Introduction
This manual concerns the air handling unit type Rotovex SR, manufactured by Systemair AB. It consists of basic information and recommendations concerning the design, installation, start-up, and operation, to ensure a proper fail-free operation of the unit.
The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to given guidelines, and follow all safety requirements.
Unit Components and Views
Figure 1: Illustrates the left and right versions of the Rotovex unit, showing external components and internal layout.
Left Version Components:
- 1. Supply air
- 2. Extract air
- 3. Exhaust air
- 4. Outside air
- 5. Pressure sensor supply air filter
- 6. Fan, extract air
- 7. Fan supply air
- 8. Control Heat exchanger
- 9. Heat exchanger, Rotor
Right Version Components:
- 10. Rotor motor
- 11. Filter, Extract air
- 12. Filter, supply air
- 13. Pressure sensor supply air fan
- 14. Electrical Heater / Water coil
- 15. Electrical Connection box (see fig.3)
- 16. Safety switch
- 17. Pressure sensor extract air filter
- 18. Pressure sensor extract fan
Connection Box
Figure 2: Details the connection box and its components.
Connection Box Components:
- 20. Fuse heater
- 21. Fuse fans
- 22. 24 V Transformer
- 23. Control unit Corrigo
- 24. Contactor
- 25. ADO - terminal block tool
- 26. Overheating protection (EL- heating battery, Manual reset)
- 27. Overheating protection (EL- heating battery, Automatic reset)
The diagram also indicates an "Earth" connection point.
Unit External Components
Figure 3: Shows various external components and accessories of the unit.
- 1. Supply air
- 2. Extract air
- 3. Exhaust air
- 4. Outside air
- 5. VAV pressure transmitter supply air (accessories)
- 6. VAV pressure transmitter extract air (accessories)
- 7. Damper and motor exhaust air (accessories)
- 8. Damper and motor outside air (accessories)
- 9. Sensor supply air
- 10. Sensor extract air
- 11. Sensor outside air
Control Panel and Connection Block
Figure 4: Illustrates the control panel interface and the connection block with cables.
Control Panel Buttons:
- 1. Alarm button
- 2. Alarm LED
- 3. Write enable LED
- 4. OK button
- 5. Clearing button
- 6. Mounting holes
Connection Block (Item 7):
- 7a. Yellow cable
- 7b. Orange cable
- 7c. Red cable
- 7d. Brown cable
- 7e. Black cable
The diagram also shows a display with text like "Extended running", "Supply air temp", "Running mode", and "Service".
Operation
General
This manual describes the most common functions/settings. For more information about other functions/settings, please see the attached Corrigo E – Manual. The Corrigo E – Manual can also be retrieved from www.regin.se in different languages.
N.B. Rotovex units with an Electrical heater have a 3-minute re-cooling period after being turned off. If the fire alarm is activated when the heater is on, the fan stops immediately without re-cooling, which can cause the overheating protection to trip. See Figure 2 for the location to reset the manual overheating protection.
Maximum allowed supply air temperature is 35°C.
Set the Menu Language
Press the
button while switching on the mains supply. Press the button. Choose the language with the buttons. Confirm the choice with the button. Press the button to go back in the menus.The language can also be changed in the main menu: press the
3 times on the control panel.Control Panel
Access Rights
There are 2 different logon levels: Operator level and Service level.
- Service level gives read/write access to settings and parts of the configuration menu.
- Operator level permits read/write access to a limited number of settings and parameters.
Password
As default, Rotovex SR comes with the following passwords for different levels:
- Operator: 1111
- Service: 2222
How to Operate
Refer to Figure 4 for control panel details.
The menus in the Corrigo E are organized in a horizontal tree structure. The
buttons are used to move between menus at the present menu level. The buttons are used to move between menu levels. When changing parameters, the buttons are used to increase or decrease the value of the parameter, and the buttons to move between digits within the parameter.- The button is used to confirm the choice of a parameter setting.
- The button is used to abort an initiated parameter change and restore the original value.
- The button is used to access the alarm list.
Changing Parameters
In some menus, parameters can be set. This is indicated by the [LED indicator] flashing. To change a parameter, first press the
button; the [LED indicator] changes to a steady light. A cursor will appear at the first settable value. If you wish to change the value, use the buttons. For numbers with multiple digits, use the buttons to move between digits.When the desired value is displayed, press
. Settings outside the intervals are not registered. Preset values count. If further settable values are displayed, the cursor automatically moves to the next one. To pass a value without changing it, press .To abort a change and return to the initial setting, press and hold the
button until the cursor disappears.Navigating the Menus
The start display (the normal display) is at the root of the menu tree.
