Hilti Firestop Foam CFS-F FX

Technical Manual

European Technical Assessment ETA 10/0109

FLEXIBLE FIRESTOP FOAM CFS-F FX

Hilti Firestop Foam CFS-F FX is a versatile foam sealant designed for firestopping applications in various construction scenarios.

Applications

Advantages

Technical Data

Characteristic Details
Base materials Concrete, Masonry, Drywall
Approvals ETA-10/0109
Repenetration Easy
Approx. tack-free time (at 23 °C/50% rel. humidity) 5 min
Approx. curing time1) 10 min
Application temperature range 10 - 35 °C
Temperature resistance range -30 - 60 °C
Storage and transportation temperature range 5 - 25 °C
Required dispenser HDM 330, HDE 500
Content per can / cartridge 325 ml

Accessories

Ordering designation Item number Sales pack quantity
HDM 330 manual dispenser 2036319 1 pc
HDE 500-A22 cordless dispenser 2005637 1 pc

GENERAL INSTRUCTIONS FOR USE

The following steps illustrate the general application process for Hilti Firestop Foam CFS-F FX:

  1. Prepare the opening and the penetrating items.
  2. Apply the foam to the opening, ensuring complete coverage.
  3. Use the appropriate Hilti dispenser (e.g., HDM 330, HDE 500-A22).
  4. Ensure the foam expands to fill the entire void.
  5. Allow the foam to cure according to the specified time.
  6. Trim excess foam if necessary.
  7. The system is now ready for further treatment or inspection.

CONSUMPTION GUIDE

The following tables provide an estimate of the number of 325 ml cartridges required for various opening sizes and penetration fill levels.

Circular opening – 200 mm depth

Opening Ø (mm) Visual fill of penetrating items
0% 10% 30% 60%
90 1.0 1.0 1.0 0.5
120 1.5 1.5 1.0 1.0
140 2.0 2.0 1.5 1.0
160 2.5 2.5 2.0 1.0
180 3.0 3.0 2.5 1.5
200 4.0 3.5 3.0 1.5
220 4.5 4.0 3.5 2.0
240 5.5 5.0 4.0 2.5
250 6.0 5.5 4.0 2.5
280 7.5 6.5 5.0 3.0
300 8.5 7.5 6.0 3.5
320 9.5 8.5 6.5 4.0
340 10.5 9.5 7.5 4.5
350 11.5 10.0 8.0 4.5
400 14.5 13.5 10.5 6.0

Rectangular opening – 200 mm depth

Opening (mm) Visual fill of penetrating items
Width Height 0% 10% 30% 60%
50 100 1.0 1.0 0.5 0.5
100 100 1.5 1.5 1.0 0.5
100 150 2.0 2.0 1.5 1.0
100 200 2.5 2.5 2.0 1.0
100 250 3.0 3.0 2.5 1.5
100 300 3.5 3.5 2.5 1.5
200 200 5.0 4.5 3.5 2.0
200 225 5.5 5.0 4.0 2.5
200 250 6.0 5.5 4.5 2.5
200 300 7.0 6.5 5.0 3.0
200 400 9.5 8.5 6.5 4.0
300 300 10.5 9.5 7.5 4.5
300 350 12.5 11.0 8.5 5.0
300 400 14.0 12.5 10.0 6.0
400 400 18.5 17.0 13.0 7.5

GENERAL INFORMATION

The following diagrams illustrate the general principles for applying Hilti Firestop Foam CFS-F FX in different construction elements.

Partition

Flexible wall

Rigid wall

Floor

Penetration Types and Approvals

Penetration Penetration Ø Flexible wall Rigid wall Rigid floor
Blank seal N/A El 90 El 120 El 120
Cables, Cable bundles Cables Ø ≤ 80 mm, Bundles Ø ≤ 100 mm El 90 El 120 (ta ≥ 100 mm) El 120 (ta ≥ 150 mm)
Metal conduits Ø ≤ 16 mm El 60 up to El 120 (ta ≥ 100 mm) El 120 (ta ≥ 150 mm) El 120 (ta ≥ 150 mm)
Plastic conduits Ø ≤ 16 mm El 120 El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm)
Flexible / rigid plastic conduits 16 mm ≤ Ø ≤ 32 mm El 90 up to El 120 (ta ≥ 100 mm) El 120 (ta ≥ 150 mm) El 120 (ta ≥ 150 mm)
Bundles of plastic, conduits Ø ≤ 100 mm bundle El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm)
AL composite pipes 16 mm ≤ Ø ≤ 32 mm El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm)
Penetration Penetration Ø Flexible wall Rigid wall Rigid floor
Non-insulated metal pipes 28 mm El 90 (ta ≥ 200 mm) El 90 (ta ≥ 200 mm) El 90 (ta ≥ 200 mm)
Metal pipes with mineral wool insulation 12 mm Ø ≤ 168 mm El 60 up to El 120 (ta ≥ 150 mm) El 120 (ta ≥ 150 mm) El 120 (ta ≥ 150 mm)
Metal pipes with Armaflex insulation 6 mm Ø ≤ 42 mm El 60 up to El 120 (ta ≥ 150 mm) El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm)
Metal pipes with Armaflex insulation with CFS-B Firestop Bandage 28-114 mm El 60 up to El 120 (ta ≥ 150 mm) El 120 (ta ≥ 150 mm) El 120 (ta ≥ 200 mm)
Plastic pipes ≤ 50 mm El 120 (ta ≥ 150 mm) El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm)
Plastic pipes with CFS-B PE/PVC 50-110 mm El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm) El 120 (ta ≥ 200 mm)

