Aprilaire Model 8820 Touch Screen Wi-Fi Automation Thermostat

Safety & Installation Instructions

Wi-Fi Setup

To connect the 8820 thermostat to a Wi-Fi network, follow these steps. You will need a computer or mobile device with Wi-Fi and a web browser.

Step 1: Verify the thermostat is in Wi-Fi Connection Mode

The thermostat defaults to Wi-Fi Connection Mode. Confirm this by checking for strobing radio bars on the thermostat display.

If the thermostat is not in Wi-Fi Connection Mode, refer to the Owner's Manual for instructions on clearing Wi-Fi settings.

Step 2: Connect to the thermostat using a computer or mobile device

On your computer or mobile device, scan for available networks. The thermostat should appear as APRILAIRE8820 followed by a unique identifier (last 6 digits of the MAC address). Connect to the thermostat you wish to configure.

If installing multiple thermostats, the MAC address for each will be displayed in the message center. The MAC address can also be found by removing the front cover.

Step 3: Configure the thermostat to connect to the Wi-Fi network

Open a web browser on your computer or mobile device and enter: http://192.168.1.99/index.html

In the web browser interface, select the desired network and enter its security credentials.

Step 4: Verify the thermostat is connected to the Wi-Fi network

After entering the required information, the thermostat will connect to the selected Wi-Fi network. The radio bars will then display the Wi-Fi signal strength. If signal strength is not displayed, refer to "Troubleshooting Wi-Fi Connection" on page 22.

If not using a home automation system and instead using an Aprilaire account, set "Automation Enable" to "Aprilaire Cloud" in the installer setup menu (pages 8 & 9). Visit my.aprilaire.com for the Wi-Fi Thermostat App User Guide and startup instructions.

Installation

Installation Location Recommendations

Thermostat should be mounted:

Do not mount thermostat:

Outdoor Temperature Sensor (Included)

The included 8052 sensor can be attached to terminals S1 and S2 to measure outdoor temperature. This sensor must be enabled in the installer setup menu.

Heat pump models can use outdoor temperature for effective heat pump utilization:

Indoor Air Quality functions can use the outdoor temperature sensor for:

Outdoor temperature sensor should be mounted:

Wiring Terminal Diagram Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Remote Temperature Sensor (Optional)

An optional 8051 flush mount or 8053 surface mount remote temperature sensor can be attached to terminals T1 and T2. This sensor can be used to control a large space by averaging with the thermostat's internal sensor or overriding it, based on installer setup menu settings.

Remote temperature sensor should be mounted:

Do not mount remote sensor:

Wiring Terminal Diagram Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Thermostat Mounting

  1. Remove the rear mounting plate from the thermostat.
  2. Pull wires through the opening on the back of the rear mounting plate.
  3. Position and level the mounting plate on the wall and mark hole locations.
  4. Drill 1/4" holes and insert supplied anchors (for drywall).
  5. Place mounting plate over anchors, insert and tighten screws.
  6. Seal wire entry holes to prevent drafts affecting temperature readings.

Power & Reset Options

The thermostat is powered by 24VAC. It maintains the clock for 24 hours during power loss and has a memory backup for settings. The reset button (under the front cover) can reset the thermostat to factory defaults, including Installer System Settings.

[RESET BUTTON Icon]

Wiring Terminal

Wire specifications: 18-24 gauge thermostat wire.

Installation notes:

Terminal Descriptions:

¹Jumper between RC & R is used in single transformer systems (see wiring diagrams).

Wiring Terminal Diagram Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Wiring Diagrams

The following diagrams illustrate typical wiring configurations. Refer to individual equipment manuals for specific details.

Conventional Heat/Cool Wiring Diagrams

Single Transformer (Use Jumper Wire)

Diagram shows connections for 1st Cooling, 2nd Cooling, Fan, Cooling Transformer, 1st Heating, 2nd Heating, Heating Transformer, Remote Temp Sensor, Outdoor Temp Sensor, Not Used terminals.

Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Two Transformers (Remove Jumper Wire)

Diagram shows connections for 1st Cooling, 2nd Cooling, Fan, Cooling Transformer, 1st Heating, 2nd Heating, Heating Transformer, Remote Temp Sensor, Outdoor Temp Sensor, Not Used terminals.

Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Heat Pump Wiring Diagrams

Single Transformer (Use Jumper Wire)

Diagram shows connections for Reversing Valve, 1st Compressor, 2nd Compressor, Fan, Transformer, 2nd Aux Heating, 1st Aux Heating, Fault Detect, Outdoor Temp Sensor, Remote Temp Sensor, Not Used terminals.

Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Two Transformers (Remove Jumper Wire)

Diagram shows connections for Reversing Valve, 1st Compressor, 2nd Compressor, Fan, Transformer, 2nd Aux Heating, 1st Aux Heating, Fault Detect, Outdoor Temp Sensor, Remote Temp Sensor, Not Used terminals.

Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Indoor Air Quality Equipment Wiring Diagrams

Dehumidifier Wiring

Diagram shows connection for Dehumidifier Transformer and terminals RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2.

Note: The I1/I2 output is a dry contact closure. The dehumidifier wiring diagram is for a normally open dry contact input.

Humidifier Wiring

Diagram shows connection for Humidifier Transformer and terminals RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2.

Note: The humidifier wiring diagram assumes the control is powering a solenoid valve.

Ventilation Wiring

Diagram shows connection for Normally Closed Damper Transformer and terminals RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2.

Note: The ventilation diagram assumes the control is for a normally closed damper.

Refer to individual humidifier, dehumidifier, or ventilation installation instructions for product-specific wiring details.

Support Module Wiring Diagram

Diagram shows connections for Model 8081 or 8082 Support Module with terminals RC, C, RSB, RSA, T1, T2, T3, T4.

Note: Up to four Support Modules can be wired to the thermostat. Use CAT-5 wire. Total wire length for all support modules should not exceed 1000 feet.

Terminal Reference: RSB RSA I2 C I1 O/B Y Y2 G RC R W2 W L S2 S1 T1 T2

Setup & Testing

Equipment Type Selection Switch (SW1)

This thermostat supports heat pump or heat/cool systems. Switch SW1, located on the back of the thermostat face, selects this option. This setting is displayed in the Installer System Settings under "Equipment Type".

SW1 positions: HEAT/COOL, HEAT PUMP.

Installer Setup Menu

How to Enter the Installer Setup Menu and Select Equipment to Setup:

  1. Press [MODE] to set the system to OFF.
  2. Press [MENU] to enter the main menu.
  3. Press and hold [SETUP] for seven seconds until [INSTALL SETUP] appears.
  4. Press [INSTALL SETUP] to enter the installer setup menu.

In the Installer Setup menu, you can select Thermostat or Indoor Air Quality (IAQ) setup. For IAQ setup, you can then choose to configure Air Cleaning, Humidification, Dehumidification, or Ventilation.

Use [NEXT] or [BACK] to navigate settings. Use [UP ARROW] or [DOWN ARROW] to adjust options. Press [MENU] to exit. Press [DONE] to save and exit, or [CANCEL] to exit without saving.

If IAQ setup is selected first, the Installer System Setting for Outdoor Sensor will be presented before entering IAQ setup.

To reset Installer System Settings to defaults, press the [RESET] button for 5 seconds.

Change System Settings

Press [NEXT] or [BACK] to page through settings. Press [UP ARROW] or [DOWN ARROW] to adjust the setting.

