Durastar Installation Manual: Floor Console Indoor Unit

This manual provides detailed installation instructions for the Durastar Floor Console Indoor Unit, compatible with models DRAS09F2A, DRAS12F2A, and DRAS16F2A, utilizing R-454B refrigerant, 208/230V, 1ph 60HZ.

Model Number:

Serial Number:

Purchase Date:

Installing Contractor Company Name:

? TIP: Capture relevant information about your Durastar mini-split equipment before it is installed and write it above for future reference.

Introduction

To better serve you, please do the following before contacting customer service:

Symbols Used in This Manual

Refrigerant R-454B, Safety Group A2L

⚠️ WARNING: RISK OF FIRE DUE TO FLAMMABLE MATERIALS Follow handling instructions carefully in compliance with national regulations.

Explanation of symbols displayed on the unit:

Important Safety Precautions

⚠️ WARNING: Turn off the air conditioner and disconnect the power before installing, cleaning, or repairing the air conditioner. Failure to do so can cause electric shock.

Improper handling can cause serious damage or injury. Please read the following safety information in its entirety.

Operation, Cleaning, and Maintenance Safety Precautions

Electrical Safety

Installation Safety

Refrigerant Safety (A2L)

A2L Refrigerant Safety Precautions

1. Installation (Where Refrigerant Pipes Are Allowed)

LEAK DETECTION SYSTEM installed: Unit must be powered except for service. For the unit with a refrigerant sensor, when the refrigerant sensor detects refrigerant leakage, the indoor unit will display an error code and emit a buzzing sound, the compressor of the outdoor unit will immediately stop, and the indoor fan will start running. The service life of the refrigerant sensor is 15 years. When the refrigerant sensor malfunctions, the indoor unit will display the error code “FHCC”. The refrigerant sensor cannot be repaired and can only be replaced by the manufacturer. It shall only be replaced with the sensor specified by the manufacturer.

2. Requirements for Installation Space and Ventilation with Flammable Refrigerant

Because a FLAMMABLE REFRIGERANT is used, the requirements for installation space of appliance and/or ventilation requirements are determined according to:

  1. Pressure test the refrigerant piping to 500 PSI.
  2. The test pressure after removal of pressure source shall be maintained for at least 1 hour with no decrease of pressure indicated by the test gauge, with test gauge resolution not exceeding 5% of the test pressure.
  3. During the evacuation test, after achieving a vacuum level specified in the manual or less, the refrigeration system shall be isolated from the vacuum pump and the pressure shall not rise above 1500 microns within 10 min. The vacuum pressure level shall be specified in the manual, and shall be the lessor of 500 microns or the value required for compliance with national and local codes and standards, which may vary between residential, commercial, and industrial buildings.

Field-made refrigerant joints indoors shall be tightness tested according to the following requirements: The test method shall have a sensitivity of 0.18 oz (5 g) per year of refrigerant or better under a pressure of at least 125% of the maximum allowable pressure. No leak shall be detected.

3. Qualifications Of Workers

Any maintenance, service, and repair operations must be performed by qualified personnel. Any working procedure that impacts safety must be performed only by qualified individuals who have completed the necessary training and obtained certification to demonstrate their competence. The training of these procedures is carried out by national training organizations or manufacturers that are accredited to teach the relevant national competency standards that may be set in legislation. All training shall follow the ANNEX HH requirements of UL 60335-2-40 4th Edition.

Examples for such working procedures are:

4. Checks To The Area

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.

5. Work Procedure

Works shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.

6. General Work Area

All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Working in confined spaces shall be avoided.

7. Checking For Presence Of Refrigerant

The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e., no sparking, adequately sealed, or intrinsically safe.

8. Presence Of Fire Extinguisher

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

9. No Ignition Sources

No person carrying out work in relation to a REFRIGERATING SYSTEM which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing, and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "No Smoking" signs shall be displayed.

10. Ventilated Area

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any work that could produce ignition. Keep ventilation openings clear of obstruction. Ventilation shall continue during the period that the work is carried out. Proper ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

11. Checks To The Refrigeration Equipment

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times, the manufacturer's maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer's technical department for assistance. The following checks shall be applied to installations using FLAMMABLE REFRIGERANTS:

12. Checks To Electrical Devices

Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include:

13. Wiring

Check that wiring will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges, or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

14. Detection Of Flammable Refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

The following leak detection methods are deemed acceptable for refrigerant systems:

✏️ Note: Examples of leak detection fluids are bubble method and fluorescent method agents.