Pressing
will move you through the menu choices at the lowest level. will move you back through the choices.To enter a higher menu level, use
or to place the display marker opposite the menu you wish to access and press . If you have sufficient logon privileges, the display will change to the chosen menu.At each level, there may be several new menus through which you can move using the
buttons. Sometimes, further sub-menus are linked to a menu or menu item, indicated by an arrow symbol at the right-hand edge of the display. To choose one, use again. To back down to a lower menu level, use .Alarms
The
(pos.1 in Figure 4) opens the alarm queue. Pressing this button displays all active and non-acknowledged alarms in the menu window. The (pos.2 in Figure 4) blinks if there are non-acknowledged alarms and shines steadily if alarms are active but have been acknowledged. If there are multiple alarms, use buttons to move between them. An alarm can be acknowledged or blocked using and buttons. To abort and return to the start menu, select 'Cancel' and press the button.For alarm settings, see the Commissioning protocol (pages 22 and 23).
Extra Stop Function
For some alarm types, such as electric heating high temperature limit and water heating frost protection, it would be dangerous not to stop the unit on alarm. Therefore, for these alarm types, the program will always reset the stop function to 'Active' even if the operator chooses 'Inactive'. It is not possible to remove the display text concerning the stop function for these alarm types due to program space limitations.
Starting up the Unit
- Control that all external equipment are connected.
- Switch on fuses (pos.21 in Figure 2) in the unit.
- Switch on the supply voltage.
- Set present time and date, set the control temperature, and program the week schedule. Do the necessary settings for extra functions, if any.
Initial Setup of the Unit
On the first start-up, the controller initiates a special program for setting language, supply air temperature set point, time & date, and week schedule for normal speed. Use the
button to move between changeable parameters and the arrows to see displayed alternatives. Confirm by pressing again. Move down in the menu structure using the arrows.Step 1: Select Language
Select language by pressing
, then move between alternatives with the buttons. Confirm by pressing . Move to the next level by pressing the .Display Example:
Choose Language |
---|
English |
Step 2: Extract Air Temperature & Supply Air Set Point
Shows the actual extract air temperature. Set the supply air set point. Default is 18°C (log on to service level needed, code 2222, to change default setting).
Display Example:
Extract air temp |
---|
Actual: .... °C |
Setp.: 18 °C |
Step 3: Time and Date Check
Check and ensure the correct time and date are displayed; if not, change the settings.
Display Example:
Time: 12.46 |
---|
Date: 2010-03-12 |
Weekday: Friday |
Step 4: Week Schedule (Monday-Friday, Normal Speed)
Set the week schedule for normal speed operation from Monday to Friday. It's possible to set 2 periods per day.
Display Example:
Normal speed |
---|
Monday → Friday |
Per 1: 07:00 – 16:00 |
Per 2: 00:00 – 00:00 |
Step 5: Week Schedule (Saturday/Holiday, Normal Speed)
Set the week schedule for normal speed operation during Saturdays and holidays. It's possible to set 2 periods per day.
Display Example:
Normal speed |
---|
Saturday → Holiday |
Per 1: 00:00 – 00:00 |
Per 2: 00:00 – 00:00 |
Step 6: Week Schedule (Monday-Friday, Reduced Speed)
Set the week schedule for reduced speed operation from Monday to Friday. It's possible to set 2 periods per day.
Display Example:
Reduced speed |
---|
Monday → Friday |
Per 1: 00:00 – 00:00 |
Per 2: 00:00 – 00:00 |
Step 7: Week Schedule (Saturday/Holiday, Reduced Speed)
Set the week schedule for reduced speed operation during Saturdays and holidays. It's possible to set 2 periods per day.
Display Example:
Reduced speed |
---|
Saturday → Holiday |
Per 1: 00:00 – 00:00 |
Per 2: 00:00 – 00:00 |
Step 8: End Wizard
Select "Yes" or "No".
Display Example:
End Wizard |
---|
No |
After finishing the setup, the menu system for "Operator level" will be available.
See below menu overviews that display the available menus in the Operator level followed by the "Service level" manual.
To enter Service level use code 2222 in the "Access rights" menu. For operator level use code 1111.
