is already installed with anti-dusk kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dusk from your inverter and increases product reliability in harsh environment.
6.2 Clearance and Maintenance
Step 1: Please loosen the screw in counterclockwise direction on the top of the inverter.
Diagram: Illustration showing screws on top of the inverter to be loosened.
Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.
Diagram: Illustration showing the dustproof case being removed and air filter foam extracted.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7 SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | 3.5KW | 5.5KW |
---|---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
|
Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
|
High Loss Voltage | 280Vac±7V | |
High Loss Return Voltage | 270Vac±7V | |
Max AC Input Voltage | 300Vac | |
Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
Low Loss Frequency | 40±1Hz | |
Low Loss Return Frequency | 42±1Hz | |
High Loss Frequency | 65±1Hz | |
High Loss Return Frequency | 63±1Hz | |
Output Short Circuit Protection | Circuit Breaker | |
Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
|
Output power derating: When AC input voltage drops to 170V, the output power will be derated. |
Diagram: Graph showing Output Power vs. Input Voltage. Rated Power is constant until 170V, then derates to 50% Power at 90V. |
Table 2 Inverter Mode Specifications
INVERTER MODEL | 3.5KW | 5.5KW |
---|---|---|
Rated Output Power | 3.5KW | 5.5KW |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 93% | |
Overload Protection | 5s@≥150% load; 10s@110%~150% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 24Vdc | 48Vdc |
Cold Start Voltage | 23.0Vdc | 46.0Vdc |
Low DC Warning Voltage | @load < 50%: 22.0Vdc @load ≥ 50%: 21.0Vdc |
@load < 50%: 44.0Vdc @load ≥ 50%: 42.0Vdc |
Low DC Warning Return Voltage | @load < 50%: 22.5Vdc @load ≥ 50%: 22.0Vdc |
@load < 50%: 45.0Vdc @load ≥ 50%: 44.0Vdc |
Low DC Cut-off Voltage | @load < 50%: 20.5Vdc @load ≥ 50%: 20.0Vdc |
@load < 50%: 41.0Vdc @load ≥ 50%: 40.0Vdc |
High DC Recovery Voltage | 32Vdc | 62Vdc |
High DC Cut-off Voltage | 33Vdc | 63Vdc |
No Load Power Consumption | <35W |
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL | 3.5KW | 5.5KW |
---|---|---|
Charging Algorithm | 3-Step | |
AC Charging Current (Max) | 80Amp (@VI/P=230Vac) | 80Amp (@VI/P=230Vac) |
Bulk Charging Voltage | Flooded Battery: 29.2V AGM / Gel Battery: 28.2V |
Flooded Battery: 58.4V AGM / Gel Battery: 56.4V |
Floating Charging Voltage | 27Vdc | 54Vdc |
Charging Curve | Diagram: Graph showing Charging Curve with Voltage and Current vs. Time, illustrating Bulk, Absorption, and Maintenance stages. |
MPPT Solar Charging Mode
INVERTER MODEL | 3.5KW | 5.5KW |
---|---|---|
Max. PV Array Power | 5000W | 6000W |
Nominal PV Voltage | 240Vdc | |
PV Array MPPT Voltage Range | 120~450Vdc | |
Max. PV Array Open Circuit Voltage | 500Vdc | |
Max Charging Current (AC charger plus solar charger) | 100Amp | 100Amp |
Table 4 General Specifications
INVERTER MODEL | 3.5KW | 5.5KW |
---|---|---|
Safety Certification | CE | |
Operating Temperature Range | -10°C to 50°C | |
Storage temperature | -15°C~60°C | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Dimension (D*W*H), mm | 100 x 300 x 440 | |
Net Weight, kg | 9.5 | 9.7 |
8 TROUBLE SHOOTING
Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
---|---|---|---|
Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
|
Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. |
Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
Fault code 03 | Battery is over-charged. | Return to repair center. Check if spec and quantity of batteries are meet requirements. |
|
Fault code 01 | Fan fault | Replace the fan. | |
Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center |
|
Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
Fault code 52 | Bus voltage is too low. | ||
Fault code 55 | Output voltage is unbalanced. |
9 Appendix: Approximate Back-up Time Table
3.5KW
Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
---|---|---|
300 | 449 | 1100 |
600 | 222 | 525 |
900 | 124 | 303 |
1200 | 95 | 227 |
1500 | 68 | 164 |
1800 | 56 | 126 |
2100 | 48 | 108 |
2400 | 35 | 94 |
2700 | 31 | 74 |
3200 | 28 | 67 |
5.5KW
Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
---|---|---|
500 | 613 | 1288 |
1000 | 268 | 613 |
1500 | 158 | 402 |
2000 | 111 | 271 |
2500 | 90 | 215 |
3200 | 76 | 182 |
3500 | 65 | 141 |
4000 | 50 | 112 |
4500 | 44 | 100 |
5000 | 40 | 90 |
Note: Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers.
Model Number: 327-100015-02G
Models: 327-100015-02G, 3.5KW Plus Inverter MPPT SCC AC Charger, Inverter MPPT SCC AC Charger, MPPT SCC AC Charger, SCC AC ChargerRelated Documents
![]() |
PowMr Hybrid Inverter 3.5KW & 5.5KW Technical Specifications Detailed technical specifications for PowMr 3.5KW and 5.5KW hybrid inverters, covering line mode, inverter mode, charge mode, and general operating parameters. |
![]() |
PowMr POW-VM5K-III 5KW Solar Inverter | All-In-One MPPT Charger Controller Discover the PowMr POW-VM5K-III, a 5KW All-In-One MPPT Solar Hybrid Inverter and Charger Controller. This document details its features, specifications, and applications for efficient solar energy management. |
![]() |
PowMr POW-SunSmart SP5K Hybrid Solar Inverter User Manual Comprehensive user manual for the PowMr POW-SunSmart SP5K hybrid solar inverter, detailing installation, operation, features, technical specifications, and troubleshooting for efficient solar energy management. |
![]() |
PowMr Solar Inverter Quick Installation Guide This guide provides essential steps for installing and operating PowMr solar inverters, covering mounting, electrical connections, and basic troubleshooting for home, RV, and off-grid applications. |
![]() |
PowMr 2.0KW/3.2KW Inverter/MPPT SCC/AC Charger User Manual Comprehensive user manual for the PowMr 2.0KW/3.2KW Inverter, MPPT SCC, and AC Charger. Covers installation, operation, safety instructions, specifications, and troubleshooting for efficient solar energy management. |
![]() |
1.5KW/3KW/5KW Solar Inverter/Charger User Manual Comprehensive user manual for the 1.5KW, 3KW, and 5KW Solar Inverter/Charger, covering installation, operation, and troubleshooting. |
![]() |
PowMr 1.5KW/3KW/5KW Solar Inverter/Charger User Manual Comprehensive user manual for the PowMr 1.5KW, 3KW, and 5KW Solar Inverter/Charger, covering installation, operation, specifications, and troubleshooting for hybrid power systems. |
![]() |
PowMr POW-SunSmart 5.5KW-48V Solar Hybrid Inverter User Manual and Installation Guide Comprehensive user manual for the PowMr POW-SunSmart 5.5KW-48V solar hybrid inverter, covering installation, operation, safety instructions, technical specifications, and troubleshooting. |