Aprilaire Model 8820 Touch Screen Wi-Fi Automation Thermostat
Safety & Installation Instructions
Wi-Fi Setup
To connect the 8820 thermostat to a Wi-Fi network, follow these steps. You will need a computer or mobile device with Wi-Fi and a web browser.
Step 1: Verify the thermostat is in Wi-Fi Connection Mode
The thermostat defaults to Wi-Fi Connection Mode. Confirm this by checking for strobing radio bars on the thermostat display.
If the thermostat is not in Wi-Fi Connection Mode, refer to the Owner's Manual for instructions on clearing Wi-Fi settings.
Step 2: Connect to the thermostat using a computer or mobile device
On your computer or mobile device, scan for available networks. The thermostat should appear as APRILAIRE8820 followed by a unique identifier (last 6 digits of the MAC address). Connect to the thermostat you wish to configure.
If installing multiple thermostats, the MAC address for each will be displayed in the message center. The MAC address can also be found by removing the front cover.
Step 3: Configure the thermostat to connect to the Wi-Fi network
Open a web browser on your computer or mobile device and enter: http://192.168.1.99/index.html
In the web browser interface, select the desired network and enter its security credentials.
Step 4: Verify the thermostat is connected to the Wi-Fi network
After entering the required information, the thermostat will connect to the selected Wi-Fi network. The radio bars will then display the Wi-Fi signal strength. If signal strength is not displayed, refer to "Troubleshooting Wi-Fi Connection" on page 22.
If not using a home automation system and instead using an Aprilaire account, set "Automation Enable" to "Aprilaire Cloud" in the installer setup menu (pages 8 & 9). Visit my.aprilaire.com for the Wi-Fi Thermostat App User Guide and startup instructions.
Installation
Installation Location Recommendations
Thermostat should be mounted:
- On an interior wall, in a frequently occupied space.
- Approximately 5' above floor.
- At least 18" from outside wall.
- Thermostat can be mounted to a vertical junction box.
Do not mount thermostat:
- Behind doors, in corners, or other dead air spaces.
- In direct sunlight, near lighting fixtures, or other heat-generating appliances.
- On an outside or unconditioned area wall.
- In the flow of a supply register, in stairwells, or near outside doors.
- On a wall with concealed pipes or ductwork.
Outdoor Temperature Sensor (Included)
The included 8052 sensor can be attached to terminals S1 and S2 to measure outdoor temperature. This sensor must be enabled in the installer setup menu.
Heat pump models can use outdoor temperature for effective heat pump utilization:
- Below the Low Balance Point: Heat pump is locked out; only auxiliary heating is used.
- Above the High Balance Point: Auxiliary heating is locked out; only the heat pump is used.
Indoor Air Quality functions can use the outdoor temperature sensor for:
- Controlling humidification setpoint to prevent condensation.
- Locking out humidification for temperatures over 60°F or below -30°F.
- Locking out ventilation based on high/low outdoor temperatures.
- Displaying outdoor temperature on the thermostat.
Outdoor temperature sensor should be mounted:
- On the side of the building, out of direct sunlight (north side recommended).
- Above the snow line.
- At least 3' away from exhaust vents and condensing lines.
- Using less than 300' of wire.
- Do not route wires along 120 VAC lines.
Wiring Terminal Diagram Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Remote Temperature Sensor (Optional)
An optional 8051 flush mount or 8053 surface mount remote temperature sensor can be attached to terminals T1 and T2. This sensor can be used to control a large space by averaging with the thermostat's internal sensor or overriding it, based on installer setup menu settings.
Remote temperature sensor should be mounted:
- On an interior wall, in a frequently occupied space.
- Approximately 5' above floor.
- At least 18" from outside wall.
- Using less than 300' of wire.
Do not mount remote sensor:
- Behind doors, in corners, or other dead air spaces.
- In direct sunlight, near lighting fixtures, or other heat-generating appliances.
- On an outside or unconditioned area wall.
- In the flow of a supply register, in stairwells, or near outside doors.
- On a wall with concealed pipes or ductwork.
- Near 120 VAC lines.
Wiring Terminal Diagram Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Thermostat Mounting
- Remove the rear mounting plate from the thermostat.
- Pull wires through the opening on the back of the rear mounting plate.
- Position and level the mounting plate on the wall and mark hole locations.
- Drill 1/4" holes and insert supplied anchors (for drywall).
- Place mounting plate over anchors, insert and tighten screws.
- Seal wire entry holes to prevent drafts affecting temperature readings.
Power & Reset Options
The thermostat is powered by 24VAC. It maintains the clock for 24 hours during power loss and has a memory backup for settings. The reset button (under the front cover) can reset the thermostat to factory defaults, including Installer System Settings.
[RESET BUTTON Icon]
Wiring Terminal
Wire specifications: 18-24 gauge thermostat wire.