To perform more advanced settings, please see the enclosed CD where the Corrigo E – manual can be found.
Menu Overview: OPERATOR/SERVICE LEVEL
This overview shows both the Operator and Service level. Parts unique to the Service level are marked with a grey background. To log on to the Service level, use code 2222 under Access rights.
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
Rotovex SR 07 EL 2011-03-15 09:00 System:Stopped Sp:18.0 Act: °C |
→ Running mode | Running mode Auto |
Start screen headline. Can be set to 5 different layouts. (Changeable at “system level" under the configuration menu). |
Running time SAF: 0.0 h EAF: 0.0 h |
Set Running mode to Auto, On or Off. Shows the time in hours that the motors have been operating. SAF = Supply air fan. EAF = Exhaust air fan. |
||
→ Selected functions | Control function | Shows type of air temperature control the unit is configured for. | |
Extract air control | Shows type of fan speed control the unit is configured for. | ||
Fan control | |||
Flow control | |||
Heating: Water | Shows type of heating selected. | ||
Exchanger: Rot. Excha | Shows type of exchanger selected. | ||
Cooling: Water | Shows type of cooling selected. | ||
Free cool active: No | Shows the status of the free cooling function. | ||
Support control Active: No CO2/VOC active Never |
Shows the status of the support control function. Shows the status of the demand ventilation (CO2/VOC) function. |
||
Fire damper function Not active Operation when alarm Stopped |
Shows the status of the fire damper function. |
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
→Temperature | Frost protection Actual: °C |
Active | Shows the status of the frost protection function. |
Cooling recovery No |
Shows the status of the cooling recovery function. | ||
External set point |
Not active | Shows the status of the external set point. | |
→ Alarm events | Shows all registered alarms along with the time and date they occurred. Move down and up in the list by pressing ↑↓. |
||
→Input/Output | →Analogue inputs | Shows the status of the Analogue inputs. | |
→Digital inputs | Shows the status of the Digital inputs. | ||
→Universal inputs | Shows status of Universal Analogue inputs. | ||
→Analogue outputs | Shows the status of Universal Digital inputs. | ||
→Digital outputs | Shows the status of the Analogue outputs. | ||
Shows the status of the Digital outputs. | |||
Extract air temp Act.: °C Setp: 18.0°C |
If cascade control Max/min supply setp. Max: 30°C Min: 12.0°C |
Shows the configured temperature control (Default is Extract air temp). Shows the actual temperature in the chosen control mode. Set the temperature for the chosen control mode. Set the maximum and minimum allowed supply air temperature in case of cascade control. Logon to service level needed to change settings. |
|
Outdoor temp: °C Supply air temp Actual: °C Setp: 18°C |
Shows the actual outdoor air temperature. Shows the actual supply air temperature. Shows the calculated supply air set point. The exhaust air controller output signal generates the supply air controller's set point value. |
||
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
→Air Control | Frost protection Actual: °C |
Shows the actual water temperature in the water heating battery (Only visible for HW units). | |
Exhaust air temp Actual: °C |
Shows the actual exhaust air temperature. | ||
Efficiency Exchanger Actual: % |
Shows the actual heat recovery efficiency. The function calculates the heat exchangers temperature efficiency in % when the output signal to the exchanger is higher than 98% and the outdoor temperature is lower than 10°C. When the control signal is lower than 98% or the outdoor temperature is higher than 10°C the display will show 0%. |
||
Flow control SAF Actual: m³/h Setp.: m³/h |
This menu option becomes visible if the unit is configured for "Flow control" or "Pressure control". Shows airflow for the supply air fan (constant airflow control). Only visible if the unit is configured for Flow control. |
||
Flow control SAF Setp 1/1: 1100 m³/h Setp 1/2: 550 m³/h |
Set the normal (1/1) and reduced (1/2) airflow for the supply air fan. | ||
Outdoor comp.Setp. 1 -20°C = 10 m³/h 0°C = 0 m³/h Act. Comp: 0 m³/h |
Set the SAF airflow compensation for the settable outdoor temperature. The outdoor compensation is linear and is set using two parameter pairs which give the value of the compensation at two different outdoor temperatures. The compensation can be positive or negative. Shows the actual airflow compensation. |
||
Flow control EAF Actual: + INF m³/h Setp.: m³/h |
Shows airflow for the extract air fan (constant airflow control). Only visible if the unit is configured for Flow control. |
||
Flow control EAF Setp 1/1: 1100 m³/h Setp 1/2: 550 m³/h↓ |
