Quick Start Guide: XID and XIB Isolator Mounting
ACCUREX
XID Mixed Flow Fan - Isolator Mounting
Instructions for positioning and mounting XID mixed flow fans using isolators.
- Move the XID mixed flow fan to the desired location and determine the mounting position.
- For horizontal mount applications (excluding neoprene), mount the isolators directly to the fan.
- For neoprene and vertical mount applications, use supplied brackets.
- Ensure all fasteners are tight and all washers are used.
This Quick Start Guide is supplementary and does not replace the Installation Operation Manual (IOM). Refer to the IOM for comprehensive information.
Vibration Isolator Dimensional Data (XID Mixed Flow)
Model | A | B | C |
---|---|---|---|
XID-7 | 12 | 13-1/8 | 19-3/4 |
XID-9 | 14 | 16-7/8 | 23-1/2 |
XID-12 | 17-1/2 | 20 | 26-5/8 |
XID-15 | 22 | 23-3/4 | 30-3/8 |
XID-16 | 23 | 25-3/4 | 32-3/8 |
XID-18 | 24-1/8 | 28-3/8 | 35 |
XID-20 | 26-5/8 | 31 | 37-5/8 |
XID-22 | 29-1/2 | 33-3/4 | 40-3/8 |
XID-24 | 33 | 37-1/4 | 43-7/8 |
XID-27 | 36-1/2 | 40-3/4 | 47-3/8 |
XID-30 | 40-1/2 | 44-3/4 | 51-3/8 |
XID-33 | 44-3/4 | 49 | 55-5/8 |
All dimensions are in inches.
Mounting Type Diagrams
Horizontal Mount: Depicts a fan unit mounted directly on isolators, showing dimensions A and B.
Horizontal Hanging Neoprene Mount: Depicts a fan unit with neoprene isolators mounted below, showing dimensions A, B, and C.
Vertical Mount: Depicts a fan unit mounted vertically with isolators, showing dimensions A, B, and C. Includes diameter indicators ∅0.50 in. and ∅1.25 in.
Isolator Sizing for All XID and XIB Fans
Isolators are selected based on the specific fan's weight. For replacement or retrofit isolators where the fan weight is unknown, use the chart below to determine the appropriate isolator color and kit part number.
Model Type to Weight Range Mapping
Model Type | Weight Range |
---|---|
XID Mixed Flow | 0-150 lbs |
XID Centrifugal | 150-300 lbs |
XIB Centrifugal | 300-500 lbs |
Isolator Part Numbers by Weight Range
Isolator Type | 0-150 lbs | 150-300 lbs | 300-500 lbs | 500-700 lbs | 700-1200 lbs |
---|---|---|---|---|---|
Spring Hanging 1" | 850343 | 850344 | 850345 | 850346 | |
Spring Hanging 2" | 855858 | 855859 | 855860 | 855861 | |
Spring Base Mount | 850347 | 850348 | 850349 | 850350 | |
Neoprene Hanging | 855837 | 855838 | |||
Neoprene Base Mount | 855834 | 855835 | 855836 |
XID and XIB Centrifugal Fan - Isolator Mounting
Instructions for mounting XID and XIB centrifugal fans using isolators.
For centrifugal XID/XIB, punch out (4) knock-out holes which are located on the unit top and bottom panels.
Assemble the brackets to the unit according to the drawings shown and refer to respective parts list (reverse side).
Ensure all fasteners are tight and all washers are used.
This Quick Start Guide is supplementary and does not replace the Installation Operation Manual (IOM). Refer to the IOM for comprehensive information.