Installation notes:
- Ensure power at the HVAC equipment is off.
- Loosen screw terminals, insert stripped wire, and re-tighten.
- Push excess wire back into the opening and plug the wall opening to prevent drafts.
Terminal Descriptions:
- RSB & RSA: Model 8081 or 8082 Support Module communication
- I1 & I2: Indoor Air Quality control output
- C: Common
- O/B: Reversing valve
- Y: First stage cooling (conventional) / First stage compressor (heat pump)
- Y2: Second stage cooling (conventional) / Second stage compressor (heat pump)
- G: Fan
- RC: 24VAC supply cooling¹
- R: 24VAC supply heating¹
- W2: Second stage heat (conventional) / Second stage auxiliary (heat pump)
- W: First stage heat (conventional) / First stage auxiliary (heat pump)
- L: System fault indicator (optional) (heat pump only)
- S1 & S2: Outdoor temperature sensor (included)
- T1 & T2: Remote temperature sensor (optional)
¹Jumper between RC & R is used in single transformer systems (see wiring diagrams).
Wiring Terminal Diagram Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Wiring Diagrams
The following diagrams illustrate typical wiring configurations. Refer to individual equipment manuals for specific details.
Conventional Heat/Cool Wiring Diagrams
Single Transformer (Use Jumper Wire)
Diagram shows connections for 1st Cooling, 2nd Cooling, Fan, Cooling Transformer, 1st Heating, 2nd Heating, Heating Transformer, Remote Temp Sensor, Outdoor Temp Sensor, Not Used terminals.
Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Two Transformers (Remove Jumper Wire)
Diagram shows connections for 1st Cooling, 2nd Cooling, Fan, Cooling Transformer, 1st Heating, 2nd Heating, Heating Transformer, Remote Temp Sensor, Outdoor Temp Sensor, Not Used terminals.
Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Heat Pump Wiring Diagrams
Single Transformer (Use Jumper Wire)
Diagram shows connections for Reversing Valve, 1st Compressor, 2nd Compressor, Fan, Transformer, 2nd Aux Heating, 1st Aux Heating, Fault Detect, Outdoor Temp Sensor, Remote Temp Sensor, Not Used terminals.
Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Two Transformers (Remove Jumper Wire)
Diagram shows connections for Reversing Valve, 1st Compressor, 2nd Compressor, Fan, Transformer, 2nd Aux Heating, 1st Aux Heating, Fault Detect, Outdoor Temp Sensor, Remote Temp Sensor, Not Used terminals.
Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Indoor Air Quality Equipment Wiring Diagrams
Dehumidifier Wiring
Diagram shows connection for Dehumidifier Transformer and terminals RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2.
Note: The I1/I2 output is a dry contact closure. The dehumidifier wiring diagram is for a normally open dry contact input.
Humidifier Wiring
Diagram shows connection for Humidifier Transformer and terminals RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2.
Note: The humidifier wiring diagram assumes the control is powering a solenoid valve.
Ventilation Wiring
Diagram shows connection for Normally Closed Damper Transformer and terminals RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2.
Note: The ventilation diagram assumes the control is for a normally closed damper.
Refer to individual humidifier, dehumidifier, or ventilation installation instructions for product-specific wiring details.
Support Module Wiring Diagram
Diagram shows connections for Model 8081 or 8082 Support Module with terminals RC, C, RSB, RSA, T1, T2, T3, T4.
Note: Up to four Support Modules can be wired to the thermostat. Use CAT-5 wire. Total wire length for all support modules should not exceed 1000 feet.
Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2
Setup & Testing
Equipment Type Selection Switch (SW1)
This thermostat supports heat pump or heat/cool systems. Switch SW1, located on the back of the thermostat face, selects this option. This setting is displayed in the Installer System Settings under "Equipment Type".
SW1 positions: HEAT/COOL, HEAT PUMP.
Installer Setup Menu
How to Enter the Installer Setup Menu and Select Equipment to Setup:
- Press [MODE] to set the system to OFF.
- Press [MENU] to enter the main menu.
- Press and hold [SETUP] for seven seconds until [INSTALL SETUP] appears.
- Press [INSTALL SETUP] to enter the installer setup menu.
In the Installer Setup menu, you can select Thermostat or Indoor Air Quality (IAQ) setup. For IAQ setup, you can then choose to configure Air Cleaning, Humidification, Dehumidification, or Ventilation.
Use [NEXT] or [BACK] to navigate settings. Use [UP ARROW] or [DOWN ARROW] to adjust options. Press [MENU] to exit. Press [DONE] to save and exit, or [CANCEL] to exit without saving.
If IAQ setup is selected first, the Installer System Setting for Outdoor Sensor will be presented before entering IAQ setup.
