R. STAHL 8530/1-MCB-STA103-C63-500-4 Circuit Breaker
Article Number: 293906
Product Overview
The R. STAHL 8530/1-MCB-STA103-C63-500-4 circuit breaker is part of the system components for technology. It offers excellent current limitation in case of short circuits and high breaking capacity (10, 15, or 25 kA), leading to reduced load on electrical lines and improved selectivity with upstream fuses. The modular design allows for 1 to 4 pole configurations and nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Key Features:
- Disconnector function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of installations due to modular design
- Simple mounting via DIN rail in Ex e enclosures
- Fixed thermal and magnetic tripping adjustment
- Ergonomic operating lever for safe connection and disconnection
- Protection against re-closing during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
- Applications (zones): 1, 2
- Applications (zones) Note: Can be used in zones 21/22 with Ex tb/tc enclosure protection
- Homologation IECEX gas: IECEX FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- Homologation ATEX gas: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certifications: ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
- Certificate of conformity: Certificate of conformity (ATEX)
Electrical Data
- Rated operating voltage AC: 230/400 V
- Rated operating current: 63 A
- Frequency: 50/60 Hz
- Rated switching capacity: 10 kA
- Electrical service life: 2 x 104
- Mechanical service life: 2 x 104
- 1st auxiliary function: Auxiliary contact 1 changeover contact + Error signal contact 1 changeover contact
- Voltage 1st auxiliary function AC: 230 V
- Max. current 1st auxiliary function: 2 A
- 2nd auxiliary function: None
- Max. voltage 2nd aux. function DC: Not specified
Tripping Characteristic
- Type: C
Number of Poles
- Poles: 3-pole
Environmental Conditions
- Ambient temperature: -40 °C ... 70 °C
- Ambient temperature (Fahrenheit): -40 °F ... 158 °F
- Ambient temperature Note: Divergent ambient temperatures based on valid certificates upon request
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP2X
- Enclosure material: Thermoplastic
- Minimum connection terminal size: 1.5 mm²
- Maximum connection terminal size: 25 mm²
- Minimum AWG connection size: 16 AWG
- Maximum AWG connection size: 4 AWG
- Minimum connection size 2: 1.5 mm²
- Maximum connection size 2: 10 mm²
- Minimum AWG connection size 2: 16 AWG
- Maximum AWG connection size 2: 8 AWG
- Minimum HIKO connection size: 0.5 mm²
- Maximum HIKO connection size: 4 mm²
- Minimum HIKO AWG connection size: 18 (unece.unit.AWG)
- Maximum HIKO AWG connection size: 14 (unece.unit.AWG)
- Minimum torque: 2 N·m
- Maximum torque: 3 N·m
- Connection terminal note: 2 conductor connections (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (only one cross-sectional difference can be connected in the upper and lower chamber). Permitted connection terminal combinations are listed in the operating instructions.
Dimensions
- Width: 110 mm (4.33 in)
- Mounting width: 110 mm (4.33 in)
- Length: 165 mm (6.5 in)
- Depth of installation: 138.3 mm (5.44 in)
- Weight: 1.8 kg (3.969 lb)
Mounting / Installation
- Torque: 2-3 N·m
- Torque (lbf in): 17.7 ... 26.6 lbf-in
- Torque auxiliary contact: 0.4-0.6 Nm
- Torque auxiliary contact (lbf in): 3.5 ... 5.3 lbf in
Technical Diagrams
Tripping Characteristic Curve C: A graph shows the tripping time in seconds against the multiple of the rated current (I/In) for tripping characteristic C. The curve illustrates the time delay for overcurrent protection.
Measurement Diagram: A dimensional drawing shows the overall dimensions of the circuit breaker, including width, length, and installation depth, with measurements provided in both millimeters and inches.
Accessories
-
Cylinder Lock: For locking (shackle Ø 3). Article Number: 107115
-
Quadruple immobilization device: Locking/tagging tongs for individual component locking using up to 4 cylinder locks. Article Number: 227232
-
Fixing Kit: A set of fixings for mounting the component on a mounting plate without a top hat rail. Article Number: 276618
R. STAHL Schaltgeräte GmbH reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.