Systemair Topvex SoftCooler SR09, SR11 Installation Instructions

Document Reference: 208765.A004

1 Declaration of Conformity

Manufacturer: Systemair Sverige AB, Industrivägen 3, SE-739 30 Skinnskatteberg, SWEDEN. Office: +46 222 440 00, Fax: +46 222 440 99, www.systemair.com

Confirms that the following products comply with applicable directives and regulations:

Applicable Directives and Regulations:

Applied Harmonized Standards:

Complete technical documentation is available. Dated: Skinnskatteberg, 15-03-2016. Signed: Mats Sándor, Technical Director.

2 Warnings

The following admonitions are presented throughout the document:

[Danger]

[Warning]

[Caution]

3 Refrigerant Control/Reporting

Topvex SoftCooler SR units contain more than 3kg of refrigerant per circuit. A control report must be established by a certified cooling technician before commissioning. Leakage control with record keeping is required annually. Reporting to the inspection authority is necessary if the total refrigerant amount on the property exceeds 10 kg. Regulations may vary by country; consult local government.

4 Product Information

4.1 General

This manual concerns the Systemair Topvex SoftCooler SR, including models SR09 and SR11. It is available in Right (R) or Left (L) configurations, indicating the supply air outlet side when viewed from the access side. The manual provides basic information and recommendations for design, installation, start-up, and operation to ensure proper function. Thoroughly reading and adhering to this manual and safety requirements is crucial for proper and safe operation.

4.2 Technical Data

4.2.1 Dimensions and Weights

Figure 1: Dimensions (mm) SR09, SR11 (Drawn as left hand unit)

Diagram description: A diagram showing the unit with dimensions labeled A through G. Arrows indicate supply and exhaust air flow.

ModelA (mm)B (mm)C (mm)D (mm)E (mm)F (mm)G (mm)Weight, kgWeight, TOT (kg)
SR091120600400108104260915230665
SR1112308004001351652151025260695

4.2.2 Technical Data

ModelVoltageCurrent (A)Power (W)Fuse, slowQuantity of R410A, kg
Topvex SoftCooler SR09400V 3N~, 50Hz159230204.1
Topvex SoftCooler SR11400V 3N~, 50Hz159230204.8

4.3 Components

Figure 2: Basic components in left hand unit

Diagram description: A schematic showing the internal components of the unit.

PositionDescription
1Compressor
2Condenser coil
3Evaporator coil
4Filter drier with sight glass
5Electronic expansion valve
6Drip-tray with drain
7Water seal
8Cable grommet for external cabling
9El. cabinet
10Frequency converter
11Pressure/hot gas switches
12Measuring points refrigerant system high/low

4.4 Electrical Cabinet

Figure 3: Electrical cabinet

Diagram description: A diagram showing the internal layout of the electrical cabinet.

PositionDescription
1Terminal block, mains supply
2Circuit breaker (MCB) oil heater
3Relays
4Terminal block, internal/external connections
5Frequency converter
6DC choke
724V transformer
8LCD display

5 Transport and Storage

Store and transport the Topvex SoftCooler to protect it from physical damage. Cover the unit to prevent dust, rain, and snow ingress. The appliance is delivered as one piece on a pallet. Use a forklift for transport. Avoid transferring the unit once installed on the floor, as feet can be damaged by lateral loading.

[Warning] The unit is heavy. Handle with care during transport and mounting to avoid pinching injuries. Use protective clothing. Ensure the unit does not tip over.

6 Installation

6.1 Unpacking

Verify all ordered equipment is delivered before starting installation. Report any discrepancies to the supplier.

6.2 Where/How to Install

Topvex SoftCooler units are for indoor installation. Place the unit on a horizontal, flat, and completely levelled surface. Electronic components require temperatures between 0°C and +50°C for interference-free operation. Maximum operating temperatures are: Outside air +33°C, Extract air +28°C, Ambient temperature +28°C. Ensure easy access for regular maintenance and inspection doors. Leave sufficient space for opening doors and removing main components. General maintenance includes inspecting and cleaning the drip tray and flange coils. A floor drain is required for condensation water. Avoid placing the unit directly against a wall to prevent low-frequency noise vibrations; insulate the wall if necessary.

6.3 Installing the Unit

6.3.1 Installation

Figure 4: Installation, left hand unit

Diagram description: Shows the unit with connections for Supply, Exhaust, Outdoor, and Extract air. Includes positions for VAV pressure transmitters, dampers, and sensors.