Thermostat Installer System Settings Table

System settingDescriptionFactory default setting (bold) and setting range
00. Automation EnableSelects if the thermostat connects with an automation system or an Aprilaire account.0: Aprilaire Cloud
1: Automation System
01. Equipment TypeEquipment type set by SW1.Heat/Cool
Heat Pump
02. Temperature ScaleSet the thermostat to Fahrenheit or Celsius mode.Fahrenheit
Celsius
03. Reversing ValveSelects O or B operation.0 - On in cooling
B - On in heating
04. Control SetupUsed to lockout heating or cooling outputs. Note: Only available if Equipment Type is set to Heat/Cool.Heat and Cool
Heat Only
Cool Only
05. Heat/Cool: Cooling Stages
Heat Pump: Compressor Stages
Heat/Cool: Number of Cooling Stages.
Heat Pump: Number of Compressor Stages.
One
Two
06. Heat/Cool: Heating Stages
Heat Pump: Aux Heat Stages
Heat/Cool: Number of Heat Stages.
Heat Pump: Number of Auxiliary Heat Stages.
One
Two
07. Heat/Cool: Fan Control in Heating
Heat Pump: Auxiliary Equipment Type
Heat/Cool: Determines if the thermostat or equipment controls the fan in heating.
Heat Pump: Auxiliary Equipment type.
Gas/Oil Heat (equipment controls fan)
Electric Heat (thermostat controls fan)
08. Extended Fan - HeatExtends fan operation after heat call ends.Disable
Enable (90 second extension)
09. Extended Fan - CoolExtends fan operation after cool call ends.Disable
Enable (90 second extension)
10. Temperature Sensor OffsetField adjustment of controlling temperature sensor(s).0° (no offset applied)
-4°F to +4°F (-2°C to +2°C)
11. Humidity OffsetField adjustment of internal RH sensor.0 (no offset applied)
-5% to +5%
12. Auto ChangeoverEnable or disable Auto Changeover mode.Disable
Enable
13. DeadbandAuto Changeover mode deadband.3°F (1.5°C)
2°F to 9°F (1°C to 4.5°C)
14. Remote SensorSelect if remote sensor is attached, and if it is attached, if it is the primary control or averaged with the built-in sensor. If the remote sensor is the primary control it can be configured to use the built-in sensor as a back-up sensor.Not installed
Control no backup
Control with built-in backup
Average with thermostat built-in sensor
15. Outdoor SensorSelects if an outdoor temperature sensor is not installed, a wired sensor is installed, or the outdoor temperature is provided by the automation system. Note: Automation is only available if Automation Enable is set to Automation System.Not installed
Installed
Automation
18. Compressor Min Off TimeMinimum off time for compressor protection.5 minutes
1 to 5 minutes
19. Heating Min Off TimeMinimum off time for heating.2 minutes
1 to 5 minutes
20. Equipment Min On TimeMinimum on time for heating and cooling.2 minutes
1 to 5 minutes
21. Auto Changeover TimeMinimum time between heating and cooling calls.4 minutes
1 to 5 minutes
22. First Stage DifferentialFirst stage differential.1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
23. Second Stage DifferentialSecond stage differential.1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
24. Third Stage DifferentialThird stage differential.1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
25. Fourth Stage DifferentialFourth stage differential.1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
26. AwayEnables the Away feature. The Away feature allows the automation system or Aprilaire mobile and web apps to use a single button press to set the thermostat to a predefined setpoint(s). The thermostat will hold the setpoint(s) until Away is canceled with the automation system or app or at the thermostat.Disable
Enable
27. Heat BlastEnables the Heat Blast feature.Disable
Enable
28. Blast OffsetAmount of heating when Heat Blast is initiated.3°F (1.5°C)
3°F to 5°F (1.5°C to 2.5°C)
37. Stage RateAccumulation of equipment run time in equipment staging determination. 1 = more rapid staging of equipment (comfort). 5 = slower staging of equipment (economy).2
1 to 5 or "OFF" to ignore accumulated run time.
38. Progressive RecoveryEnable or disable progressive recovery.Disable
Enable
39. Low Balance PointOutdoor temperature low balance point. Note: This option is only available if the thermostat is set to Heat Pump and Outdoor Sensor is set to Installed or Automation.20°F or -8°C
0°F to 60°F (-18°C to 12°C) or OFF to ignore LBP
40. High Balance PointOutdoor temperature high balance point. Note: This option is only available if the thermostat is set to Heat Pump and Outdoor Sensor is set to Installed or Automation.65°F or 14.5°C
0°F to 80°F (-18°C to 22°C) or OFF to ignore HBP
41. Program FormatEnables the 7-day program.7-Day
Non-Prog
42. Reset Service RemindersClears the Air Filter, Dehumidifier, Fresh Air, and HVAC service reminders if they are active and resets the start date to the current date. Clears the Change Water Panel reminder if it is active. If the reminder is set to Timed, the clock will be reset.No
Yes
43. HVAC Service ReminderThe period for displaying the "HVAC Service Reminder" message.Off
1 to 12 months or "Off" to disable
44. Constant BacklightEnable constant, low intensity backlight.Disable
Enable
45. Backlight IntensitySet the active backlight intensity. Note: The minimum setting is 40% when Constant Backlight is enabled.100 Percent
0 to 100 Percent
51. Support Module Controlling Temp SensorsSets the number of controlling support module temperature sensors.NONE
1 to 8
52. Support Module Controlling RH SensorsSets the number of controlling support module humidity sensors.NONE
1 to 4
53. Display Monitor Support Module SensorSelects if the temperature or humidity values from support modules that are configured for monitoring are displayed in the message center of the thermostat.No
Yes