Set the normal (1/1) and reduced (1/2) airflow for the extract air fan. | ||
Outdoor comp.Setp. 1 -20°C = 10 m³/h 0°C = 0 m³/h Act. Comp: 0 m³/h |
Set the EAF airflow compensation for the settable outdoor temperature. The outdoor compensation is linear and is set using two parameter pairs which give the value of the compensation at two different outdoor temperatures. The compensation can be positive or negative. Shows the actual airflow compensation. |
||
Pressure control SAF Actual: Pa Setp.: Pa |
Shows the actual external pressure and set point for the supply air fan. Only visible if the unit is configured for "Pressure control" (VAV). |
||
Pressure control SAF Setp 1/1: 250 Pa Setp 1/2: 100 Pa |
Set the external pressure set point for normal speed (1/1) and reduced speed (1/2) for the supply air fan. | ||
Outdoor comp.Setp. 1 -20°C = 0 Pa 10°C = 0 Pa Act. Comp: 0 Pa |
Set the SAF pressure compensation for the settable outdoor temperature. The outdoor compensation is linear and is set using two parameter pairs which give the value of the compensation at two different outdoor temperatures. The compensation can be positive or negative. Shows the actual pressure compensation. |
||
Pressure control EAF Actual: Pa Setp.: Pa |
Shows the actual external pressure and set point for the extract air fan. Only visible if the unit is configured for "Pressure control" (VAV) |
||
Pressure control EAF Setp 1/1: 250 Pa Setp 1/2: 100 Pa |
Set the external pressure set point for normal speed (1/1) and reduced speed (1/2) for the supply air fan. | ||
Outdoor comp.Setp. 1 -20°C = 0 Pa 10°C = 0 Pa Act. Comp: 0 Pa |
Set the EAF pressure compensation for the settable outdoor temperature. The outdoor compensation is linear and is set using two parameter pairs which give the value of the compensation at two different outdoor temperatures. The compensation can be positive or negative. Shows the actual pressure compensation. |
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
→ Time settings | → Time/Date | Set correct time and date. | |
→ Timer normal speed |
Set week schedule Monday to Sunday + Holiday for normal speed. Possible to set 2 periods per day. 00:00 - 24:00 for continuous running. 00:00 00:00 inactivates the period. Note the settings in the commissioning record. |
||
→Timer reduced speed |
Set week schedule Monday to Sunday + Holiday for reduced speed. Possible to set 2 periods per day. 00:00 - 24:00 for continuous running. 00:00 00:00 inactivates the period. Note the settings in the commissioning record. |
||
→ Extended running |
Extended running 60 min Time in ext. running 0 min |
Set the time for extended running. Digital inputs can be used to force the unit to start or increase to Normal running although the timer says the running mode should be Off or Reduced. If the running time is set to 0 the unit only runs as long as the digital input is closed. The time the extended running is active is monitored in "Time in ext. Running". It's also possible to set a time here as well in order to shorten the initial set period. |
|
→ Holidays | Holidays (mm:dd) 1:01-01 2:09-04 - 09-10 3:01-05 - 01-05 |
Set up to 24 separate possible holiday periods for a full year. A holiday period can be any number of consecutive days from one and upwards. The dates are in the format: MM:DD. When the current date falls within a holiday period, the scheduler will use the settings for the weekday "Holiday". |
|
→ Manual/Auto | Supply Temperature contr. Auto Manual set: 0.0 |
In this menu the running mode of all the configured output signals and a number of control functions can be manually controlled. The supply air controller's output signal can be manually set (Manual/Auto) to any value between 0 and 100%. The temperature output signals will change accordingly if they are in Auto mode. It is also possible to manually control each of the temperature output signals individually. Since leaving any of the outputs in manual control will disrupt the normal control, an alarm will be generated as soon as any output is set to a manual mode. |
|
Set the supply air temperature to "Auto", "On" or "Off". Set the output signal between 0-100%. The outputs Y1, Y2 and Y3, if in Auto-mode, will follow the signal according to the set split values. |
|||
SAF: Auto Manual set: 0.0 EAF: Auto Manual set: 0.0 |
Set the start signal for SAF (supply air fan) & EAF (exhaust air fan) to "Auto, Manual full speed, Manual half speed or Manual. | ||
Heating Auto Manual set: 100.0 |
Set the heating to Auto, Manual or Off. Set the manual output 0-100%. |
||
Exchanger Auto Manual set: 0.0 |
Set the exchanger rotor control to Auto, Manual or Off. Set the manual output 0-100%. |
||
Cooling Auto Manual set: 0.0 |
