System Test
Test heating, emergency heat, cooling, and fan. Available tests vary by thermostat and system type.
FocusPRO® 5000 Series System Test
1. To begin, press and hold the ▲ and ▼ buttons until the screen changes.
The thermostat screen displays '10' and '0' with 'Done' and 'Next' buttons. The ▲ and ▼ buttons are used for navigation.
2. Press ▲/▼ to turn the system on or off.
3. Press NEXT to advance to the next test.
4. Press DONE to end the system test.
5. Continue with system tests.
FocusPRO® 6000 Series System Test
1. To begin, press and hold the ▲ and ▼ buttons until the screen changes.
The thermostat screen displays '10' and '0' with 'Done' and 'Next' buttons. The ▲ and ▼ buttons are used for navigation.
2. Press ▲/▼ to turn the system on or off.
3. Press NEXT to advance to the next test.
4. Press DONE to end the system test.
5. Continue with system tests.
Table 2. System Test Procedures
System Test Number | Test Type | System Status Number and Description |
---|---|---|
10 | Heating System | 0 Heater and fan turn off 1 Stage 1 heating on (fan turns on if configuration function 1 is 1, 5, 9, or 10, or if configuration function 3 is 1). 2 Stage 2 heating on 3 Stage 3 heating on |
20 | Emergency Heating System | 0 Heater and fan turn off 1 Heater and fan turn on 2 Stage 2 heater (auxiliary heater) turns on |
30 | Cooling System | 0 Compressor and fan turn off 1 Compressor and fan turn on 2 Stage 2 compressor on |
40 | Fan System | 0 Off 1 On |
Installation Configuration
Available options and default settings vary by thermostat.
FocusPRO® 5000 Series Installation Configuration
1. To begin, press and hold the ▲ and FAN buttons until the screen changes.
The thermostat screen displays '0' and '0' with 'Done' and 'Next' buttons. The ▲ and FAN buttons are used for navigation.
2. Press ▲/▼ to change the setting.
3. Press NEXT to advance to the next function.
4. Press DONE to exit and save settings.
5. Continue with installation configuration functions.
FocusPRO® 6000 Series Installation Configuration
1. To begin, press and hold the ▲ and FAN buttons until the screen changes.
The thermostat screen displays '0' and '0' with 'Done' and 'Next' buttons. The ▲ and FAN buttons are used for navigation.
2. Press ▲/▼ to change the setting.
3. Press NEXT to advance to the next function.
4. Press DONE to exit and save settings.
5. Continue with installation configuration functions.
Table 1. Installation Configuration Functions
Function No. | Configuration Function | Settings and Options (Factory defaults in bold) |
---|---|---|
1 | System Type | 0 1 Heat/1 Cool Conventional System 1 1 Heat/1 Cool Heat Pump (no aux. heat) 2 Heat Only: 2-wire systems, 3-wire zone valves (Series 20), normally open zone valves 3 Heat Only with Fan 4 Cool Only 5 2 Heat/1 Cool Heat Pump (with aux. heat) 6 2 Heat/2 Cool Conventional System 7 2 Heat/1 Cool Conventional System 8 1 Heat/2 Cool Conventional System 9 2 Heat/2 Cool Heat Pump (no aux. heat) 10 3 Heat/2 Cool Heat Pump (with aux. heat) |
2 | Reversing Valve (O/B terminal) | 0 Controls valve in cooling 1 Controls valve in heating |
3 | Fan Control (Heating) | 0 Gas/Oil Heater (equipment controls fan for heating) 1 Electric Heating System (thermostat controls fan for heating) |
5 | Heating Cycle Rate Stage 1 | 5 Gas or oil heating systems less than 90% efficiency 1 Steam or gravity systems 3 Hot water or 90%+ efficiency heating systems 9 Electric heating system: [Other options: 1-12] |
6 | Heater Cycle Rate Stage 2 (Auxiliary Heater) | 5 Gas or oil heating systems less than 90% efficiency 1 Steam or gravity system 3 Hot water or 90%+ efficiency heating systems 9 Electric heating system: [Other options: 1-12] |
7 | Auxiliary Heat Cycle Rate | 5 Gas or oil heating systems less than 90% efficiency 1 Steam or gravity system 3 Hot water or 90%+ efficiency heating systems 9 Electric heating system: [Other options: 1-12] |
8 | Emergency Heat Cycle Rate | 9 Electric heating system 1 Steam or gravity system 3 Hot water or 90%+ efficiency heating systems 5 Gas or oil heating systems less than 90% efficiency [Other options: 1-12] |
9 | Compressor Cycle Rate Stage 1 | 3 Recommended [Other options: 1-6] |
10 | Compressor Cycle Rate Stage 2 | 3 Recommended [Other options: 1-6] |
12 | Manual or Automatic Changeover | 0 Manual Changeover (Heat/Cool/Off) 1 Automatic Changeover (Heat/Cool/Auto/Off) 2 Auto Changeover Only (Auto) |
13 | Adaptive Intelligent Recovery™ | 1 On 0 Off |
14 | Temperature Display | 0 Fahrenheit 1 Celsius |
15 | Compressor Protection | 5 5-minute Off Time for Compressor [Other options: 0-4 minutes] |
16 | Program Format | 0 5/2 (programmable for weekdays and weekends) 1 5/1/1 (programmable for weekdays, Saturday, and Sunday) |
26 | Auxiliary Heat Control | 0 Comfort 1 Economy |
27 | Heating System Temperature Range Limiter | 90 Maximum heating setting is 90 °F (32 °C) [Other options: 40-89 °F (4.5 °C to 32 °C)] |
28 | Cooling System Temperature Range Limiter | 50 Minimum cooling setting is 50 °F (10 °C) [Other options: 51-99 °F (10.5 °C to 37 °C)] |
Functions 13 and 16 are only available on the 6000 series; function 26 is only available on the 5000 series.
Caution
EQUIPMENT DAMAGE HAZARD.
During testing, compressor protection is disabled. To prevent equipment damage, do not allow the compressor to run at high speeds.