If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut-off valves) in a part of the system remote from the leak. See the following instructions for removal of refrigerant.

15. Evacuation

When breaking into the refrigerant circuit to make repairs – or for any other purpose, conventional procedures shall be used. However, for flammable refrigerants, it is important that best practice be followed, since flammability is a consideration.

The following procedure shall be adhered to:

The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. For appliances containing flammable refrigerants, the system shall be purged with OXYGEN-FREE NITROGEN (OFN) to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems.

For appliances containing flammable refrigerants, refrigerant purging shall be achieved by breaking the vacuum in the system with OXYGEN-FREE NITROGEN (OFN) and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum (requirement). This process shall be repeated until no refrigerant is within the system (requirement). When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.

The outlet for the vacuum pump shall not be close to any potential ignition sources, and ventilation shall be available.

16. Charging Procedures

In addition to conventional charging procedures, the following requirements shall be followed:

Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.

Labeling

Equipment shall be labeled stating that it has been decommissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing FLAMMABLE REFRIGERANTS, ensure that there are labels on the equipment stating the equipment contains FLAMMABLE REFRIGERANT.

Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e., special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of the flammable refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition.

The recovered refrigerant shall be processed according to local legislation in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.

If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The compressor body shall not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it shall be carried out safely.

Unventilated Areas

Transportation, Marking and Storage for Units That Employ Flammable Refrigerants

The following information is provided for units that employ FLAMMABLE REFRIGERANTS.

Transport of equipment containing flammable refrigerants: Attention is drawn to the fact that additional transportation regulations may exist with respect to equipment containing flammable gas. The maximum number of pieces of equipment or the configuration of the equipment permitted to be transported together will be determined by the applicable transport regulations.

Marking of equipment using signs: Signs for similar appliances used in a work area are generally addressed by local regulations and give the minimum requirements for the provision of safety and/or health signs for a work location. All required signs are to be maintained, and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions that need to be taken in connection with these signs. The effectiveness of signs should not be diminished by too many signs being placed together. Any pictograms used should be as simple as possible and contain only essential details.

Disposal of equipment using flammable refrigerants: See national regulations.

Storage of equipment/appliances: The storage of the appliance should be in accordance with the applicable regulations or instructions, whichever is more stringent.

Storage of packed (unsold) equipment: Storage package protection should be constructed in such a way that mechanical damage to the equipment inside the package will not cause a leak of the REFRIGERANT CHARGE. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

Additional Precautions

Specifications of R-454B Refrigerant

Fuse Specifications

The air conditioner's circuit board (PCB) is designed with a fuse to provide over-current protection. The specifications of the fuse are printed on the circuit board, for example: T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC, etc.

✏️ Note: Only a blast-proof ceramic fuse can be used.

R454B Required Room Height and Minimum Room Area

R454B UL guidelines require dissipation if there is a refrigerant leak and are based on total square footage and total system charge. The total system charge includes any component that holds refrigerant, including line sets, indoor coils, and outdoor units. The minimum room area for operating and storing the unit should be as specified in the following table.

