Accurex Model XCR and XIR Ceiling and Inline Fans

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.

Direct Drive Ceiling Exhaust Fan

Designed for clean air applications where low sound levels are required. Many options and accessories are available such as lights, motion detectors, ceiling radiation dampers and speed controls. Capacities range from 25 to 1,600 cfm (42 to 2,718 m³/hr) and 1 in. wg (248 Pa). AMCA Licensed for Sound and Air Performance.

Diagram: Illustration of a Direct Drive Ceiling Exhaust Fan unit.

Direct Drive Inline Exhaust Fans

Designed for clean air applications where low sound levels are required. Capacities range from 70 to 3,800 cfm (119 to 6,456 m³/hr) and 1 in. wg (248 Pa). AMCA Licensed for Air Performance.

Diagram: Illustration of a Direct Drive Inline Exhaust Fan unit.

WARNING!

To reduce the risk of fire, electric shock, or injury to persons, observe the following:

Visual: Warning symbol ❗

CAUTION!

For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

Visual: Caution symbol ⚠️

AVERTISSEMENT!

Pour réduire le risque d’incendie, de choc électrique ou de blessure corporelle, respecter cd qui suit:

Visual: Warning symbol ❗

Prepare the fan

Power Assembly

If power assembly (motor, wheel, and scroll) is not installed in housing, insert the electrical plug into fan socket, then slide scroll end of power assembly into fan housing. Attach by using two sheet metal screws provided.

Diagram: Exploded view of 'B Model' power assembly installation.

Diagram: Exploded view of 'A Model' power assembly installation.

Remove Wiring Knockout

Remove either top or side wiring knockout, depending on wiring direction, by bending it back and forth to break tabs.

Diagram: Illustration showing how to remove a wiring knockout by bending. Includes labels for 'Electrical Access Panel' and 'Knockouts'.

Ductwork

Check ductwork to see if the fan's discharge requires rotation from horizontal to vertical discharge.

Diagram: Shows two fan orientations for ductwork, indicating airflow direction.

Fan Rotation

To rotate from horizontal to vertical discharge (A Models Only)

A50-500, 710, 780 Models

Remove the two screws holding the power assembly in and pull power assembly out. Rotate power assembly 180 degrees and put back into fan. Use the same screws to reattach power assembly to fan housing. Flip fan over and remove the four screws holding the discharge duct and damper assembly. Exchange the assembly with plate mounted on top of fan, as shown in these illustrations.

Diagram: Shows steps for rotating the power assembly for A50-500, 710, 780 models.

A700, 900-1500 Models

Remove the eight screws holding the access panel or collar as shown in picture. Rotate the fan housing so the discharge is facing up. Replace access panel or collar and screws.

Diagram: Shows steps for rotating the fan housing for A700, 900-1500 models. Includes labels for 'Access Panel'.

Ceiling Radiation Damper (CRD)

If fan is to be used in a fire resistive membrane ceiling, a ceiling radiation damper must be used. If the ceiling radiation damper is already mounted to the fan from the factory, proceed to Install the Fan.

To mount the ceiling radiation damper to fan, make sure grille attachment tabs are facing down. Then place the inlet part of the fan into the ceiling radiation damper collar, and use self-tapping sheet metal screws (by others) to screw through the damper collar and into the fan housing. If the fan/light combination is being used, make sure ceiling radiation damper has an electrical plug in it. The electrical plug must be inserted into the fan. Make sure the electrical wire will not interfere with damper operation as shown in figure below.

Diagram: Shows CRD attachment for A50-510, 710, 780 Models, B Models, and A 700, 900-1550 Models. Includes labels for 'Attachment Tabs', 'Wires to ceiling fan', 'Wires from lighted grille', and a warning 'Do not allow interference in this area'.

Discharge Installation A50-90 Models

  1. Insert plastic duct tab into box slots.
    Diagram: Shows inserting a plastic duct tab into box slots. Includes labels for 'Box Slot', 'Plastic Duct Adapter Tabs'.
  2. Rotate plastic duct adapter (PN 473388) until the screw tabs meet the box.
    Diagram: Shows rotating a plastic duct adapter. Includes labels for 'Plastic Duct Adapter (PN 473388)', 'Box', 'Screw Tabs'.
  3. Install screws provided to secure discharge.
    Diagram: Shows installing screws into screw holes. Includes labels for 'Sheet Metal Screw #10x3/8 Phillips Head (PN 415838)', 'Box', 'Screw holes'.