To reset Installer System Settings to defaults, press the [RESET] button for 5 seconds.
Change System Settings
Press [NEXT] or [BACK] to page through settings. Press [UP ARROW] or [DOWN ARROW] to adjust the setting.
Thermostat Installer System Settings Table
System setting | Description | Factory default setting (bold) and setting range |
---|---|---|
00. Automation Enable | Selects if the thermostat connects with an automation system or an Aprilaire account. | 0: Aprilaire Cloud 1: Automation System |
01. Equipment Type | Equipment type set by SW1. | Heat/Cool Heat Pump |
02. Temperature Scale | Set the thermostat to Fahrenheit or Celsius mode. | Fahrenheit Celsius |
03. Reversing Valve | Selects O or B operation. | 0 - On in cooling B - On in heating |
04. Control Setup | Used to lockout heating or cooling outputs. Note: Only available if Equipment Type is set to Heat/Cool. | Heat and Cool Heat Only Cool Only |
05. Heat/Cool: Cooling Stages Heat Pump: Compressor Stages | Heat/Cool: Number of Cooling Stages. Heat Pump: Number of Compressor Stages. | One Two |
06. Heat/Cool: Heating Stages Heat Pump: Aux Heat Stages | Heat/Cool: Number of Heat Stages. Heat Pump: Number of Auxiliary Heat Stages. | One Two |
07. Heat/Cool: Fan Control in Heating Heat Pump: Auxiliary Equipment Type | Heat/Cool: Determines if the thermostat or equipment controls the fan in heating. Heat Pump: Auxiliary Equipment type. | Gas/Oil Heat (equipment controls fan) Electric Heat (thermostat controls fan) |
08. Extended Fan - Heat | Extends fan operation after heat call ends. | Disable Enable (90 second extension) |
09. Extended Fan - Cool | Extends fan operation after cool call ends. | Disable Enable (90 second extension) |
10. Temperature Sensor Offset | Field adjustment of controlling temperature sensor(s). | 0° (no offset applied) -4°F to +4°F (-2°C to +2°C) |
11. Humidity Offset | Field adjustment of internal RH sensor. | 0 (no offset applied) -5% to +5% |
12. Auto Changeover | Enable or disable Auto Changeover mode. | Disable Enable |
13. Deadband | Auto Changeover mode deadband. | 3°F (1.5°C) 2°F to 9°F (1°C to 4.5°C) |
14. Remote Sensor | Select if remote sensor is attached, and if it is attached, if it is the primary control or averaged with the built-in sensor. If the remote sensor is the primary control it can be configured to use the built-in sensor as a back-up sensor. | Not installed Control no backup Control with built-in backup Average with thermostat built-in sensor |
15. Outdoor Sensor | Selects if an outdoor temperature sensor is not installed, a wired sensor is installed, or the outdoor temperature is provided by the automation system. Note: Automation is only available if Automation Enable is set to Automation System. | Not installed Installed Automation |
18. Compressor Min Off Time | Minimum off time for compressor protection. | 5 minutes 1 to 5 minutes |
19. Heating Min Off Time | Minimum off time for heating. | 2 minutes 1 to 5 minutes |
20. Equipment Min On Time | Minimum on time for heating and cooling. | 2 minutes 1 to 5 minutes |
21. Auto Changeover Time | Minimum time between heating and cooling calls. | 4 minutes 1 to 5 minutes |
22. First Stage Differential | First stage differential. | 1°F (0.5°C) 1°F to 9°F (0.5°C to 4.5°C) |
23. Second Stage Differential | Second stage differential. | 1°F (0.5°C) 1°F to 9°F (0.5°C to 4.5°C) |
24. Third Stage Differential | Third stage differential. | 1°F (0.5°C) 1°F to 9°F (0.5°C to 4.5°C) |
25. Fourth Stage Differential | Fourth stage differential. | 1°F (0.5°C) 1°F to 9°F (0.5°C to 4.5°C) |
26. Away | Enables the Away feature. The Away feature allows the automation system or Aprilaire mobile and web apps to use a single button press to set the thermostat to a predefined setpoint(s). The thermostat will hold the setpoint(s) until Away is canceled with the automation system or app or at the thermostat. | Disable Enable |
27. Heat Blast | Enables the Heat Blast feature. | Disable Enable |
28. Blast Offset | Amount of heating when Heat Blast is initiated. | 3°F (1.5°C) 3°F to 5°F (1.5°C to 2.5°C) |
37. Stage Rate | Accumulation of equipment run time in equipment staging determination. 1 = more rapid staging of equipment (comfort). 5 = slower staging of equipment (economy). | 2 1 to 5 or "OFF" to ignore accumulated run time. |
38. Progressive Recovery | Enable or disable progressive recovery. | Disable Enable |
39. Low Balance Point | Outdoor temperature low balance point. Note: This option is only available if the thermostat is set to Heat Pump and Outdoor Sensor is set to Installed or Automation. | 20°F or -8°C 0°F to 60°F (-18°C to 12°C) or OFF to ignore LBP |
40. High Balance Point | Outdoor temperature high balance point. Note: This option is only available if the thermostat is set to Heat Pump and Outdoor Sensor is set to Installed or Automation. | 65°F or 14.5°C 0°F to 80°F (-18°C to 22°C) or OFF to ignore HBP |
41. Program Format | Enables the 7-day program. | 7-Day Non-Prog |