Indoor Air Quality System Settings Tables

The following tables contain the Indoor Air Quality system settings and their details. Default settings are shown in bold. Some settings are only present dependent upon the value of other settings. The use of the included outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality. If the outdoor temperature sensor was not enabled in the thermostat system settings, thermostat system setting 15, outdoor sensor, will be presented prior to entering the Indoor Air Quality system settings. Please refer to the Model 8820 Owner's Manual for further information about thermostat features.

Air Cleaning System Settings Table

System settingDescriptionFactory default setting (bold) and setting range
Air Cleaner InstalledSelects if an air cleaner is installed. (If set to no, no other air cleaning settings will be available.)No
Yes
Change Air Filter ReminderThe period for displaying the "Change Air Filter" message.Off
1 to 12 months or "Off" to disable

Humidifier System Settings Table

Note: A humidifier can only be installed if ventilation is not installed and Dehumidifier Control is not set to Whole Home or AC w/IAQ Output.

System settingDescriptionFactory default setting (bold) and setting range
Humidifier InstalledSelects if a humidifier is installed. Yes/On HVAC is used for applications where the humidifier is installed on the HVAC duct. Yes/Standalone is used for application where the humidifier is independent of the HVAC system. (If set to no, no other humidifier settings will be available.)No
Yes/On HVAC
Yes/Standalone
Humidifier ModeSelects auto or manual mode. Auto mode controls humidity based on the humidity setting and outdoor temperature. Manual mode controls humidity based on the %RH setpoint. (Auto mode is only available if outdoor sensor is set to Installed or Automation.)Auto
Manual
Humidity Setpoint DeadbandSelects the minimum difference between the humidifier and dehumidifier setpoints. (Only available if a humidifier is installed and dehumidifier control is set to air conditioner. Available in both set-ups.)10 Percent RH
10 to 20 Percent RH
Humidifier OperationSelects when humidification is allowed to occur relative to heating and fan operation. Without Fan allows humidification to occur without the HVAC fan. This option should only be used when the humidifier is independent of the HVAC system. Note: Without Fan is only available when Humidifier Installed is set to Yes/Standalone.Heat Only
Heat or Fan
Forces Fan
Without Fan

CAUTION: When Humidifier Operation is set to Without Fan the thermostat will turn on humidification without energizing the HVAC fan. Do not select this option when the humidifier is installed on the HVAC duct. Without airflow moisture can accumulate in the duct resulting in significant damage.

Change Water Panel ReminderSelects the when the "Change Water Panel" message is displayed.Off
1 Per Season
2 Per Season
300 Hours
600 Hours
Reminder Month (Change Water Panel Reminder set to 1 per Season)Change Water Panel Reminder set to 1 per Season: Determines the month the "Change Water Panel" message is displayed.October
November
December
January
February
March
April
May
June
July
August
September
First Reminder Month (Change Water Panel Reminder set to 2 per Season)Change Water Panel Reminder set to 2 per Season: Determines the first month the "Change Water Panel" message is displayed.October
November
December
January
February
March
April
May
June
July
August
September
Second Reminder Start MonthDetermines the second month the "Change Water Panel" message is displayed. (Only available when Change Water Panel Reminder set to 2 per Season.)October
November
December
January
February
March
April
May
June
July
August
September

Dehumidifier System Settings Table

Note: Dehumidifier Control can only be set to Whole Home or AC w/IAQ Output if ventilation and humidification are not installed.