Discharge Installation for Ceiling and Inline Exhaust Models Sizes B50-200

  1. Insert box scroll tab into box scroll slots.
    Diagram: Shows inserting a box scroll tab into box scroll slots. Includes labels for 'Box Scroll Tabs', 'Box Scroll Slots'.
  2. Rotate plastic duct adapter (PN 474433) until the two mounting tabs fully engage into the two box mounting slots.
    Diagram: Shows rotating a plastic duct adapter into box mounting slots. Includes labels for 'Box Mounting Tabs', 'Box Mounting Slots'.
  3. OPTIONAL: Align the pins on the TR 6x4 adaptor to the duct pin hole on the 6-inch duct. Push until the adaptor snaps into place.
    Diagram: Shows optional TR 6x4 adaptor installation. Includes labels for 'TR 6x4 Pin', 'TR 6x4 (PN 473324)', '6-inch Plastic Duct (PN 474433)', 'Plastic Duct Pin Hole'.

Install the Fan

  1. For best performance, choose a location with the shortest possible duct run and minimum number of elbows. Do not mount near cooking equipment, as shown in Fig. 1.
    Diagram: Fig. 1 shows a ceiling view with an area marked 'Do not install fan in this area' and indicates optimal placement for short duct runs and minimal elbows.
  2. Attach adjustable mounting brackets to fan, but leave the screws loose until proper height is determined, shown in Fig. 2. Cut hole to dimensions shown in table below:
    Diagram: Fig. 2 shows adjustable mounting brackets attached to a fan housing, with labels indicating 'Bottom Mount', 'Top Mount', and 'Slots in the brackets allow fine adjustment for flush fit with wall/ceiling opening'.

Ceiling Openings

SizesFan or Fan/LightFan/CRD
A50, A70, A90
A110, A125, A190
10⁷⁄₈ x 13³⁄₈11¹⁄₈ x 13⁷⁄₁₆
A200, A250, A290, A39012¹⁄₈ x 14¹⁄₄12¹⁄₄ x 14³⁄₈
A70023³⁄₄ x 11³⁄₄24¹⁄₈ x 12¹⁄₄
A410, A510, A710, A78014³⁄₄ x 18³⁄₈14⁷⁄₈ x 18⁷⁄₁₆
A900, A1050, A1410, A155014³⁄₄ x 2414⁷⁄₈ x 24¹⁄₈
B50 - 20014¹⁄₈ x 11³⁄₄14³⁄₈ x 12¹⁄₄

NOTE: Model A50-90 are standard with a round duct. Should Model A110-190 require a round duct, Model RDC (Round Duct Connector) may be ordered from manufacturer for field installation.

For Frame Construction:

Position unit between joists. Position brackets such that bottom edge of housing will be flush with finished ceiling, and tighten the adjustable mounting brackets, shown in Fig. 3.

Diagram: Fig. 3 shows a fan unit positioned between ceiling joists, with mounting brackets adjusted for a flush fit with the ceiling.

For Hanging Installations:

Use manufacturer's optional vibration isolator kit Part Number VI Kit. Using the fan's standard adjustable mounting brackets and 10 by 32 threaded rod (by others), hang unit as shown in Fig. 4.

Diagram: Fig. 4 shows a fan unit suspended using mounting brackets and threaded rod.

3. Installation of ductwork

Installation of ductwork is critical to the performance of the fan, shown in Fig. 5. Straight ductwork (1) or ductwork that turns in the same direction as the wheel (2) is recommended. Ductwork turning opposite the wheel direction (3) will cause turbulence and back pressure resulting in poor performance.

Diagram: Fig. 5 illustrates ductwork configurations: (1) Straight ductwork (GOOD), (2) Ductwork turning in the same direction as airflow (GOOD), (3) Ductwork turning opposite to airflow (POOR). Includes 'AIRFLOW' arrow.

4. Slide ductwork over the fan's discharge collar and securely attach it with sheet metal screws.

Make sure the screws do not interfere with damper operation. Check damper to make sure it opens freely.

Wire the Fan

  1. Remove wiring cover. If fan/light combination is being used, make sure the fan plug is connected to the fan receptacle and the light plug is connected to the light receptacle, shown in Fig. 6. Using proper wire connectors, wire the fan as shown in Fig. 7a. For wiring of light proceed to Fig. 7b.
    Diagram: Fig. 6 shows the fan and light plugs connected to their respective receptacles. Includes labels for 'Fan Outlet (top)' and 'Light Outlet (bottom)'.
  2. Push all wiring into the unit's cover and replace wiring cover.