Vibration Isolator Dimensional Data (XID/XIB Centrifugal)
Model | A | B | C | D |
---|---|---|---|---|
XID-60, 70 | 10-5/8 | 16-3/4 | 14-5/8 | 8-7/8 |
XID-80, 90, 95 | 13-1/4 | 19-3/4 | 15-1/8 | 9-3/8 |
XID-97, 98, 99 | 18-5/8 | 19-3/4 | 15-1/8 | 9-3/8 |
XID-100 | 18-5/8 | 21-3/4 | 19-5/8 | 13-7/8 |
XID-120 | 18-5/8 | 23-3/4 | 21-5/8 | 15-7/8 |
XID-130 | 18-5/8 | 25-3/4 | 23-5/8 | 17-7/8 |
XID-140 | 19-5/8 | 27-3/4 | 25-5/8 | 19-7/8 |
XID-160 | 23-1/2 | 31 | 28-3/4 | 22-7/8 |
XIB-70, 80, 90, 100 | 18 | 21-7/8 | 19-7/8 | 14-1/8 |
XIB-120 | 18 | 23-7/8 | 21-7/8 | 16-1/8 |
XIB-130 | 18 | 25-7/8 | 23-7/8 | 18-1/8 |
XIB-140 | 19 | 27-7/8 | 25-7/8 | 20-1/8 |
XIB-160 | 23 | 31-1/8 | 29 | 23-1/8 |
XIB-180 | 25 | 32-1/8 | 30 | 24-1/8 |
XIB-200 | 29 | 36-1/8 | 34 | 28-1/8 |
XIB-240 | 31 | 43-1/8 | 41 | 35-1/8 |
XIB-300 | 35 | 51 | 46-3/4 | 40-7/8 |
XIB-360 | 39-3/8 | 57 | 52-5/8 | 46-3/4 |
XIB-420 | 47 | 63 | 58-5/8 | 52-3/4 |
All dimensions are in inches. High Pressure (HP) models share isolator dimensions with standard models.
Mounting Type Diagrams (Centrifugal)
Horizontal Mount: Depicts a unit with isolators at the corners, showing dimensions A and B.
Horizontal Side Mount: Depicts a unit with isolators on the sides, showing dimensions A, B, C, and D, with an "Access Panel" indicator.
Vertical Mount: Depicts a unit with isolators at the bottom, showing dimensions A, B, C, and D, with an "Access Panel" indicator.
Related Documents
![]() |
Accurex Kitchen Ventilation Systems: Comprehensive Product Catalog Accurex, a Greenheck Group Company, offers a complete range of high-quality kitchen ventilation systems, including exhaust hoods, fire suppression systems, utility distribution, controls, pollution control units, exhaust fans, make-up air units, and grease ducts. Engineered for simplicity, efficiency, and reliability, Accurex products meet diverse commercial kitchen needs. |
![]() |
Accurex 120 Honeywell Pilot Micro Quick Start Guide: Direct Gas Make-Up Air Unit Setup Comprehensive quick start guide for the Accurex 120 Honeywell Pilot Micro Direct Gas Make-Up Air unit. Learn essential steps for initial startup, configuration, and operation. |
![]() |
Accurex 120 Baso Terminal Strip Quick Start Guide Quick start guide for the Accurex 120 Baso Terminal Strip direct gas make-up air unit, covering pre-start checks, blower startup, and burner adjustments. Includes instructions for pressure differential, gas pressure, pilot flame signal, and firing rate settings. |
![]() |
Accurex Pilot Ignition ≤ 1200 mbh Quick Start Guide A quick start guide for Accurex Pilot Ignition Direct Gas Make-Up Air units with a capacity of ≤ 1200 mbh, covering pre-start information, wiring, and operational checks for initial unit startup. |
![]() |
Accurex XRV Packaged Rooftop Ventilator: Installation, Operation, and Maintenance Manual This comprehensive manual provides essential information for the safe and effective installation, operation, and maintenance of the Accurex XRV Packaged Rooftop Ventilator series. It covers safety precautions, product overview, installation guidelines, operation details, maintenance schedules, and troubleshooting tips for models XRV-20 through XRV-220. |
![]() |
Accurex Microprocessor Controller for Dedicated Outdoor Air System Reference Guide Accurex Microprocessor Controller for Dedicated Outdoor Air Systems (DOAS) Reference Guide. Learn about features, sequences, BMS communication, occupancy modes, alarms, and control variables for efficient HVAC management. Includes technical specifications and operational details. |
![]() |
Accurex RX Series Weighing Indicators User Manual User manual for the Accurex RX series weighing indicators, covering keypad functions, display status, calibration, A/D counts display, display mode selection, zeroing, tare functions, battery capacity, low battery warnings, and error codes. Applications include electronic platform scales and weighing scales. |
![]() |
Accurex XCR & XIR Ceiling and Inline Exhaust Fan Installation, Operation, and Maintenance Manual This manual provides detailed instructions for the installation, operation, and maintenance of Accurex XCR and XIR series ceiling and inline exhaust fans. It includes safety warnings, preparation steps, wiring guidance, conversion instructions, and maintenance tips. |