Set the cooling to Auto, Manual or Off. Set the manual output 0-100%. Note: Needs to be activated in order to be visible here. |
||
P1-Heating Auto |
Set the pump control for the heating coil to Auto, On or Off. | ||
P1-Exchanger Auto |
Set the pump control for a possible run around coil to Auto, On or Off. | ||
P1-Cooling Auto |
Set the pump control for the cooling coil to Auto, On or Off. | ||
Fire damper Auto |
Set the Fire damper to Auto, Open or Close. Note: Needs to be activated in order to be visible here. Configuration of fire damper functions are made at System level. |
||
Fresh air damper (Outdoor air damper) Auto |
Set the Outdoor air damper to Auto, Open or Close. | ||
Exhaust air damper Auto |
Set the Exhast air damper to Auto, Open or Close. | ||
→ Settings | In this menu group the settings for the activated functions are available. Depending on which choices have been made in the configuration menu some of the possible alternatives may not be displayed. | ||
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
→ Control temp | Supply air control P-band: 33.0°C I-time: 100.0 sec |
Set P-band and I-time for the Supply air control function. Note: See Corrigo E ventilation 3.0 manual for deeper explanation. |
|
Room control P-band: 100.0°C I-time: 300.0 sec |
Set P-band and I-time for the Room control function. Note: See Corrigo E ventilation 3.0 manual for more info. |
||
Shutdown mode P-band: 100.0°C I-time: 100.0 sec |
Set P-band and I-time for the Shutdown function. Note: See Corrigo E ventilation 3.0 manual for deeper explanation. |
||
→ Frost protection Active Setp shutdown: 25.0°C P-band active: 5.0°C Fast stop at frost protection alarm Yes |
P-band active 5° C means that the frost protection controller will start overriding the heating output when the frost protection temperature is less than 5 degrees above the set frost alarm. default alarm limit is 7° C. Set the fast stop of the unit in case of frost protection alarm to Yes or No. |
||
→ Control flow | Flow control SAF P-band: 10000.0 m³/h I-time: 10.0 sec Min. output: 0% |
Alternatively Pressure control if chosen in the configuration of the unit from factory. Set P-band, I-time and Min. output for the supply air fan when the unit comes configured as Flow control from factory. Alternatively Pressure control if that configuration is chosen. |
|
Flow control EAF P-band: 10000.0 m³/h I-time: 10.0 sec Min. output: 0% |
Set P-band, I-time and Min. output for the Extract air fan when the unit comes configured as Flow control from factory. Alternatively Pressure control if that configuration is chosen. |
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
→ Configuration | → Alarm settings |
→ Alarm limits | Set the alarm limits and allowed deviations for the different functions. |
→ Alarm delays | Set the alarm delays and allowed deviation delays for the different functions. | ||
Restore factory settings: No Restore user settings: No |
In this menu, it is possible to restore all parameters to their factory settings or to the user settings they were saved as earlier. Select Yes or No. |
||
Save user settings No |
The current configuration can be saved in a separate memory area and can later be restored using the previous menu, Restore user settings. Select Yes or No. | ||
→ Control function |
Control function Mode: Room control |
Set type of temperature control function you want the unit to operate under. Choose between Extract air control, "Room control, Outdoor comp., Supply, Supply air control, Extract/supply air →(possible to switch between the two depending on outdoor temp.), Room/supply air →(possible to switch between the two depending on outdoor temp.), |
|
→ Free cooling | Free cool active: No |
Set free cooling active to "Yes or No. | |
Outd. temp activation 22°C |
Set the lower outdoor day temperature limit for the activation of the free cooling function. The temperature of the previous day needs to be over the set temperature in order activate the free cooling function. |
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
Outd. temp night High: 15.0°C Low: 5.0°C Room temp min. 18°C |
Set the upper outdoor night temperature limit for the activation of the free cooling function. Set the lower outdoor night temperature limit for the activation of the free cooling function. Set the lower room temperature limit. The temperature needs to be above this value for the free cooling function to stay active. |
||
Hour for start/stop Free cooling Start: 0 Stop: 7 |
Set the start and stop time for the free cooling function For example Start: 0 and Stop: 6 means that the free cooling sequence is active between 00.00 and 06.00 h. |
||
Time to block heat output after Free cooling 60 min |