Diagram: Fig. 7a shows a wiring diagram for the fan.

115 & 277 Volt
Black wire is "Hot"
White wire is "Neutral"
Green wire is "Ground"

Diagram: Fig. 7b shows voltage specifications and wire color coding.

220 - 240 Volt
Black wire is "Hot"
White wire is "Hot"
Green wire is "Neutral/Ground"

Attach the Grille

  1. If lighted grille is being used, plug wire into fan socket. If lighted grille and ceiling radiation damper are being used, plug wire from lighted grille into ceiling radiation damper socket. Do not plug wire directly into the fan socket. Make sure the wire does not interfere with the ceiling radiation damper operation.
  2. Attach grille with two screws provided. Make sure not to over tighten; over tightening will damage grille.
  3. Slide attachment screw covers over the attachment screws, shown in Figure 8 and 9.
  4. If lighted grille is being used, install light bulb(s) into light socket(s). For fluorescent lights, use 27W GU24 bulbs. For LED lights, use 10W GU24 bulbs. Manufacturer has replacement 27W GU24 bulbs, call 1-800-355-5354 to order.
  5. If lighted grille is being used, snap lens into place, by pushing on the outside edges of lens, shown in Fig. 9. To remove lens, use small screw driver and pry on one side of lens.
  6. Turn on power and check fan and light operation.

Diagram: Fig. 8 shows attaching the grille with screws.

Diagram: Fig. 9 shows snapping the lens into place.

Converting from Ceiling to Cabinet Design for Ceiling Exhaust Fans

All convertible sizes will be shipped with grille and duct collar cover. Note, this applies only to fans originally ordered as convertible.

Conversion Kit Parts List

Tools Required

Steps:

  1. Remove grille (A) by removing the two grille screws (B).
  2. Remove duct collar cover (C) by removing the four duct collar screws (D).
  3. Discard grille (A), two grille screws (B), and duct collar cover (C).
  4. Remove the six (6) tinnerman clips (E) by twisting them to one side and pulling straight out. Discard two of the six tinnerman clips.
  5. Insert the remaining four tinnerman clips (E) on grille opening side.
  6. Place blower box cover (F) over tinnerman clips (E), which were inserted in step 5.
  7. Screw the blower box cover (F) into place with four blower box cover screws (D).

Diagram: Shows parts A-F for conversion and illustrates the steps for removing and installing components.

Other Installation Considerations

Ductwork and Noise

Fiberglass ductboard is a better choice than metal ductwork for reducing fan noise and is highly recommended for low sound applications. Where metal duct is used, sound transmission can be reduced with flexible duct connections between the fan and the duct.

Diagram: Illustrates fiberglass ductboard and flexible duct connections for noise reduction.

Sound and Location

The location of these fans must be taken into consideration before installation. In critical sound installations, insulated ductwork, flexible duct connections or placing the fan in a remote section of ductwork are solutions to meeting the required fan sound levels.

Filters

The addition of an intake filter is highly recommended for these fans, even in clean air environments excess dirt can accumulate on wheels and motors causing reduced performance and imbalance.

Filters, once installed, should be checked and cleaned periodically to maintain performance. Washable aluminum mesh filters specifically designed for these fans are available, please consult your representative for more information.

Diagram: Shows 'Remote Mounted Fan Converted to Inline', 'Fiberglass Ductboard', 'Correct Low Sound Installation' with 'Flex Duct Connections', and 'Fan Mounted Directly Overhead Incorrect'.

General Maintenance Suggestions

Ceiling exhaust fans require very little maintenance. But since small problems over time left unchecked could lead to loss of performance or early motor failure, we do recommend that the unit be inspected periodically (once or twice a year).

The fan motor and wheel should be checked for dust and dirt accumulations. Dirt buildup can lead to loss of performance and motor overheating. Cleaning can be accomplished by brushing off any dust that may have accumulated. Even filtered units can accumulate build-up and should be checked when cleaning filters.

The motor should be checked for lubrication at this time. Lubricate only those motors which have an oil hole provided. A few drops of all purpose oil (SAE 20) will be sufficient.