42. Reset Service Reminders | Clears the Air Filter, Dehumidifier, Fresh Air, and HVAC service reminders if they are active and resets the start date to the current date. Clears the Change Water Panel reminder if it is active. If the reminder is set to Timed, the clock will be reset. | No Yes |
43. HVAC Service Reminder | The period for displaying the "HVAC Service Reminder" message. | Off 1 to 12 months or "Off" to disable |
44. Constant Backlight | Enable constant, low intensity backlight. | Disable Enable |
45. Backlight Intensity | Set the active backlight intensity. Note: The minimum setting is 40% when Constant Backlight is enabled. | 100 Percent 0 to 100 Percent |
51. Support Module Controlling Temp Sensors | Sets the number of controlling support module temperature sensors. | NONE 1 to 8 |
52. Support Module Controlling RH Sensors | Sets the number of controlling support module humidity sensors. | NONE 1 to 4 |
53. Display Monitor Support Module Sensor | Selects if the temperature or humidity values from support modules that are configured for monitoring are displayed in the message center of the thermostat. | No Yes |
Indoor Air Quality System Settings Tables
The following tables contain the Indoor Air Quality system settings and their details. Default settings are shown in bold. Some settings are only present dependent upon the value of other settings. The use of the included outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality. If the outdoor temperature sensor was not enabled in the thermostat system settings, thermostat system setting 15, outdoor sensor, will be presented prior to entering the Indoor Air Quality system settings. Please refer to the Model 8820 Owner's Manual for further information about thermostat features.
Air Cleaning System Settings Table
System setting | Description | Factory default setting (bold) and setting range |
---|---|---|
Air Cleaner Installed | Selects if an air cleaner is installed. (If set to no, no other air cleaning settings will be available.) | No Yes |
Change Air Filter Reminder | The period for displaying the "Change Air Filter" message. | Off 1 to 12 months or "Off" to disable |
Humidifier System Settings Table
Note: A humidifier can only be installed if ventilation is not installed and Dehumidifier Control is not set to Whole Home or AC w/IAQ Output.
System setting | Description | Factory default setting (bold) and setting range |
---|---|---|
Humidifier Installed | Selects if a humidifier is installed. Yes/On HVAC is used for applications where the humidifier is installed on the HVAC duct. Yes/Standalone is used for application where the humidifier is independent of the HVAC system. (If set to no, no other humidifier settings will be available.) | No Yes/On HVAC Yes/Standalone |
Humidifier Mode | Selects auto or manual mode. Auto mode controls humidity based on the humidity setting and outdoor temperature. Manual mode controls humidity based on the %RH setpoint. (Auto mode is only available if outdoor sensor is set to Installed or Automation.) | Auto Manual |
Humidity Setpoint Deadband | Selects the minimum difference between the humidifier and dehumidifier setpoints. (Only available if a humidifier is installed and dehumidifier control is set to air conditioner. Available in both set-ups.) | 10 Percent RH 10 to 20 Percent RH |
Humidifier Operation | Selects when humidification is allowed to occur relative to heating and fan operation. Without Fan allows humidification to occur without the HVAC fan. This option should only be used when the humidifier is independent of the HVAC system. Note: Without Fan is only available when Humidifier Installed is set to Yes/Standalone. | Heat Only Heat or Fan Forces Fan Without Fan |
CAUTION: When Humidifier Operation is set to Without Fan the thermostat will turn on humidification without energizing the HVAC fan. Do not select this option when the humidifier is installed on the HVAC duct. Without airflow moisture can accumulate in the duct resulting in significant damage. | ||
Change Water Panel Reminder | Selects the when the "Change Water Panel" message is displayed. | Off 1 Per Season 2 Per Season 300 Hours 600 Hours |
Reminder Month (Change Water Panel Reminder set to 1 per Season) | Change Water Panel Reminder set to 1 per Season: Determines the month the "Change Water Panel" message is displayed. | October November December January February March April May June July August September |
First Reminder Month (Change Water Panel Reminder set to 2 per Season) | Change Water Panel Reminder set to 2 per Season: Determines the first month the "Change Water Panel" message is displayed. | October November December January February March April May June July August September |
Second Reminder Start Month | Determines the second month the "Change Water Panel" message is displayed. (Only available when Change Water Panel Reminder set to 2 per Season.) | October November December January February March April May June July August September |
Dehumidifier System Settings Table
Note: Dehumidifier Control can only be set to Whole Home or AC w/IAQ Output if ventilation and humidification are not installed.