mc or mREL Refrigerant Charge lbs (kg)Amin: REQUIRED MINIMUM ROOM AREA: ft² (m²)
hinst: Height from the Floor to the Bottom of the Indoor Unit: ft (m) ≤ 7.2 (2.2)7.5 (2.3)7.9 (2.4)8.5 (2.6)9.2 (2.8)9.8 (3.0)
≤ 3.91 (1.776)12 (1.10)
4.0 (1.8)60 (5.53)57 (5.29)55 (5.07)51 (4.68)47 (4.35)44 (4.06)
4.4 (2.0)67 (6.15)64 (5.88)61 (5.64)56 (5.20)52 (4.83)49 (4.51)
4.9 (2.2)73 (6.76)70 (6.47)67 (6.20)62 (5.72)58 (5.31)54 (4.96)
5.3 (2.4)80 (7.38)76 (7.06)73 (6.76)68 (6.24)63 (5.80)59 (5.41)
5.7 (2.6)86 (7.99)83 (7.64)79 (7.32)73 (6.76)68 (6.28)64 (5.86)
6.2 (2.8)93 (8.60)89 (8.23)85 (7.89)79 (7.28)73 (6.76)68 (6.31)
6.6 (3.0)100 (9.22)95 (8.82)91 (8.45)84 (7.80)78 (7.24)73 (6.76)
7.1 (3.2)106 (9.83)102 (9.41)97 (9.01)90 (8.32)84 (7.73)78 (7.21)
7.5 (3.4)113 (10.45)108 (9.99)104 (9.58)96 (8.84)89 (8.21)83 (7.66)
7.9 (3.6)120 (11.06)114 (10.58)110 (10.14)101 (9.36)94 (8.69)88 (8.11)
8.4 (3.8)126 (11.68)121 (11.17)116 (10.70)107 (9.88)99 (9.17)93 (8.56)
8.8 (4.0)133 (12.29)127 (11.76)122 (11.27)112 (10.40)104 (9.66)97 (9.01)
9.3 (4.2)139 (12.90)133 (12.34)128 (11.83)118 (10.92)110 (10.14)102 (9.46)
9.7 (4.4)146 (13.52)140 (12.93)134 (12.39)124 (11.44)115 (10.62)107 (9.91)
10.1 (4.6)153 (14.13)146 (13.52)140 (12.96)129 (11.96)120 (11.11)112 (10.37)
10.6 (4.8)159 (14.75)152 (14.11)146 (13.52)135 (12.48)125 (11.59)117 (10.82)
11.0 (5.0)166 (15.36)159 (14.69)152 (14.08)140 (13.00)130 (12.07)122 (11.27)

Variable Definitions:

WARNING: The minimum room area or the minimum room area of conditioned space is based on releasable charge and total system refrigerant charge.

When the unit detects a refrigerant leak, the minimum airflow of the indoor unit is as follows:

ModelDRAS09F2ADRAS12F2ADRAS16F2A
BTU9K12K16K
Nominal Air Volume353 CFM (600 m³/h)418 CFM (710 m³/h)448 CFM (760 m³/h)

Operating Temperatures

Your air conditioner is designed to operate in the following indoor and outdoor temperatures. When your air conditioner is used outside of the following temperature ranges, certain safety features may activate and turn off the unit to protect it from damage.

COOL modeHEAT modeDRY mode
Indoor Air Temperature60°F - 90°F (16°C - 32°C)32°F - 86°F (0°C - 30°C)50°F - 90°F (10°C - 32°C)
Outdoor Air Temperature-13°F / -22°F* – 122°F (-25°C / -30°C* – 50°C)-13°F / -22°F* – 75°F (-25°C / -30°C* – 24°C)32°F - 122°F (0°C - 50°C)

* The minimum outdoor air operating temperature depends on the outdoor unit. Low ambient Sirius Heat™ models have a minimum outdoor air operating temperature of -22°F (-30°C).

To further optimize the performance of your unit, do the following:

✏️ Note: Your Durastar air conditioner's outdoor unit is equipped with a base pan heater, allowing it to continue to operate at freezing temperatures as low as –22°F (–30°C). When outdoor air temperatures are at or below 32°F (0°C), we strongly recommend keeping the unit plugged in at all times to ensure smooth ongoing performance.

✏️ Note: Keep the room's relative humidity below 80%. If the air conditioner operates in excess of this, the surface of the air conditioner may attract condensation. To help prevent condensation from forming and dripping, set the vertical airflow louver to its maximum angle (vertically to the floor) and set the fan to HIGH.

Included Accessories

The air conditioning system comes with the following accessories.

AccessoryQuantityImageAccessoryQuantityImage
Manual2[Manual Icon]Remote Control1[Remote Control Icon]
Copper Nut2[Copper Nut Icon]Battery2[Battery Icon]
Air Freshening Filter2[Filter Icon]Remote Control Holder1[Holder Icon]

⚠️ WARNING: Ensure that all service equipment and instruments are certified for use with group A2L refrigerants, specifically R-454B. Recovery equipment, pumps, hoses, and related components must be rated for the appropriate design pressures for R-454B. Manifold sets should accommodate pressures up to 800 psig on the high side and 250 psig on the low side, with a 550 psig low-side retard. Hoses must have a service pressure rating of 800 psig, while recovery cylinders should be rated for 400 psig, meeting DOT 4BA400 or DOT 4BW400 standards.