System settingDescriptionFactory default setting (bold) and setting range
Dehumidifier ControlSelects method of dehumidification. If set to None, no other dehumidifier settings will be available. If dehumidification is done with the air conditioner, using the option of AC w/IAQ Output will cause the IAQ output to be active when overcooling for dehumidification. This can be used if the HVAC equipment has a dedicated input to slow the fan during cooling to maximize dehumidification.None (no dehumidification installed)
Whole Home
Air Conditioner
AC w/IAQ Output
Humidity Setpoint DeadbandSelect the minimum difference between the humidifier and dehumidifier setpoints. (Only available if a humidifier is installed and Dehumidifier Control is set to Air Conditioner. Available in both set-ups.)10 Percent RH
10 to 20 Percent RH
Lockout Dehumidifier During CoolingSelects if dehumidification is disabled during a cooling call. (Only available if Dehumidifier Control is set to Whole Home.)No
Yes
Dehumidifier Forces FanSelect if dehumidification can turn on the fan. (Only available if Dehumidifier Control is set to Whole Home.)No
Yes
Dehumidifier Service ReminderThe period for displaying the "Dehum Service Reminder" message. (Only available if Dehumidifier Control is set to Whole Home.)Off
1 to 12 months or "Off" to disable
Dehumidifier Overcooling LimitSelects the amount of overcooling that can occur for dehumidification. (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output.)3°F (1.5°C)
1°F to 3°F (0.5°C to 1.5°C)
Dehumidify in Vacation ModeSelects if dehumidification with the air conditioner is done in Vacation Mode. (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output.No
Yes
Vacation Dehumidifier Low Temp LimitSets the lowest temperature the air conditioner will cool to, to meet RH setpoint in Vacation Mode. (Only available if Dehumidifier Control is set to Air Conditioner or AC w/IAQ Output.)75°F (23.5°C)
70°F to 85°F (21°C to 28.5°C)

Ventilation System Settings Table

Note: Ventilation can only be installed if humidification is not installed and Dehumidifier Control is not set to Whole Home or AC w/IAQ Output.