System setting | Description | Factory default setting (bold) and setting range |
---|---|---|
Dehumidifier Control | Selects method of dehumidification. If set to None, no other dehumidifier settings will be available. If dehumidification is done with the air conditioner, using the option of AC w/IAQ Output will cause the IAQ output to be active when overcooling for dehumidification. This can be used if the HVAC equipment has a dedicated input to slow the fan during cooling to maximize dehumidification. | None (no dehumidification installed) Whole Home Air Conditioner AC w/IAQ Output |
Humidity Setpoint Deadband | Select the minimum difference between the humidifier and dehumidifier setpoints. (Only available if a humidifier is installed and Dehumidifier Control is set to Air Conditioner. Available in both set-ups.) | 10 Percent RH 10 to 20 Percent RH |
Lockout Dehumidifier During Cooling | Selects if dehumidification is disabled during a cooling call. (Only available if Dehumidifier Control is set to Whole Home.) | No Yes |
Dehumidifier Forces Fan | Select if dehumidification can turn on the fan. (Only available if Dehumidifier Control is set to Whole Home.) | No Yes |
Dehumidifier Service Reminder | The period for displaying the "Dehum Service Reminder" message. (Only available if Dehumidifier Control is set to Whole Home.) | Off 1 to 12 months or "Off" to disable |
Dehumidifier Overcooling Limit | Selects the amount of overcooling that can occur for dehumidification. (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output.) | 3°F (1.5°C) 1°F to 3°F (0.5°C to 1.5°C) |
Dehumidify in Vacation Mode | Selects if dehumidification with the air conditioner is done in Vacation Mode. (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output. | No Yes |
Vacation Dehumidifier Low Temp Limit | Sets the lowest temperature the air conditioner will cool to, to meet RH setpoint in Vacation Mode. (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output.) | 75°F (23.5°C) 70°F to 85°F (21°C to 28.5°C) |
Ventilation System Settings Table
Note: Ventilation can only be installed if humidification is not installed and Dehumidifier Control is not set to Whole Home or AC w/IAQ Output.
System setting | Description | Factory default setting (bold) and setting range |
---|---|---|
Fresh Air Vent Installed | Selects if ventilation is installed. (If set to No, no other ventilation settings will be available.) | No Yes |
Fresh Air Setup Type | Selects if ventilation is configured through the Code setup or Comfort. Comfort setup has more lockout options. Code setting ensures missed lockout time is made up. | Comfort Code |
Number of Bedrooms | Selects the number of bedrooms to be used for the Calculated Minutes per Hour. | 3 Bedrooms 1 to 10 Bedrooms |
Home Size | Selects the size of the home to be used for the Calculated Minutes per Hour. | 2500 SQ FT 500 to 7500 SQ FT |
Measured CFM | Selects the ventilation CFM to be used for the Calculated Minutes per Hour. | 110 CFM 30 to 250 CFM |
Calculated Minutes per Hour | Displays the Fresh Air Time calculated. | None Range 6 to 60 Minutes |
Override | Manual adjustment of Calculated Minutes per Hour. | (Calculated Minutes per Hour) Range 6 to 60 Minutes |
Enable High Vent RH Limit | Selects if ventilation is disabled if the indoor RH exceeds the indoor RH limit. (Only available if Fresh Air Setup is set to Comfort.) | Yes No |
High Vent RH Limit | Sets the ventilation indoor RH lockout limit. (Only available if Enable High Vent RH Limit is set to Yes.) | 55% 45% to 70% |
Enable Low Vent RH Limit | Selects if ventilation is disabled if the indoor RH exceeds the indoor RH limit. (Only available if Fresh Air Setup is set to Comfort.) | No Yes |
Low Vent RH Limit | Sets the ventilation indoor RH lockout limit. (Only available if Enable Low Vent RH Limit is set to Yes.) | 20% 10% to 30% |
Enable High Vent Temperature Limit | Enables high ventilation temperature lockout limit. (Only available if Outdoor Sensor is set to Installed or Automation.) | No Yes |
High Vent Temperature Limit | Sets high ventilation temperature lockout limit. (Only available if Enable High Vent Temperature Limit is set to Yes.) | 100°F (38°C) 85°F to 105°F (29°C to 41°C) |
Enable Low Vent Temperature Limit | Enables low ventilation temperature lockout limit. (Only available if Outdoor Sensor is set to Installed or Automation.) | No Yes |
Low Vent Temperature Limit | Sets low ventilation temperature lockout limit. (Only available if Enable Low Vent Temperature Limit is set to Yes.) | 10°F (-12°C) -10°F to 40°F (-24°C to 6°C) |
HVAC Fan with Vent | Selects if ventilation forces the fan on. (Yes with high and low limits is only available if Outdoor Sensor is set to Installed or Automation.) | Yes Yes with high and low limits |
Enable High Mixing Temperature | Enables high mixing temperature. (Only available is HVAC Fan with Vent is set to Yes with high and low limits.) | No Yes |
High Mixing Temperature | Sets the high mixing temperature. (Only available if Enable High Mixing Temperature is set to Yes.) | 80°F or (26°C) 60°F to 105°F (14°C to 41°C) |
Enable Low Mixing Temperature | Enables low mixing temperature. (Only available is HVAC Fan with Vent is set to Yes with high and low limits.) | No Yes |
Low Mixing Temperature | Sets the Low mixing temperature. (Only available if Enable Low Mixing Temperature is set to Yes.) | 40°F (6°C) 0°F to 50°F (-18°C to 12°C) |
Fresh Air Service Reminder | The period for displaying the "SERVICE FRESH AIR" message. | OFF 1 to 12 months or "OFF" to disable |
Refer to manuals for humidifier, dehumidifier, air cleaner, and ventilation products for recommended installation and operation.