Tools Needed

The following tools are required for installation:

Field Supplied Installation Accessories

The following installation accessories are required and must be purchased separately:

Parts Identification

Indoor Unit

Top Air Outlet and Louver

Air Inlet

Bottom Air Outlet and Louver

Air Filter

Air Freshening Filter

Control Panel

Signal Cable

Drain Hose

Refrigerant Pipes

Remote Control Holder

Remote Control

Outdoor Unit

Air Inlets

Wiring Terminal

Signal Cable

Refrigerant Pipes

Outdoor Unit Power Cable

Air Outlet

Valve Cover

✏️ NOTE: Outdoor units will vary in appearance.

Indoor Unit Installation

Step 1: Select Installation Location

Before installing the indoor unit, you must choose an appropriate location. The following standards must be met for an appropriate location for the unit:

DO NOT install unit in the following locations:

Refer to the following diagrams to ensure proper distance from walls, ceiling and other units:

Diagram showing clearance dimensions: 4" (101mm) from sides, 6" (152mm) from bottom, 7-7/8" (200mm) from top, 40" (1015mm) from front. Default piping shown on the right side.

✏️ NOTE: If there is no pre-existing refrigerant piping, when choosing a location, leave ample room for a wall hole (see Step 3: Drill Wall Hole for Connective Piping) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the back of the unit). However, the unit can accommodate piping to either the left or right.

Step 2: Attach Mounting Plate(s) to the Wall

  1. Remove the screw that attaches the top mounting plate to the back of the indoor unit. The mounting plate is the bracket on which you will mount the indoor unit.
  2. Use a level to ensure the bracket is straight and mark the holes. Fix the mounting plate to the wall with five screws and anchors. Do not let the screws protrude more than 1/4" (6mm), or the unit will not hang vertically.
  3. Mount the unit. The bottom of the unit can touch the floor or remain suspended, but the body must be installed vertically. Refer to the diagrams below. Diagram showing mounting plate hole positions and unit mounting.

⚠️ CAUTION: Ensure that the indoor unit is completely level. Improper installation can cause the drain pipe to back up into the unit and water leaks.

4. Attach the bottom mounting plate to the wall with a screw.

Step 3: Remove the Piping Cover Plate

  1. Undo the bottom two buckles (on either the right or left side) to open the piping cover plate.
  2. Remove the piping cover plate to access the refrigerant and drain pipe connections.

Step 4: Drill Wall Hole for Connective Piping

  1. Determine the location of the wall hole based on the location of the outdoor unit. Diagram showing hole placement with dimensions 6" (150mm) and 18-1/2" (470mm).

✏️ NOTE: In order to ensure smooth drainage, the height difference between the wall outlet and the hanging plate must be greater than 18-1/2" (470mm).

  1. Using a 2 1/2" (65mm) core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 3/16 – 1/4" (5mm to 7mm). This will ensure proper water drainage. Diagram showing wall hole with downward angle for drainage.
  2. Place the protective wall hole sleeve (field supplied) into the hole. This protects pipes and cables from sharp edges and will help seal the opening when you finish the installation process. After the sleeve is inserted through the wall, connect the wall hole sleeve cover to the wall sleeve on the outside end. Make sure the cover is flush with the outside wall.

Step 5: Connect Drain Pipe

The drain pipe is used to drain condensate water away from the unit. Improper installation may cause leaks and unit or property damage.

  1. Connect a 5/8" ID drain pipe (field supplied) to the unit's connecting port using a metal worm clamp (field supplied). Make sure it is secured tightly and cannot be easily pulled loose. Diagram showing drain pipe connection with metal clamp.
  2. The drain pipe must be installed with a downward slope of at least a 1/100 gradient to prevent water from flowing back into the unit. Do not allow the drain pipe to bend or sag and trap condensation.
  3. If connecting multiple drain pipes, install the pipes as illustrated below. Diagram showing multiple drain pipe connections.
  4. Pass the drain pipe through the wall hole to the outside. The end of the pipe should be at least 2" (50mm) above the ground. If it touches the ground, the pipe may become blocked. Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard.

Step 6: Connect Signal Cable

⚠️ WARNING: Before performing any electrical or wiring work, turn off the main power to the system.

Before Performing Any Electrical Work, Read These Regulations

  1. All wiring must comply with local and national electrical codes and regulations, and must be installed by a licensed electrician.
  2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
  3. If there is a serious safety issue with the power supply, stop work immediately and contact a licensed electrician. Do not continue with the installation until the safety issue is properly resolved.
  4. Power voltage should be within 90–110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
  5. If connecting power to fixed wiring, install a surge protector and main power switch with a capacity of 1.5 times the maximum current of the unit.
  6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8" (3mm) must be incorporated in the fixed wiring. A qualified technician must use an approved circuit breaker or switch.
  7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
  8. Make sure to properly ground the air conditioner.
  9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
  10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
  11. To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 10 minutes or more before you touch the electrical components.