System settingDescriptionFactory default setting (bold) and setting range
Fresh Air Vent InstalledSelects if ventilation is installed. (If set to No, no other ventilation settings will be available.)No
Yes
Fresh Air Setup TypeSelects if ventilation is configured through the Code setup or Comfort. Comfort setup has more lockout options. Code setting ensures missed lockout time is made up.Comfort
Code
Number of BedroomsSelects the number of bedrooms to be used for the Calculated Minutes per Hour.3 Bedrooms
1 to 10 Bedrooms
Home SizeSelects the size of the home to be used for the Calculated Minutes per Hour.2500 SQ FT
500 to 7500 SQ FT
Measured CFMSelects the ventilation CFM to be used for the Calculated Minutes per Hour.110 CFM
30 to 250 CFM
Calculated Minutes per HourDisplays the Fresh Air Time calculated.None
Range 6 to 60 Minutes
OverrideManual adjustment of Calculated Minutes per Hour.(Calculated Minutes per Hour)
Range 6 to 60 Minutes
Enable High Vent RH LimitSelects if ventilation is disabled if the indoor RH exceeds the indoor RH limit. (Only available if Fresh Air Setup is set to Comfort.)Yes
No
High Vent RH LimitSets the ventilation indoor RH lockout limit. (Only available if Enable High Vent RH Limit is set to Yes.)55%
45% to 70%
Enable Low Vent RH LimitSelects if ventilation is disabled if the indoor RH exceeds the indoor RH limit. (Only available if Fresh Air Setup is set to Comfort.)No
Yes
Low Vent RH LimitSets the ventilation indoor RH lockout limit. (Only available if Enable Low Vent RH Limit is set to Yes.)20%
10% to 30%
Enable High Vent Temperature LimitEnables high ventilation temperature lockout limit. (Only available if Outdoor Sensor is set to Installed or Automation.)No
Yes
High Vent Temperature LimitSets high ventilation temperature lockout limit. (Only available if Enable High Vent Temperature Limit is set to Yes.)100°F (38°C)
85°F to 105°F (29°C to 41°C)
Enable Low Vent Temperature LimitEnables low ventilation temperature lockout limit. (Only available if Outdoor Sensor is set to Installed or Automation.)No
Yes
Low Vent Temperature LimitSets low ventilation temperature lockout limit. (Only available if Enable Low Vent Temperature Limit is set to Yes.)10°F (-12°C)
-10°F to 40°F (-24°C to 6°C)
HVAC Fan with VentSelects if ventilation forces the fan on. (Yes with high and low limits is only available if Outdoor Sensor is set to Installed or Automation.)Yes
Yes with high and low limits
Enable High Mixing TemperatureEnables high mixing temperature. (Only available is HVAC Fan with Vent is set to Yes with high and low limits.)No
Yes
High Mixing TemperatureSets the high mixing temperature. (Only available if Enable High Mixing Temperature is set to Yes.)80°F or (26°C)
60°F to 105°F (14°C to 41°C)
Enable Low Mixing TemperatureEnables low mixing temperature. (Only available is HVAC Fan with Vent is set to Yes with high and low limits.)No
Yes
Low Mixing TemperatureSets the Low mixing temperature. (Only available if Enable Low Mixing Temperature is set to Yes.)40°F (6°C)
0°F to 50°F (-18°C to 12°C)
Fresh Air Service ReminderThe period for displaying the "SERVICE FRESH AIR" message.OFF
1 to 12 months or "OFF" to disable

Refer to manuals for humidifier, dehumidifier, air cleaner, and ventilation products for recommended installation and operation.

Removal of Indoor Air Quality Control Buttons

If any Indoor Air Quality control features are not installed, the corresponding button can be removed using the following procedure:

  1. Verify the specific Indoor Air Quality control feature is not installed in the Installer System Settings (see pages 11-14).
  2. From the home screen (see page 20), press and hold the Indoor Air Quality button you wish to remove for 7 seconds.
  3. The message center will display REMOVE BUTTON and the options of NO and YES (NO will be flashing).
  4. Press [UP ARROW] or [DOWN ARROW] to select YES.
  5. Press [DONE].
  6. The button is now removed.

Once the button is removed, it can be brought back by installing the corresponding Indoor Air Quality feature (see pages 11-14).

System Test Menu

The system test menu is used to test a system after installation. The thermostat's outputs can be manually activated to test their function. The instructions below show how to enter the test mode and turn outputs on and off.

How to Enter the System Test Menu:

  1. Press [MODE] to set the system to off.
  2. Press and hold [FAN] and [MODE] for three seconds to enter system test mode.
  3. The first screen of the installer test displays the equipment configuration.
  4. Press [NEXT] to enter the first installation test or [CANCEL] to exit.

System Test Steps: Heating equipment test, Cooling equipment test, Fan equipment test, Humidification equipment test, Dehumidification equipment test, Ventilation equipment test.

System Test Menu (Continued)

Each equipment test begins with selecting the output or stage to turn on. Press [UP ARROW] or [DOWN ARROW] to change the selection. Press [NEXT] to accept the selection and proceed to the next step. If YES is selected, the thermostat will test the corresponding output. If NO is selected, the thermostat will proceed to the next step.

While the equipment test is active, the corresponding test information will be shown. Press [NEXT] to accept the selection and proceed to the next test selection.