Removal of Indoor Air Quality Control Buttons
If any Indoor Air Quality control features are not installed, the corresponding button can be removed using the following procedure:
- Verify the specific Indoor Air Quality control feature is not installed in the Installer System Settings (see pages 11-14).
- From the home screen (see page 20), press and hold the Indoor Air Quality button you wish to remove for 7 seconds.
- The message center will display REMOVE BUTTON and the options of NO and YES (NO will be flashing).
- Press [UP ARROW] or [DOWN ARROW] to select YES.
- Press [DONE].
- The button is now removed.
Once the button is removed, it can be brought back by installing the corresponding Indoor Air Quality feature (see pages 11-14).
System Test Menu
The system test menu is used to test a system after installation. The thermostat's outputs can be manually activated to test their function. The instructions below show how to enter the test mode and turn outputs on and off.
How to Enter the System Test Menu:
- Press [MODE] to set the system to off.
- Press and hold [FAN] and [MODE] for three seconds to enter system test mode.
- The first screen of the installer test displays the equipment configuration.
- Press [NEXT] to enter the first installation test or [CANCEL] to exit.
System Test Steps: Heating equipment test, Cooling equipment test, Fan equipment test, Humidification equipment test, Dehumidification equipment test, Ventilation equipment test.
System Test Menu (Continued)
Each equipment test begins with selecting the output or stage to turn on. Press [UP ARROW] or [DOWN ARROW] to change the selection. Press [NEXT] to accept the selection and proceed to the next step. If YES is selected, the thermostat will test the corresponding output. If NO is selected, the thermostat will proceed to the next step.
While the equipment test is active, the corresponding test information will be shown. Press [NEXT] to accept the selection and proceed to the next test selection.
System Test Tables
Heat / Cool Heating Equipment Test
Heat Type | W | W2 | Y | Y2 | G | |
---|---|---|---|---|---|---|
Gas | 1st Stage Test | ON | ON | |||
Gas | 2nd Stage Test | ON | ON | ON | ||
Electric | 1st Stage Test | ON | ON | |||
Electric | 2nd Stage Test | ON | ON | ON |
Heat Pump Heating Equipment Test (Electric Heat)
Compressor Stages | Aux Stages | O/B set to | W | W2 | Y | Y2 | G |
---|---|---|---|---|---|---|---|
1 | 1 | 1st Stage Test | ON | ON | ON | ON | |
1 | 1 | 2nd Stage Test | ON | ON | ON | ON | ON |
2 | 1 | 1st Stage Test | ON | ON | ON | ON | |
2 | 1 | 2nd Stage Test | ON | ON | ON | ON | ON |
2 | 1 | 3rd Stage Test | ON | ON | ON | ON | ON |
1 | 2 | 1st Stage Test | ON | ON | ON | ON | |
1 | 2 | 2nd Stage Test | ON | ON | ON | ON | ON |
1 | 2 | 3rd Stage Test | ON | ON | ON | ON | ON |
2 | 2 | 1st Stage Test | ON | ON | ON | ON | |
2 | 2 | 2nd Stage Test | ON | ON | ON | ON | ON |
2 | 2 | 3rd Stage Test | ON | ON | ON | ON | ON |
2 | 2 | 4th Stage Test | ON | ON | ON | ON | ON |
Note: System Variable 03, O/B operation selects O or B.