Typical Installation

Diagram: Shows a typical installation scenario including insulation around the fan housing, a roof cap with damper, a wall cap with damper, round ductwork, and round elbows. Labels indicate 'INSULATION* (Place around and over Fan Housing.)', 'FAN HOUSING', 'POWER CABLE*', 'ROOF CAP* (with built-in damper)', 'Keep duct runs short.', 'WALL CAP* (with built-in damper)', 'ROUND DUCT*', 'ROUND ELBOWS*', 'Seal gaps around Housing.', 'Seal duct joints with tape.'. An asterisk indicates items to be purchased separately.

Our Commitment

As a result of our commitment to continuous improvement, Accurex reserves the right to change specifications without notice. Product warranties can be found online at accurex.com, either on the specific product page or in the Warranty section of the website at Accurex.com/Resources/Warranty.

P.O. Box 410 Schofield, WI 54476
Phone: 800.333.1400 • Fax: 715.241.6191
Parts: 800.355.5354 • accurex.com

Document 474741 • XCR XIR, Rev. 5, December 2020 © 2020 Accurex, LLC

Models: XCR-B, Ceiling Exhaust Fan, Exhaust Fan, Fan

File Info : application/pdf, 8 Pages, 6.08MB

PDF preview unavailable. Download the PDF instead.

Bathroom-Fan-ceiling-IOM

References

Adobe PDF Library 15.0

Related Documents

Preview Accurex Upblast Centrifugal Roof Exhaust Fan Installation, Operation, and Maintenance Manual
This manual provides comprehensive guidance for the installation, operation, and maintenance of Accurex XRUD, XCUE, and XCUBE Upblast Centrifugal Roof Exhaust Fans. It covers safety protocols, installation procedures, operational best practices, maintenance schedules, and troubleshooting tips, ensuring optimal performance and compliance with industry codes.
Preview Accurex XFCC 482414: Kitchen Fan Control Center Installation, Operation & Maintenance Manual
Accurex Kitchen Fan Control Center (XFCC) Installation, Operation, and Maintenance Manual (Document 482414). This guide details the setup, use, and upkeep of the XFCC for commercial kitchen ventilation, including safety, electrical, temperature interlock, and troubleshooting.
Preview Accurex Kitchen Ventilation Systems: Comprehensive Product Catalog
Accurex, a Greenheck Group Company, offers a complete range of high-quality kitchen ventilation systems, including exhaust hoods, fire suppression systems, utility distribution, controls, pollution control units, exhaust fans, make-up air units, and grease ducts. Engineered for simplicity, efficiency, and reliability, Accurex products meet diverse commercial kitchen needs.
Preview Accurex Grease Trapper Kitchen Exhaust Pollution Control Unit Installation, Operation, and Maintenance Manual
This manual provides detailed instructions for the installation, operation, and maintenance of the Accurex Grease Trapper Kitchen Exhaust Pollution Control Unit (PCU). It covers receiving, unpacking, handling, storage, system components, installation procedures, electrical connections, fire system integration, operation, filter replacement, carbon tray replacement, controller setup, keypad navigation, VFD information, and maintenance schedules. Safety precautions and troubleshooting tips are also included.
Preview Accurex Pollution Control Units: Grease Trapper & Grease Trapper ESP
Accurex offers advanced pollution control units, including the Grease Trapper and Grease Trapper ESP, designed to eliminate grease, smoke, and odors from commercial kitchen exhaust systems. Learn about their features, benefits, and compliance with industry standards.
Preview Accurex XRV Packaged Rooftop Ventilator: Installation, Operation, and Maintenance Manual
This comprehensive manual provides essential information for the safe and effective installation, operation, and maintenance of the Accurex XRV Packaged Rooftop Ventilator series. It covers safety precautions, product overview, installation guidelines, operation details, maintenance schedules, and troubleshooting tips for models XRV-20 through XRV-220.
Preview Accurex XRRS Fire Ready Hood Installation, Operation, and Maintenance Manual
Comprehensive guide for the Accurex XRRS Fire Ready Hood, covering installation, operation, maintenance, and safety procedures. Includes detailed instructions, troubleshooting, and parts lists.
Preview Accurex Microprocessor Controller for Dedicated Outdoor Air System Reference Guide
Accurex Microprocessor Controller for Dedicated Outdoor Air Systems (DOAS) Reference Guide. Learn about features, sequences, BMS communication, occupancy modes, alarms, and control variables for efficient HVAC management. Includes technical specifications and operational details.