UL System NO. C-AJ-2631
Plastic Pipe Through Concrete Floor/Wall or Block Wall Assembly
F-RATING = 2-HR. T-RATING = 1-HR.
Assembly Description
This document details the assembly for a plastic pipe passing through a concrete floor/wall or block wall, providing a 2-hour F-rating and a 1-hour T-rating.
Bottom View: Depicts the assembly from below, showing the components around the pipe penetration.
Section A-A: Illustrates a cross-section of the assembly, detailing the layers and components involved in sealing the penetration.
Components and Materials
- Concrete Floor or Wall Assembly (2-HR. Fire-Rating): Can be lightweight or normal weight concrete (minimum 2-1/2" thick) or any UL classified concrete block wall.
- Penetrating Item: Maximum 4" nominal diameter plastic pipe, including PVC (cellular or solid core), CPVC (closed piping system only), ABS (cellular or solid core), or FRPP.
- Mineral Wool: Minimum 2" thickness with a minimum 4 pcf density, tightly packed and recessed to accommodate sealant.
- Hilti FS-ONE MAX or FS-ONE Intumescent Firestop Sealant: Minimum 1/2" depth.
- Sheet Metal Cover Plate: Minimum 28 GA. steel, consisting of two halves with a minimum 2" overlap at the seam. Sized to overlap the assembly by a minimum of 1-1/2". The overall dimensions should not exceed the opening diameter plus 4". The inside diameter should be a maximum of 1/4" larger than the pipe's outside diameter. The cover plate is secured to the underside of the concrete floor or both sides of the wall using specified fasteners.
- Hilti CP 643N Firestop Collar: Equipped with fastening hooks.
- Fastening Hooks: Secured to the metal cover plate with self-tapping steel screws and steel washers, and to the concrete floor or wall using specified anchors or fasteners.
Notes
- Maximum diameter of opening: 8".
- Annular space: Minimum 0", maximum 3-1/2".
- Piping system type: Closed or vented. PVC, ABS, FRPP must be SCH 40; CPVC must be SDR 13.5.
- Hilti CP 643N Firestop Collars, sheet metal cover plate, and Hilti FS-ONE MAX or FS-ONE Intumescent Firestop Sealant are required on both sides of a wall.
Manufacturer Information
HILTI, Inc.
Tulsa, Oklahoma USA
(800) 879-8000
Document Details
Sheet | 1 of 2 |
Scale | 11/64" = 1" |
Date | Jan. 05, 2015 |
Drawing No. | CAJ 2631b |