System Test Tables

Heat / Cool Heating Equipment Test

Heat TypeWW2YY2G
Gas1st Stage TestONON
Gas2nd Stage TestONONON
Electric1st Stage TestONON
Electric2nd Stage TestONONON

Heat Pump Heating Equipment Test (Electric Heat)

Compressor StagesAux StagesO/B set toWW2YY2G
111st Stage TestONONONON
112nd Stage TestONONONONON
211st Stage TestONONONON
212nd Stage TestONONONONON
213rd Stage TestONONONONON
121st Stage TestONONONON
122nd Stage TestONONONONON
123rd Stage TestONONONONON
221st Stage TestONONONON
222nd Stage TestONONONONON
223rd Stage TestONONONONON
224th Stage TestONONONONON

Note: System Variable 03, O/B operation selects O or B.

Heat Pump Heating Equipment Test (Gas Heat)

Compressor StagesAux StagesO/B set toWW2YY2G
111st Stage TestONONONON
112nd Stage TestONONONONON
211st Stage TestONONONON
212nd Stage TestONONONONON
213rd Stage TestONONONONON
121st Stage TestONONONON
122nd Stage TestONONONONON
123rd Stage TestONONONONON
221st Stage TestONONONON
222nd Stage TestONONONONON
223rd Stage TestONONONONON
224th Stage TestONONONONON

Note: System Variable 03, O/B operation selects O or B.

Heat / Cool Cooling Equipment Test

WW2YY2G
1st Stage TestONONON
2nd Stage TestONONONONON

Heat Pump Cooling Equipment Test

O/B set toWW2YY2G
1st Stage TestOONONON
1st Stage TestBONONON
2nd Stage TestOONONONONON
2nd Stage TestBONONONONON

Note: System Variable 03, O/B operation selects O or B.

Fan Equipment Test

WW2YY2G
ONON

Humidification Equipment Test

I1/I2G
ONON

Dehumidification Equipment Test

I1/I2G
ONON

Ventilation Equipment Test

I1/I2G
ONON

Quick Reference to Controls & Display

Home Screen

Displays:

Note: Backlight is activated with the first button press and automatically turns off.

Main Menu

Accessed via the [MAIN MENU] button. Options include:

Troubleshooting

Display is Blank

Temperature Settings Do Not Change

Ensure heating and cooling temperatures are set to acceptable ranges:

Heating System Does Not Respond ("HEATING" Appears on Screen)

Cooling System Does Not Respond ("COOLING" Appears on Screen)

Fan Does Not Turn On in a Call for Heat

Heat Pump Issues Cool Air in Heat Mode, or Warm Air in Cool Mode

Heat/Cool Both On at Same Time

Heating Equipment is Running in Cool Mode

"HEATING" Is Not Displayed

"COOLING" Is Not Displayed

Humidifier Does Not Operate in Auto Mode

Troubleshooting Wi-Fi Connection

The Wi-Fi connection status is communicated via the radio strength indicator and the message center. The table below describes various statuses, messages, and radio bar displays.

Wi-Fi connection statusRadio status indicatorMessage Center
Normal Operation.Wi-Fi signal strength indicated by the number of bars.No corresponding message
The thermostat Wi-Fi settings have not been entered. Refer to Wi-Fi Setup on page 2 for instructions for entering the Wi-Fi settings.The frame is displayed and the bars cycle from 0 to 4.Displays the SSID of the thermostat. Note: The SSID will be used to identify the thermostat when using a smart device to connect the thermostat to your Wi-Fi router.
The thermostat cannot connect to the Wi-Fi router. Verify that the router is functioning properly.The frame and all bars flash on and off.WiFi Connection Lost
Indicates the thermostat was not configured properly when connecting to the router. Confirm there is no IP conflict and repeat Wi-Fi setup. Note: If the thermostat is configured to work with an Aprilaire account this indicates that the thermostat cannot connect to the Aprilaire Cloud. Confirm that the internet connection is working.The display will alternate between displaying the frame and all bars.Internet Connection Lost
There is an internal error with the thermostat Wi-Fi radio. The thermostat will continue to control the HVAC and indoor air quality control equipment, but will not be able to connect to Wi-Fi. Contact an HVAC professional for repair.The frame will flash on and off.Radio Error
Wi-Fi radio turned off. Refer to the Accessing Wi-Fi Settings Menu in the Owner's Manual for information about turning the Wi-Fi radio on.Not displayed.WiFi Turned Off

Error Codes

If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to recover every 10 minutes.