PositionDescription
1Supply
2Exhaust
3Outdoor
4Extract
5VAV pressure transmitter supply air (accessories)
6VAV pressure transmitter extract air (accessories)
7Damper and motor exhaust air (accessories)
8Damper and motor outside air (accessories)
9Sensor supply air
10Topvex SoftCooler SR

6.3.2 Installation Procedure

  1. Prepare the mounting surface: Ensure it is flat, level, and can support the unit's weight. Follow local rules and regulations.
  2. Lift the unit into place. [Warning] Beware of sharp edges during mounting and maintenance. Use a proper lifting device and protective clothing.
  3. Level the unit using the enclosed mounting feet.
  4. Connect the unit electrically to the mains via the all-pole circuit breaker (safety switch) located inside the unit. Wiring is routed through the top casing to the electrical connection box. Refer to the wiring diagram and chapter 6.4.2.1 for details.

[Warning] The unit's electrical connection must be preceded by an all-pole circuit breaker with a minimum 3 mm gap.

[Danger] Ensure Mains supply is disconnected before maintenance or electrical work. All electrical connections must be by an authorized installer according to local rules and regulations.

6.4 Dividing the Topvex SR Air Handling Unit

Before installing the Topvex SoftCooler SR, the Topvex SR unit must be divided (Figure 5). To split the unit: Remove the heat exchanger, supply air fan, and extract air filter. Loosen cable connectors. The unit halves are joined by 4 M10 screws. Identify sections: C. Control section, D. Heat recovery section. Gables can be dismounted by removing 6 MRX M6 screws. Reassemble in reverse order.

Figure 5: Left hand version

Diagram description: Illustrates the unit split into sections labeled A, B, C, D, E.

Note: When reassembling, ensure correct cable connections as per cable markings.

6.4.1 Assembly the Topvex SoftCooler SR

Figure 6: Left hand unit (right hand units are mirrored)

Diagram description: Shows the steps for assembling the SoftCooler with the air handling unit parts.

Ensure sealing stripes and faces between unit halves are undamaged. Place the SoftCooler between the air handling unit parts and push them together. Join with 4 M10 screws. Remove the cover plate on top, the exhaust air filter, and the supply air fan to access the inner upper mounting screws. Remount these components after securing the screws.

6.4.1.1 Condensation and Heat Insulation

Outdoor air and discharge ducts must be well insulated against condensation, especially in cold rooms. Use insulating covering (minimum 100 mm mineral wool) with a plastic diffusion barrier. For extremely low outdoor temperatures, additional insulation is required, totaling at least 150 mm. [Caution] Ensure all joints are covered with insulation and tape in cold places. Cover duct connections/ends during storage and installation. Do not connect tumble dryers to the ventilation system.

6.4.1.2 Condensation Drain

[Warning] The unit must not be operated before the condensation drain and water seal are connected to the floor drain. The drain connects under the drip-tray in the bottom of the unit. Use the included plastic connection pipe, cut to the correct height 'H' based on the table below, which relates 'H' to maximum negative pressure.

Figure 7: Dimension and assembly

Diagram description: Shows the condensation drain connection with height 'H' and a table relating 'H' to maximum negative pressure.

H (mm)Max. Negative pressure (Pa)
85500
110750
1351000
1Normal conditions

An extra pipe is needed to connect the water seal outlet to the floor drain. Ensure this pipe has a minimum slope of 1:200 to the floor drain and is in a frost-free space.

Figure 8: Pipe to floor drain

Diagram description: Illustrates the pipe connection from the unit to the floor drain.

6.4.2 Electrical Connection

[Danger] Ensure Mains supply is disconnected before maintenance or electrical work. All electrical connections must be by an authorized installer according to local rules and regulations. Operation in the refrigerant cycle and handling refrigerants must be performed by certified personnel.

6.4.2.1 External/Internal Connections

Figure 9: Electrical connection, left hand unit

Diagram description: Shows cable fastener, control cable, and power supply connections.

Connections:

  1. Wire the prepared control cable from the Topvex SoftCooler electrical connection box to the Topvex SR electrical cabinet (supply air part). Use the grommet to enter the cabinet and secure the cable with self-adhesive fasteners.
  2. Connect wires to the terminal block in the electrical cabinet according to labeling and the wiring diagram.
  3. Connect the cooler unit electrically to the mains (400V 3~, 50 Hz) via the all-pole circuit breaker (safety switch). The power cable connects directly to the SoftCooler electrical connection box. Dimension wire and fuses according to electrical data (Figure 4.2.2).
  4. Make electrical connections for the Topvex SR air handling unit as per its installation instruction.

Mains supply is the only external connection for the Topvex SoftCooler.

