QUICK REFERENCE DATA

*SA3MD4M Series Split System Air Conditioner for Manufactured Housing

Model and Efficiency

Model Number: *SA3MD4M

Efficiency Rating: 13.4 SEER2

Table 1. Physical Data

Model Number: *SA3MD4M

Model Recommended Refrigerant Suction Line O.D. Refrigerant Charge
(R-410A in ounces for outdoor unit & 20' Lineset)
0 - 24 ft. 25 - 39 ft. 40 - 75 ft.
1RN24K 3/4" 3/4" 3/4" 67
1RN30K 3/4" 3/4" 3/4" 72
1SN36K 3/4" 7/8" (1) 7/8" (1) 65
1SN42K 7/8" 7/8" 7/8" 71
1SN48K 7/8" 7/8" 7/8" 74

NOTE: Liquid line is 3/8" O.D. for entire length.

Refrigerant Charge Notes:

  • (1) Requires 7/8" to 3/4" reducer from line to unit.
  • (2) Requires 1-1/8" to 7/8" reducer from line to unit.
  • (3) Additional charge for line sets above 20 feet. Values based on suction line as follows with 3/8" liquid line:
    • (a) 3/4" = 0.6 oz. per additional foot.
    • (b) 7/8" = 0.7 oz. per additional foot.
    • (c) 1 1/8" = 0.8 oz. per additional foot.

For other line set dimensions, refer to the Application Guidelines for Refrigerant Lines Addendum.

Table 2. Restrictor or TXV / Charge Addition (Oz)

Model Number: *SA3MD4M

MODELS SUPPLIED WITH ID OUTDOOR UNIT BOM CHARGE (OZ.) REQUIRED RESTRICTOR OR TXV (CHARGE ADDITION (OZ) / RATED AIRFLOW (SCFM))
1RN24K 1RN30K 1SN36K 1SN42K 1SN48K
C84-X
C84DAMX24U-B 669564 67 669564 (0 / 850) -- -- --
C84DAMX30U-B 669565 72 -- 669565 (0 / 1000) -- --
C84DAMX36U-B 669566 65 -- -- 669566 (0 / 1165) --
C84DAMX42U-B 669567 71 -- -- -- 669567 (0 / 1220)
C84DAMX48U-B 669568 74 -- -- -- -- 669568 (0 / 1400)

NOTES:

  • The charges listed are only valid for the standard 20' lineset.
  • Numbers listed as 0.*** are restrictor diameters, while numbers listed as 669*** are TXV part numbers.

THE CHARGE ADDITIONS PROVIDED IN THIS DOCUMENT ARE ESTIMATES BASED ON TEST DATA AND SHOULD ONLY BE A STARTING POINT. AFTER FOLLOWING THESE DIRECTIONS PLEASE ADJUST THE REFRIGERANT AMOUNT BASED ON THE APPROPRIATE CHARGING TABLES OR CHARTS IN THE INSTALLATION INSTRUCTIONS OR CHARGING LABEL.

Instructions for Use

  1. Find the column for the model of outdoor unit that is being installed.
  2. Find the row for the model of the indoor unit that is being installed.
  3. Find the cell in the table in which this row and column meet. In this cell the appropriate orifice / TXV and charge addition for this match are listed. If the text in this cell is BOLD, then a change of orifice is necessary.
  4. If a change in restrictor is necessary, then the appropriate restrictor will already be supplied with the outdoor unit.

Examples

  • For the *SA3MD4M1RN24K / C8DAMX24U-B match the appropriate TXV is 669564 and no additional charge needs to be added. (NO CHANGES NECESSARY).
  • For the *SA3MD4M1SN36K / C84DAMX36U-B match the appropriate TXV is 669566 and no additional charge needs to be added. (NO CHANGES NECESSARY).

PDF preview unavailable. Download the PDF instead.

10434520 Adobe PDF Library 16.0.7 Adobe InDesign 17.3 (Windows)

Related Documents

Preview VSA3BD4M Series Residential Split System Air Conditioner Quick Reference Data
Quick reference data for the VSA3BD4M Series Residential Split System Air Conditioner, including refrigerant line sizes, R-410A charge amounts, and required restrictor or TXV with charge addition for various indoor and outdoor unit combinations. This document provides essential specifications for installation and setup.
Preview GSA2BE4M Series Split System Air Conditioner Quick Reference Data
Quick reference data for the GSA2BE4M Series Split System Air Conditioner for Manufactured Housing, including refrigerant charge, physical data, and restrictor or TXV charge addition.
Preview GSA2(B,Q)D Series High Efficiency Air Conditioner Technical Specifications
Technical specifications and features for the GSA2(B,Q)D Series High Efficiency Air Conditioner, a 13 SEER manufactured housing system with 2-4 ton capacity. Includes model identification codes, dimensions, physical and electrical specifications, and system cooling capacities.
Preview GSA2QE4M1S Series Split System Air Conditioner Quick Reference Data
Quick reference data for the GSA2QE4M1S Series Split System Air Conditioner with Quick Connect Couplings, including physical data, refrigerant charge, and required restrictor or TXV information.
Preview SA1BE4M1 Series Residential Split System Air Conditioner Quick Reference Data
Quick reference data for the SA1BE4M1 Series Residential Split System Air Conditioner, including electrical specifications, physical data, and required restrictor or TXV information for various indoor and outdoor unit combinations.
Preview GXH24-36MSK4DH 2/3 Ton Inverter Split System Heat Pump ODU Submittal
Submittal document for the GXH24-36MSK4DH 2/3 Ton Inverter Split System Heat Pump Outdoor Unit (ODU). Details features, benefits, specifications, and installation clearances for this high-efficiency heat pump system.
Preview SA1BE4M1 Series 14 SEER Split System Air Conditioner Quick Reference Data
Technical quick reference data for the SA1BE4M1 Series 14 SEER split system air conditioner designed for manufactured housing. Includes electrical specifications, condenser data, refrigerant charge, dimensions, clearance requirements, and unit compatibility tables.
Preview Split System Air Conditioner Installation Instructions for Manufactured Housing
Comprehensive installation guide for Nortek Global HVAC SA3MD4M1 series split system air conditioners, covering safety, electrical, refrigerant charging, and maintenance procedures for manufactured housing.