Set the delay in minutes from the time where the free cooling sequence has stopped until a possible heating sequence is initiated, i.e. how long a cooler room temperature than set temperature can be accepted. | ||
Fan output when free cooling SAF: 0 % EAF: 0 % |
Set the fan speed in percentage of the normal speed for each fan individually during the free cooling sequence. | ||
Outdoor sensor placed in intake channel (intake duct) No |
Set if the outdoor sensor is placed in the intake duct or not. Choose between No and Yes Preset is No. |
||
→ Support control |
Support control Active: No EAF running during Support contr.: Yes Min. run time for support ctrl: 60 min |
When using the control function room control or extract air temperature control, it is possible to utilize support-heating and/or support-cooling. Minimum running time is settable 0...720 minutes. (factory setting 20 minutes). Choose between "Active: Yes or No". (For start and stop temperatures see the "Temperature" menu). Set the minimum running time in minutes for support control. |
Menu Overview (Continued)
Main menu item | Sub-menu item 1 | Sub-menu item 2 | Explanations |
---|---|---|---|
→ Access rights | → CO2/VOC Control |
CO2/VOC active Never Type: Fan Min. time: 60 min |
In applications with varying occupancy the fan speeds can be controlled by the air quality as measured by a CO2/VOC-sensor. See encl. corrigo manual (CD) for det. explanation. Set active to Never, Always or If time channel off. Set what should be regulated. Select type Fan Set the min. time the unit is activated by the CO2/VOC demand function. |
Activation level 1/2-speed: 800 ppm 1/1-speed: 1000 ppm diff: 160 ppm |
Set the activation level at 1/2 speed Set the activation level at 1/1 speed Set allowed diff. value. |
||
→ Cooling recovery |
Cooling recovery No Cooling limit: 2.0°C |
Set the cooling recovery to Yes or No. Set the cooling limit (the difference in temperature between extract air and outdoor air that activates the cooling recovery). |
|
→ Log on | Log on Enter password XXXX Actual level: None |
Log on to service level by entering a 4-digit code. After reaching the desired level go back with "LEFT" arrow (press 2 times) on the control panel. Standard code from factory to enter service level is 2222. Back to operator level: 1111 |
|
→ Log off | Log off No Actual level: None |
Log off from system level by changing "No" to "Yes" with the "OK" and "UP/DOWN" buttons Automatic logoff after 6 minutes of inactivity. |
|
→ Change password |
Change password for level:None New password XXXX |
Set a new password for the level of your choice. Can only be done once logged on to the service level. |
Free Cooling Description
This function is used during the warm period to save energy by using cold outdoor air, e.g. during night time, to cool down the building.
The following is only valid if the free cooling function is set to Active in the program menu.
Free cooling is only activated when the following starting conditions are met:
- Less than 4 days have passed since the unit was last in running mode.
- The outdoor temperature during the previous running period exceeded a set limit (+22°C).
- It is between 00:00 and 07:00:00 in the day (settable).
- The timer outputs for normal speed, Extended running normal and External stop are Off.
- A time channel will be On sometime during the recently started 24 hours.
The unit checks the night temperature (indoor and outdoor temperature) during 3 minutes at the set starting hour when the fans are started so that the sensors can perform a temperature measurement. If above conditions are met the free cooling function is started, if not the unit goes back to OFF position.
If the outdoor sensor is not located in the outdoor air inlet duct and a room sensor has been selected, the unit will not start free cooling as long as all the temperatures are not within the start and stop temperature intervals.
Stop conditions:
- Outdoor temp above the set max value (+18°C) or below the set min value (condensation risk, +10°C).
- The room temp/extract air temp is below the set stop value (+18°C).
- One of the timer outputs for normal speed, External stop or Extended running normal is On.
- The time has past 07:00:00.
When free cooling is active, the fans run at normal speed or the set value for pressure/flow control and the digital output Free cooling is active. The outputs Y1-Heating, Y2-Heat exchanger and Y3-Cooling are shut down. After free cooling has been activated, the heating output is blocked for 60 minutes (configurable time).
Warning
In order to avoid electrical shock, fire or other damage that might occur in connection with faulty use and operation of the unit, it is important to consider the following:
- The system must be installed according to the mounting instructions.