Heat Pump Heating Equipment Test (Gas Heat)
Compressor Stages | Aux Stages | O/B set to | W | W2 | Y | Y2 | G |
---|---|---|---|---|---|---|---|
1 | 1 | 1st Stage Test | ON | ON | ON | ON | |
1 | 1 | 2nd Stage Test | ON | ON | ON | ON | ON |
2 | 1 | 1st Stage Test | ON | ON | ON | ON | |
2 | 1 | 2nd Stage Test | ON | ON | ON | ON | ON |
2 | 1 | 3rd Stage Test | ON | ON | ON | ON | ON |
1 | 2 | 1st Stage Test | ON | ON | ON | ON | |
1 | 2 | 2nd Stage Test | ON | ON | ON | ON | ON |
1 | 2 | 3rd Stage Test | ON | ON | ON | ON | ON |
2 | 2 | 1st Stage Test | ON | ON | ON | ON | |
2 | 2 | 2nd Stage Test | ON | ON | ON | ON | ON |
2 | 2 | 3rd Stage Test | ON | ON | ON | ON | ON |
2 | 2 | 4th Stage Test | ON | ON | ON | ON | ON |
Note: System Variable 03, O/B operation selects O or B.
Heat / Cool Cooling Equipment Test
W | W2 | Y | Y2 | G | |
---|---|---|---|---|---|
1st Stage Test | ON | ON | ON | ||
2nd Stage Test | ON | ON | ON | ON | ON |
Heat Pump Cooling Equipment Test
O/B set to | W | W2 | Y | Y2 | G | |
---|---|---|---|---|---|---|
1st Stage Test | O | ON | ON | ON | ||
1st Stage Test | B | ON | ON | ON | ||
2nd Stage Test | O | ON | ON | ON | ON | ON |
2nd Stage Test | B | ON | ON | ON | ON | ON |
Note: System Variable 03, O/B operation selects O or B.
Fan Equipment Test
W | W2 | Y | Y2 | G | |
---|---|---|---|---|---|
ON | ON |
Humidification Equipment Test
I1/I2 | G | |
---|---|---|
ON | ON |
Dehumidification Equipment Test
I1/I2 | G | |
---|---|---|
ON | ON |
Ventilation Equipment Test
I1/I2 | G | |
---|---|---|
ON | ON |
Quick Reference to Controls & Display
Home Screen
Displays:
- Room Temperature
- Current Day
- Outdoor Temperature
- Room Relative Humidity
- Temperature Setting
- Wi-Fi Signal Strength
- Heat Blast Button
- Main Menu Button
- Air Cleaning Button (Enters Event-Based™ Air Cleaning Control Screen)
- Humidity Control Button (Enters Humidity Control Screen)
- Fresh Air Button (Enters Ventilation Control Screen)
- Temperature Adjustment Indicators
- Heat Pump Only Emergency Heat or Auxiliary Heat (Red indicator)
- System Fault (Yellow indicator)
- Maintenance Reminder (Yellow flashing indicator)
- Hold Button (Sets or Clears Hold)
- Current Time & Date
Note: Backlight is activated with the first button press and automatically turns off.
Main Menu
Accessed via the [MAIN MENU] button. Options include:
- Set Schedule Button
- Clean Screen (Locks out touch screen for 30 seconds)
- Set Vacation Hold (Hold - To Time and Date)
- Set Current Time and Date
- Done Button (Exit Menu)
- Installer/User System Setting
Troubleshooting
Display is Blank
- Check circuit breaker and reset if necessary.
- Ensure power switch at the heating & cooling system is on.
- Make sure the furnace door is closed securely.
Temperature Settings Do Not Change
Ensure heating and cooling temperatures are set to acceptable ranges:
- Heat: 40° to 90°F (4° to 32°C).
- Cool: 50° to 99°F (10° to 37°C).
Heating System Does Not Respond ("HEATING" Appears on Screen)
- Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment for the cause.
- Check for 24VAC between the heat terminal (W) and the transformer common. If 24VAC is present, the thermostat is functional; check the heating equipment.
- Check for loose or broken wires between the thermostat and the heating equipment.
Cooling System Does Not Respond ("COOLING" Appears on Screen)
- Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment for the cause.
- Check for 24VAC between the cooling terminal (Y) and the transformer common. If 24VAC is present, the thermostat is functional; check the cooling system.
- Check for loose or broken wires between the thermostat and the cooling equipment.
Fan Does Not Turn On in a Call for Heat
- Check System Setting 07 (Fan Control) to ensure it matches the system type (see page 9).
Heat Pump Issues Cool Air in Heat Mode, or Warm Air in Cool Mode
- Check System Setting 03 (O/B Operation) to ensure the reversing valve operation matches the heat pump.
Heat/Cool Both On at Same Time
- Check SW1 (Equipment Type) to ensure it matches the installed heating/cooling equipment (see page 8).
- Ensure heating and cooling wires are not shorted together.