Wiring diagram showing connections for Indoor Unit (Power Supply, Signal High Voltage) and Outdoor Unit (Power to Indoor Unit, Signal High Voltage, Main Power Supply) with voltage specifications.

The signal cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it for connection.

Use the Right Cable

Cable Sizing

Use a minimum of 14 AWG for power and signal cables connected to and between the indoor and outdoor units.

Choose the Correct Size of Cable

The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.

Wiring the Indoor Unit

  1. Grasp the left and right tabs of the front panel and pull the panel outward.
  2. Remove the electric control box cover, by removing the screw at the top.
  3. Unscrew the cable clamp below the terminal block and place it to the side.
  4. Remove the casing connecting plate from the back of the chassis and knock out the indicated hole in the chassis.
  5. Reinstall the casing connecting plate.
  6. From the back of the unit to the front, thread the cable through the hole of the casing connecting plate and the knock-out hole in the chassis. Diagram showing cable threading through chassis.
  7. Prepare the cable for connection:
    • Using wire strippers, strip the jacket from the ends of the cable to reveal about 6" of the wires.
    • Strip the insulation from the ends of the wires.
    • Using a wire crimper, crimp u-lugs to the ends of the wires.
  8. Connect the u-lugs to the terminals. Match the wire colors/labels with the labels on the terminal block. Firmly screw the u-lug of each wire to its corresponding terminal. Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box.
  9. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the unit. Screw the cable clamp down tightly.
  10. Replace the electric control box cover and the front panel.

⚠️ WARNING: All wiring must be performed strictly in accordance with the wiring diagram located on the inside of the control box lid.

Step 7: Prepare Refrigerant Piping

  1. If pre-existing refrigerant piping is already embedded in the wall, proceed directly to Step 8: Install Panel.
  2. If there is no pre-existing piping, connect the indoor unit's refrigerant piping to the connective piping that will join the indoor and outdoor units. Refer to the Refrigerant Piping Connections section of the outdoor unit's installation manual for detailed instructions.

⚠️ WARNING: Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will affect the unit's performance.

IMPORTANT NOTE: The TOTAL SYSTEM CHARGE WEIGHT should be noted on the label adjacent to the unit rating label on the outdoor unit.

Step 8: Wrap Pipes and Cable

Before passing the refrigerant piping, drain pipe, and the signal cable through the wall hole, you must bundle them together to save space, protect them, and insulate them.

  1. Bundle the drain pipe, refrigerant pipes, and signal cable as shown below. Diagram showing piping configuration in the back of the unit with drain pipe, signal wire, and refrigerant piping.

✏️ NOTE: The drain pipe MUST be at the bottom of the bundle. Putting the drain pipe at the top of the bundle can cause the drain pan to overflow, which can lead to fire or water damage.

✏️ NOTE: DO NOT intertwine the signal cable with any of the other wires while bundling these items together.

  1. Using adhesive vinyl tape, attach the drain pipe to the underside of the refrigerant pipes.
  2. Using insulation tape, wrap the signal wire, refrigerant pipes, and drain pipe tightly together. Double-check that all items are bundled.

✏️ NOTE: When wrapping the bundle, keep the ends of the piping unwrapped. You need to access them to test for leaks at the end of the installation process (refer to the Electrical and Gas Leak Checks section of the outdoor unit's installation manual).

Step 9: Complete a Water Discharge Test

Before the test, make sure that the water discharge pipeline is sloped smoothly and check that each connection is sealed properly.

  1. Connect the power supply and set the air conditioner to operate in the cool mode.
  2. Keep cool mode running for at least 10 min.
  3. Stop the air conditioner. Wait for three (3) minutes, and then check if there is anything unusual. If the water discharge piping layout is not correct, the excessive water flow will cause the water level error and “EHOE” error code will be displayed on the display panel. There may even be water overflowing from the water pan.
  4. If the water is not draining properly, check the rise height and slope of the drain tubing. Also check to make sure there is not an obstruction.

Troubleshooting

Safety Precautions

If ANY of the following conditions occurs, turn off your unit immediately!