- Insulate mains supply before service or cleaning of the heat recovery unit.
- Tumble dryer must not be connected directly to the ventilation system.
- Make sure the filter is mounted in its place before running the system.
- Maintenance must be performed according to the instructions.
Maintenance
Maintenance of the Rotovex should normally be carried out 3 – 4 times a year. Apart from general cleaning, the following should be observed:
-
Changing Supply / Extract air filter (indicates as "Filter guard" in the control panel, fig.3 and 4).
The bag filter cannot be cleaned and must be changed as necessary. New filters can be ordered from Systemair. Pressure guards monitor Supply and Extract air filters.
Initial pressure drop is approx. for EU7 filters = 80Pa and for EU5 filter = 45Pa. Final pressure drop is approx. 240 Pa.
-
Checking the heat exchanger (Once a year), (fig.1).
After long times use, dust may build up in the exchanger and block the airflow. It is vital to clean the exchanger regularly to maintain high efficiency. The heat exchanger cannot be taken out of the unit. Clean the surface of the exchanger using a vacuum cleaner with a brush fitting. Take great care not to damage the surface. If necessary, compressed air may be used to remove dirt. If the transmission belt is worn or slack, it should be replaced.
-
Checking the fans (once a year), (fig.1).
Even if the required maintenance, such as changing of filters, is carried out, dust and grease may slowly build up inside the fan (pos.6 and 7 in fig. 1). This will reduce the efficiency. The fans may be cleaned with a cloth or a soft brush. Do not use water. White spirit can be used to remove obstinate settlements. Allow drying properly before remounting.
-
Cleaning extract louvres and inlet diffusers (when necessary).
The system supplies fresh air to the building and extracts the used indoor air via the duct system and diffusers/louvres. Diffusers and louvres are mounted in ceilings/walls in bedrooms, living rooms, wet rooms, WC etc. Remove diffusers and louvers and wash in hot soapy water as required. (Diffusers/ louvres must be put back with their original settings and positions in order not to unbalance the system).
-
Checking the fresh air intake.
Leaves and pollution could plug up the air intake grille and reduce the capacity. Check the air intake grille at least twice a year, and clean if necessary.
-
Checking the duct system (when necessary).
Dust and grease settlements may build up in the duct system even if filters are changed regularly. This will reduce the efficiency of the installation. The duct runs should therefore be cleaned/ changed when necessary. Steel ducts can be cleaned by pulling a brush soaked in hot soapy water, through the duct via diffuser/ louver openings or special inspection hatches in the duct system (if fitted).
NOTE! In addition, roof cowl must be checked once a year and cleaned as necessary.
Troubleshooting
Should problems occur, please check or correct the following before contacting your service representative. Always check if there are any alarms active in the control panel.
-
Fan(s) do not start
- Check if there are any alarm messages.
- Check the settings in the control panel (times, week schedule, auto, manual operating etc.).
- Check that the fuses are not defect.
-
Reduced airflow
- A.) Check the settings of fan speed.
- B.) Check that the Fresh / Exhaust air damper, if used, opens.
- C.) Change of filters required?
- D.) Cleaning of diffusers/louvers required?
- E.) Cleaning of fans required?
- F.) Is roof unit/air intake clogged?
- G.) Duct system. Check visible duct runs for damage and/or build-up of dust/pollution.
- H.) Check diffuser/louver openings.
-
Cold supply air
- A.) Check control temperature on the control panel.
- B.) Check if overheating thermostat is alert. If necessary, reset by pressing the red button, marked , on top of the connection box (pos.26 in fig.2).
- C.) Check if the extract filter must be changed.
- D.) Check that the heat exchanger is rotating.
- E.) Check if the fan thermo contact has tripped, shows as Fan alarm in the control panel. If necessary, reset it (see page 3).
-
Noise/ vibrations
- A.) Clean fan impellers.
- B.) Pull the fans out and check that the 2 screws holding the fans are tightened.
Service
Before calling your service representative, make a note of the specification and production number from the data plate.
Company Information
Systemair AB reserves the right to make changes and improvements to the contents of this manual without prior notice.
Systemair AB
Industrivägen 3
SE-739 30 Skinnskatteberg
Phone +46 222 440 00
Fax +46 222 440 99
www.systemair.com
Document Number: 205675 (27-05-2011)