Applications
- For the quick connection of pipe clamps with FUS channels.
- For use in dry interior areas.
Advantages
- The design of the FCN Clix S fits to the FUS channel profile and allows for a quick and easy installation.
- The spring effect of the FCN Clix S guarantees simple and precise positioning in the channel.
- Installation by rotating 90° enables post-installation to installed channel.
- The serration on the T-head bolt provides a secure hold in FUS channels.
- The pre-mounted threaded stud allows for direct mounting of the pipe clamps to the channel without additional material.
Properties
- Washer: S235JR (material no. 1.0038)
- Threaded stud: DIN 976 steel 4.8
- Hexagonal nut: resistance class 8
- Plastic cage: Polyamide PA 6
- Zinc plating: electro zinc-plated
Installation FCN Clix S
A description of the installation process for the FCN Clix S bolt into a channel profile. The sequence involves inserting the T-head bolt into the channel, rotating it 90 degrees to lock it in place, placing the pipe clamp onto the bolt's threaded stud, and finally tightening the hexagonal nut to secure the clamp.
Technical Data
Diagram illustrating the dimensions of the FCN Clix S bolt, showing the T-head width (SW) and the length of the threaded stud (L), with the thread size indicated as A.
Item | Item no. | Thread A | Length L [mm] | Width across nut SW [mm] | Sales unit [pcs] |
---|---|---|---|---|---|
FCN Clix S 8x30 | 567462 | M8 | 30 | 13 | 50 |
FCN Clix S 8x40 | 567463 | M8 | 40 | 13 | 50 |
FCN Clix S 8x60 | 567464 | M8 | 60 | 13 | 50 |
FCN Clix S 8x80 | 567465 | M8 | 80 | 13 | 50 |
FCN Clix S 8x100 | 567466 | M8 | 100 | 13 | 50 |
FCN Clix S 10x30 | 567467 | M10 | 30 | 17 | 50 |
FCN Clix S 10x40 | 567468 | M10 | 40 | 17 | 50 |
FCN Clix S 10x60 | 567469 | M10 | 60 | 17 | 50 |
FCN Clix S 10x100 | 567470 | M10 | 100 | 17 | 50 |
FCN Clix S 12x40 | 567471 | M12 | 40 | 19 | 50 |
FCN Clix S 12x60 | 567472 | M12 | 60 | 19 | 50 |
Loads
Diagram showing the FCN Clix S bolt installed in a channel, with an arrow indicating the recommended tension load (Nrec).
Item | Item no. | Max. recommended tension load for FUS 1,5 mm [kN] | Max. recommended tension load for FUS 2,0 mm [kN] | Max. recommended tension load for FUS 2,5 mm [kN] | Installation torque Tinst [Nm] | Sales unit [pcs] |
---|---|---|---|---|---|---|
FCN Clix S 8x30 | 567462 | 3.0 | 4.0 | 4.0 | 10 | 50 |
FCN Clix S 8x40 | 567463 | 3.0 | 4.0 | 4.0 | 10 | 50 |
FCN Clix S 8x60 | 567464 | 3.0 | 4.0 | 4.0 | 10 | 50 |
FCN Clix S 8x80 | 567465 | 3.0 | 4.0 | 4.0 | 10 | 50 |
FCN Clix S 8x100 | 567466 | 3.0 | 4.0 | 4.0 | 10 | 50 |
FCN Clix S 10x30 | 567467 | 4.0 | 5.0 | 8.0 | 15 | 50 |
FCN Clix S 10x40 | 567468 | 4.0 | 5.0 | 8.0 | 15 | 50 |
FCN Clix S 10x60 | 567469 | 4.0 | 5.0 | 8.0 | 15 | 50 |
FCN Clix S 10x100 | 567470 | 4.0 | 5.0 | 8.0 | 15 | 50 |
FCN Clix S 12x40 | 567471 | 4.0 | 5.0 | 8.0 | 20 | 50 |
FCN Clix S 12x60 | 567472 | 4.0 | 5.0 | 8.0 | 20 | 50 |