  • The power cord is damaged or abnormally warm
  • You smell a burning odor
  • The unit emits loud or abnormal sounds
  • A power fuse blows or the circuit breaker frequently trips
  • Water or other objects fall into or out of the unit

DO NOT ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER IMMEDIATELY!

Troubleshooting Table

ISSUEPOSSIBLE CAUSES
Unit does not turn on when pressing ON/OFF buttonThe Unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be restarted within three minutes of being turned off.
The unit changes from COOL/HEAT mode to FAN modeThe unit may change its setting to prevent frost from forming on the unit. Once the temperature increases, the unit will start operating in the previously selected mode again.
The set temperature has been reached, at which point the unit turns off the compressor. The unit will continue operating when the temperature fluctuates again.
The indoor unit emits white mistIn humid regions, a large temperature difference between the room's air and the conditioned air can cause white mist.
Both the indoor and outdoor units emit white mistWhen the unit restarts in HEAT mode after defrosting, white mist may be emitted due to moisture generated during the defrosting process.
The indoor unit makes noisesA rushing air sound may occur when the louver resets its position. A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit's plastic parts.
Both the indoor unit and outdoor unit make noisesLow hissing sound during operation: This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units. Low hissing sound when the system starts, has just stopped running, or is defrosting: This noise is normal and is caused by the refrigerant gas stopping or changing direction. Squeaking sound: Normal expansion and contraction of plastic and metal parts caused by temperature changes during operation can cause squeaking noises.
The outdoor unit makes noisesThe unit will make different sounds based on its current operating mode.
Dust is emitted from either the indoor or outdoor unitThe unit may accumulate dust during extended periods of non-use, which will be emitted when the unit is turned on. This can be mitigated by covering the unit during long periods of inactivity.
The unit emits a bad odorThe unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations. The unit's filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operateDuring operation, the fan speed is controlled to optimize product operation.
Operation is erratic, unpredictable, or unit is unresponsiveInterference from cell phone towers and remote boosters may cause the unit to malfunction. In this case, try the following:
  • Disconnect the power, then reconnect.
  • Press ON/OFF button on remote control to restart operation.

✏️ NOTE: If problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as your model number.

Troubleshooting Table (Continued)

PROBLEMPOSSIBLE CAUSESSOLUTION
Poor Cooling PerformanceTemperature setting may be higher than ambient room temperature.Lower the temperature setting.
The heat exchanger on the indoor or outdoor unit is dirty.Clean the affected heat exchanger.
The air filter is dirty.Remove the filter and clean it according to instructions.
The air inlet or outlet of either unit is blocked.Turn the unit off, remove the obstruction and turn it back on.
Doors and windows are open.Make sure that all doors and windows are closed while operating the unit.
Low refrigerant due to leak or long-term use.Check for leaks, re-seal if necessary, and top off refrigerant.
Excessive heat is generated by sunlight.Block sunlight in installation area. Close windows and curtains during periods of high heat or bright sunshine.
Too many sources of heat in the room (people, computers, electronics, etc.).Reduce amount of heat sources.
Poor Heating PerformanceThe outdoor temperature is extremely low.This model is designed to work down to -13°F, however, heating performance is impacted at temperatures below freezing.
Cold air is entering through doors and windows.Make sure that all doors and windows are closed during use.
Low refrigerant due to leak or long-term use.Check for leaks, re-seal if necessary, and top off refrigerant.
The unit starts and stops frequentlyThere's too much or too little refrigerant in the system.Check for leaks and recharge the system with refrigerant.
Incompressible gas or moisture has entered the system.Evacuate and recharge the system with refrigerant.
The compressor is broken.Replace the compressor.
The voltage is too high or too low.Install a manostat to regulate the voltage.
The unit is not workingPower failure.Wait for the power to be restored.
The power is turned off.Turn on the power.
The fuse is burned out.Replace the fuse.
Remote control batteries are dead.Replace the batteries.
The Unit's 3-minute protection has been activated.Wait three minutes after restarting the unit.
Timer is activated.Turn timer off.
Indicator lamps continue flashing or error code appearsThe unit may stop operation or continue to run safely. If the indicator lamps continue to flash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If the problem persists, contact your nearest service technician.

✏️ NOTE: If your problem persists after performing the checks and diagnostics above, turn off your unit immediately and contact an authorized service center.