Error codeMessageError Description
01"SENSOR ERROR"Open temperature sensor circuit
02Shorted temperature sensor circuit
03"EEPROM ERROR"Error in permanent memory
06"REMOTE SENSOR ERROR"Open remote temperature sensor circuit
07Shorted remote temperature sensor circuit
08"SUPPORT MODULES LOST"All support modules with controlling temperature sensors are in error

Thermostat Features

Specifications

CategorySpecification
EnvironmentOperating: 32° to 120°F (0° to 48.9°C)
Shipping: -30° to 150°F (-34.4° to 65.5°C)
Relative humidityOperating: 5% to 90% R.H. (non-condensing)
ElectricalOperating voltage: 24VAC (18-30VAC)
CurrentMaximum: 2.5A (total), 1.0A (single output)
Maximum surge current: 5A
ThermalOutdoor & Remote temperature sensor: Maximum distance: 300 feet
Room temperature measurementDisplay range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurementDisplay range: -40° to 130°F (-40° to 55°C)
Setpoint temperature rangeHeat: 40° to 90°F (4° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Setpoint humidity rangeHumidification: 10% to 50% R.H.
Dehumidification: 40% to 90% R.H.

PDF preview unavailable. Download the PDF instead.

aprilaire-touchscreen-wi-fi-install-instructions-126281 Adobe PDF Library 15.0 Adobe InDesign CC 2017 (Macintosh)

Related Documents

Preview Aprilaire Product Specifications Quick Reference Guide
Comprehensive quick reference guide for Aprilaire HVAC products including humidifiers, dehumidifiers, air cleaners, ventilation systems, thermostats, zone controls, and dampers. Find product specifications, sizing guidelines, and application information.
Preview Aprilaire Wi-Fi Thermostats with IAQ Control - Smart Home Comfort Solutions
Explore Aprilaire's line of Wi-Fi thermostats offering advanced IAQ control, energy savings, and smart home integration. Learn about features, models, and benefits for homeowners and HVAC professionals.
Preview Aprilaire Model 8920W Wi-Fi Indoor Air Quality Thermostat Owner's Manual
This owner's manual provides comprehensive instructions for setting up, operating, and troubleshooting the Aprilaire Model 8920W Wi-Fi Indoor Air Quality Thermostat. Learn about features like remote access, indoor air quality control, scheduling, and more.
Preview Aprilaire Model 8910W Home Comfort Control with Wi-Fi: Owner's Manual
This owner's manual provides comprehensive instructions for operating and maintaining the Aprilaire Model 8910W Home Comfort Control with Wi-Fi. It covers setup, system modes, indoor air quality functions, scheduling, Wi-Fi connectivity, troubleshooting, and warranty information.
Preview AprilAire S86N MU/MUPR Thermostat Safety & Installation Instructions
Comprehensive safety and installation guide for AprilAire S86N MU and S86N MUPR Multi-Stage Universal Thermostats, detailing installation, wiring, setup, testing, troubleshooting, features, and specifications.
Preview Aprilaire Wi-Fi Thermostats with IAQ Control: Smart Home Comfort & Air Quality
Explore Aprilaire's advanced Wi-Fi thermostats offering intuitive control over temperature, humidity, air purity, and fresh air. Enhance home comfort, energy savings, and indoor air quality with smart features and easy app management. View product portfolio and specifications.
Preview AprilAire S86 SKU Transitions: Thermostat Model Comparison
Explore the transition of AprilAire thermostat SKUs, comparing existing models like 8620 with the new S86NMU, S86NMUPR, and S86WMUPR series, detailing features, stages, and connectivity.
Preview Aprilaire Wi-Fi IAQ Control Product Portfolio
Explore the Aprilaire Wi-Fi IAQ Control product portfolio, featuring advanced thermostats designed for comprehensive home comfort and air quality management. Compare models like 8920W, 8910W, 8620W, and 8476W with detailed feature breakdowns and a full line comparison.