Heating Equipment is Running in Cool Mode
- Check SW1 (Equipment Type) to ensure it matches the installed heating/cooling equipment (see page 8).
"HEATING" Is Not Displayed
- Check Installer System Setting number 04 (Control Setup) is set correctly.
- Change the System Mode to Heat and set the temperature level above the current room temperature.
"COOLING" Is Not Displayed
- Check Installer System Setting number 04 (Control Setup) is set correctly.
- Change the System Mode to Cool and set the temperature level below the current room temperature.
Humidifier Does Not Operate in Auto Mode
- Check Installer System Setting number 15 (Outdoor Sensor) is set to Installed or Automation.
- Verify the outdoor sensor is functioning correctly or if set to Automation, that it has not timed out. If functioning correctly, the outdoor temperature will display in the outdoor temperature location (see Home Screen on page 20).
Troubleshooting Wi-Fi Connection
The Wi-Fi connection status is communicated via the radio strength indicator and the message center. The table below describes various statuses, messages, and radio bar displays.
Wi-Fi connection status | Radio status indicator | Message Center |
---|---|---|
Normal Operation. | Wi-Fi signal strength indicated by the number of bars. | No corresponding message |
The thermostat Wi-Fi settings have not been entered. Refer to Wi-Fi Setup on page 2 for instructions for entering the Wi-Fi settings. | The frame is displayed and the bars cycle from 0 to 4. | Displays the SSID of the thermostat. Note: The SSID will be used to identify the thermostat when using a smart device to connect the thermostat to your Wi-Fi router. |
The thermostat cannot connect to the Wi-Fi router. Verify that the router is functioning properly. | The frame and all bars flash on and off. | WiFi Connection Lost |
Indicates the thermostat was not configured properly when connecting to the router. Confirm there is no IP conflict and repeat Wi-Fi setup. Note: If the thermostat is configured to work with an Aprilaire account this indicates that the thermostat cannot connect to the Aprilaire Cloud. Confirm that the internet connection is working. | The display will alternate between displaying the frame and all bars. | Internet Connection Lost |
There is an internal error with the thermostat Wi-Fi radio. The thermostat will continue to control the HVAC and indoor air quality control equipment, but will not be able to connect to Wi-Fi. Contact an HVAC professional for repair. | The frame will flash on and off. | Radio Error |
Wi-Fi radio turned off. Refer to the Accessing Wi-Fi Settings Menu in the Owner's Manual for information about turning the Wi-Fi radio on. | Not displayed. | WiFi Turned Off |
Error Codes
If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to recover every 10 minutes.
Error code | Message | Error Description |
---|---|---|
01 | "SENSOR ERROR" | Open temperature sensor circuit |
02 | Shorted temperature sensor circuit | |
03 | "EEPROM ERROR" | Error in permanent memory |
06 | "REMOTE SENSOR ERROR" | Open remote temperature sensor circuit |
07 | Shorted remote temperature sensor circuit | |
08 | "SUPPORT MODULES LOST" | All support modules with controlling temperature sensors are in error |
Thermostat Features
- Remote access and control over Wi-Fi.
- Indoor air quality control: Humidification (automatic or manual), Dehumidification, Event-Based™ air cleaning, Ventilation with temperature and humidity limits.
- Temperature control.
- Heat Blast® raises the room temperature 3°F to 5°F.
- Large touch screen with adjustable backlight - constant backlight option available.
- Message center provides feedback and instructions.
- 7-day programmability.
- Displays room temperature, room humidity, temperature setting, and outdoor temperature.
- Air filter, humidifier, dehumidifier, fresh air, and HVAC service reminders.
- Programmable fan control with fan circulation mode.
- Easy to use temperature control can override program schedule at any time.
- Progressive recovery ensures proper temperature at the start of a program event.
- Built-in compressor protection prevents damage to your equipment.
- System test mode.
Specifications
Category | Specification |
---|---|
Environment | Operating: 32° to 120°F (0° to 48.9°C) Shipping: -30° to 150°F (-34.4° to 65.5°C) |
Relative humidity | Operating: 5% to 90% R.H. (non-condensing) |
Electrical | Operating voltage: 24VAC (18-30VAC) |
Current | Maximum: 2.5A (total), 1.0A (single output) Maximum surge current: 5A |
Thermal | Outdoor & Remote temperature sensor: Maximum distance: 300 feet |
Room temperature measurement | Display range: 32° to 99°F (0° to 40°C) |
Outdoor temperature measurement | Display range: -40° to 130°F (-40° to 55°C) |
Setpoint temperature range | Heat: 40° to 90°F (4° to 32°C) Cool: 50° to 99°F (10° to 37°C) |
Setpoint humidity range | Humidification: 10% to 50% R.H. Dehumidification: 40% to 90% R.H. |