⚠️ WARNING: If error codes EHC1 or EHC2 flash, a refrigerant leak is detected. A buzzer will continue to beep for 5 to 6 minutes before stopping. You can also press any button on the remote controller to stop the buzzer. The unit will go into Turbo to mitigate the leak. Check connections and perform a leak test as described in the outdoor unit installation manual.

Wiring Diagram

Detailed wiring diagram for the indoor unit, outdoor unit, main board, and multi-function control board, showing component connections, part names, and voltage specifications.

Error Codes – Indoor Unit

This table lists common error codes displayed by the indoor unit and their corresponding operations or error descriptions.

CODE DISPLAYEDOPERATION OR ERROR DESCRIPTION
dFDefrost (not an error code)
FCForced cooling (not an error code)
EC07ODU fan speed out of control
EC51ODU EEPROM parameter error
EC52ODU coil temp. sensor (T3) error
EC53ODU ambient temp. sensor (T4) error
EC54COMP. discharge temp. sensor (TP) error
EC56IDU coil outlet temp. sensor (T2B) error
ECC1Other IDU refrigerant sensor detects leakage (Multi-zone)
EHOOIDU EEPROM malfunction
EHOAIDU EEPROM parameter error
EHObIDU main control board and display board communication error
EH31IDU fan (1) speed malfunction
EH32IDU fan (2) speed malfunction
EH60IDU room temp. sensor (T1) error
EH61IDU coil temp. sensor (T2) error
EHC1Refrigerant sensor detects leakage
EHC2Refrigerant sensor is out of range and leakage is detected
EHC3Refrigerant sensor is out of range
EL01IDU & ODU communication error
EL0CSystem lacks refrigerant
FHCCRefrigerant sensor error
PC00ODU IPM module protection
PC01ODU voltage protection
PC02Compressor top (or IPM) temp. protection
PC03Pressure protection (low or high pressure)
PC04Inverter compressor drive error
PCOLLow ambient temperature protection
----IDUs mode conflict (Multi-zone)
Models: DRA5H36M2A, DRAS09F2A, DRAS09F2A, DRAF24F2A, DRA5H36M2A Series Sirius Heat Floor Mounted Mini Split Heat Pump System, DRA5H36M2A Series, Sirius Heat Floor Mounted Mini Split Heat Pump System, Floor Mounted Mini Split Heat Pump System, Mini Split Heat Pump System, Split Heat Pump System, Heat Pump System

File Info : application/pdf, 32 Pages, 10.67MB

PDF preview unavailable. Download the PDF instead.

87844e47552a7ab3842016f4b8bdd5a7

References

Adobe PDF Library 17.0

Related Documents

Preview Durastar Split-Style Air Conditioner Installation Manual
Comprehensive installation manual for Durastar Wall Mounted Indoor Unit Split-Style Air Conditioners, covering safety, setup, operation, and troubleshooting for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, and DRAW24F1B.
Preview Durastar DRAS12F1B Floor Mounted Mini-Split Air Conditioner Installation Manual
This installation manual provides detailed instructions for the Durastar DRAS12F1B floor-mounted split-style air conditioner. It covers safety precautions, installation steps, parts identification, troubleshooting, and wiring diagrams.
Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering safety precautions, installation steps, troubleshooting, and specifications for models DRAW06F2A through DRAW33F2A using R-454B refrigerant.
Preview Durastar Single Zone Outdoor Unit Installation Manual
This manual provides comprehensive installation instructions for the Durastar Single Zone Outdoor Unit Split-Style Air Conditioner, covering safety precautions, parts identification, installation steps, wiring diagrams, troubleshooting, and error codes.
Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering model numbers DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, and DRAW24F1B. Includes safety precautions, parts identification, step-by-step installation procedures, troubleshooting, and wiring diagrams.
Preview Durastar DRAS12F1B Floor Mounted Indoor Unit Owner's Manual
Comprehensive owner's manual for the Durastar DRAS12F1B split-style air conditioner, covering installation, operation, maintenance, troubleshooting, and warranty information.
Preview Durastar Wall Mounted Mini-Split Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners, covering operation, safety, maintenance, troubleshooting, and warranty for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, DRAW33F1B.
Preview Durastar Split-Style Air Conditioner Installation Manual for Outdoor Units
This installation manual provides comprehensive guidance for Durastar single-zone outdoor split-style air conditioners, including models DRA1U09S1B, DRA1U12S1B, DRA1U18S1B, and DRA1U24S1B. It covers safety precautions, installation steps, wiring, refrigerant piping, system evacuation, and troubleshooting.