Excerpt of ETA document. Check the exact field of application (cable types and diameters, pipe types/diameters and wall thickness/insulations type) in the ETA 10/0109 document.

OTHER APPROVED APPLICATIONS

Hilti Firestop Foam CFS-F FX is also approved for the following applications:

Refer to the ETA for more details on these applications.

CHARACTERISTICS OF CFS-F FX

Characteristics Flexible wall Rigid wall
Health and the environment
Air permeability (gas tightness)
A p 50 Pa ⇒ 0.0007 q/A [m³/(h x m²)] (174 mm thickness of layer)
A p 250 Pa ⇒ 0.0033 q/A [m³/(h x m²)] Permeability regarding air
EN 1026
Dangerous substances Below any respective occupational exposure limits as far as such limits exist. Material safety data sheet
Safety in use
Resistance to impact / movement / Mechanical resistance and stability / Adhesion
Soft body impact: Energy 1200 Nm
Hard body impact: Energy 10 Nm
EOTA Technical Report TR001, A1
Protection against noise (Airborne sound insulation) Rw (C; Ctr) = 61 (-2; -6) dB
Dn,e,w (C; Ctr) = 69 (−2; −7) dB
EN ISO 140-3
EN ISO 20140-10
EN ISO 717-1
Durability and serviceability Category Y2 (suitable for penetration seals intended for use at temperatures between - 20 °C and + 70 °C) no exposure to rain or UV.
May be coated with acrylic dispersion, alkyd resin, polyurethan / acrylic and epoxy resin).
EOTA Technical Report TR024 EAD 350454-00-1104:2017
Reaction to fire Class E EN 13501-1
Models: CFS-F FX, Flexible Firestop Foam, CFS-F FX Flexible Firestop Foam, Firestop Foam

File Info : application/pdf, 8 Pages, 6.42MB

PDF preview unavailable. Download the PDF instead.

Technical-Manual-for-ETA-10-0109-CFS-F-FX-firestop-foam-for-penetrations-Approval-document-ASSET-DOC-2412696

References

Adobe PDF Library 16.0 Adobe InDesign 16.4 (Macintosh)

Related Documents

Preview Hilti Firestop Acrylic Sealant CFS-S ACR Technical Manual
Technical manual for Hilti Firestop Acrylic Sealant CFS-S ACR, detailing its applications, technical data, approved uses in various joint and penetration types, and key characteristics.
Preview Hilti CFS-MSL GPA Firestop Collar Installation Guide
Comprehensive guide detailing the installation process for the Hilti CFS-MSL GPA firestop collar, including safety precautions and step-by-step assembly instructions.
Preview Hilti Firestop Acrylic Sealant CFS-S ACR / CP 606 - Application Guide
Comprehensive guide for applying Hilti Firestop Acrylic Sealant CFS-S ACR / CP 606, detailing joint and penetration sealing procedures with curing information and safety guidelines.
Preview Hilti CFS-CT HDB: High-Density Coated Firestop Board Technical Manual
Comprehensive technical manual for Hilti's CFS-CT HDB high-density coated firestop board. This document details technical specifications, applications, advantages, installation instructions, and classification data for firestopping various building penetrations.
Preview Hilti Firestop System C-AJ-2631: Plastic Pipe Through Concrete Floor/Wall or Block Wall Assembly
Detailed installation guide for the Hilti Firestop System C-AJ-2631, outlining the assembly for plastic pipes passing through concrete floors, walls, or block walls. Provides fire ratings, material specifications, and assembly instructions for ensuring fire safety.
Preview Hilti CAJ 8318a: Firestop System for Multiple Penetrations in Concrete Walls and Floors
Technical specifications and installation guide for the Hilti CAJ 8318a UL System, detailing firestop solutions for multiple non-metallic, metallic, and cable penetrations through concrete floor and block wall assemblies with a 2-hour fire rating.
Preview Hilti CFS-MSL FGR Firestop System Installation Guide
Comprehensive installation guide for the Hilti CFS-MSL FGR firestop system, detailing assembly steps, component placement, and securing procedures with textual descriptions of diagrams.
Preview Hilti Fire Protection Systems: Comprehensive Guide for Concrete, Wood, and Masonry
Explore Hilti's advanced fire protection systems for sealing cables, pipes, and joints in concrete, wood, and masonry structures. Discover product details, technical specifications, approvals, and digital tools like the Hilti Brandschutz-Selektor and Fieldwire.