Table 1: External connections
Terminal blockDescriptionRemark
PEGround400V 3N~, 50Hz supplied via safety switch
NN (Earthed neutral, supply voltage)
L1L1 (Phase, supply voltage)
L2L2 (Phase, supply voltage)
L3L3 (Phase, supply voltage)

The prepared operating cable in the Topvex SoftCooler should be routed to the electrical cabinet in the supply air part of the Topvex air handling unit and connected to terminal blocks matching the cable markings.

Table 2: Internal connections
Terminal blockDescriptionRemark
GG24V AC
4DI refReference
10DO refReference
15DOSignal from control unit E28 for "DX cooling step1" (cooling demand), controls relay R1 to start compressor.24V AC, 0.5A
74DIAlarm indication cooling (Run Error P1-Cooling).NO
90AO refReference
94AOControl signal from control unit E28 for cooling, controls frequency converter "FC".0-10V DC

7 Function Description

Figure 10: Left hand unit

Diagram description: A schematic illustrating the functional components of the unit.

PositionDescription
HEExchanger
DODamper outdoor air (accessory)
DEHDamper exhaust air (accessory)
FCFrequency converter
CPRCompressor
EVEvaporator
COCondenser
HPSCondenser pressure sensor
OT/ETOverheating/Max. temp switches
FGS/FGEAir filter pressure switches

7.1 General

Control unit E28 (UC) senses the extract temperature sensor (ETS) to maintain the set extract temperature by sequentially controlling the compressor (CPR), heat exchanger (HE), and hot water/electrical heater (HWL/H, ELH). The supply air temperature sensor (SS) limits the supply air temperature.

7.2 Power Control

The compressor (CPR) is controlled steplessly by the frequency converter (FC) between set minimum and maximum frequencies.

7.3 Power Limitation

The programmable controller monitors the condensing pressure via the high pressure sensor (HPS). If the pressure exceeds the set limit, the compressor (CPR) speed is gradually reduced to prevent a high pressure alarm.

Note: This instruction covers functions for the Topvex SoftCooler SR. For a complete description, refer to "SR 09,11, TR 09-15 Installation instruction".

8 Commissioning Protocol

Company:

Responsible:

8.1 General

Customer:Date:Installation:
Object/unit:Item no:Installation address:
Model/size:Serial no:Designation:

8.2 Installation Protocol

MomentDoneNote
Control report cooling concerning installation established. (Refer to chapter 3, Refrigerant Control/Reporting).
All unit parts undamaged.
Installation carried out according to instructions (see chapter 6.4.1, Assembly the Topvex SoftCooler).
Condensation drain connected (see chapter 6.4.1.2, Condensation drain).
Mains supply connected via the Safety switch (see chapter 6.4.2, Electrical connection).
Internal operating cable connected (see chapter 6.4.2.1, External/Internal connections).
Supply and extract airflow adjusted.

8.3 Preparing Control Unit E28

To ensure correct functions, configure the control unit E28 (or use PC software "Corrigo E-tool Ventilation"). Log in to E28 (using code 3333) or download the configuration file (.vtc) from the Systemair online catalogue.

MomentDoneNote
Select menu Configuration-Input/Output: Select DI, Browse to DI4, set to P1-Cooling.Note: DI4 cannot be used for extended run when Topvex SoftCooler is used.
Select menu Configuration-Control function: Check setting is Extract air control or Room control.
Select menu Configuration Cooling: Set DX. Set Limit for supply air control on active to 0.0°C.
Select Configuration step controllers/step contr. cooling: Activation levels (scroll down), Select Chiller groups: 1, Set Min in/out connecting time: 1 sec.
Select menu Configuration Cooling recovery: Set Cooling recovery to position No.

8.4 Before Compressor Start

The compressor crankcase oil must be heated before the first start to prevent damage.

MomentDoneNote
Stop the Supply- and extract fan (via the Topvex air handling units safety switch).
Turn on the mains supply for the Topvex SoftCooler via the safety switch. Verify voltage is on (frequency converter display lights up). Wait for a minimum of 2 hours for the oil to reach approximately +30°C.

8.5 Control Cooling Operation

MomentDoneNote
Start the Supply- and extract fan (via the Topvex air handling units safety switch). Run the unit on dimensioning airflows.Supply air: ________ m³/h
Extract air: ________ m³/h
Start the compressor by establishing a 100% cooling demand: Log in to control unit E28 (2222), Select menu Hand/Auto, Select Cooler type/coil, Set Cooler to Manual output 100.0.Outdoor air temperature: ________ °C
Supply air temperature: ________ °C
Extract air temperature: ________ °C
Exhaust air temperature: ________ °C
Hotgas temperature: ________ °C
Liquid line temperature: ________ °C
Run the compressor for at least 10 minutes. Read the Extract-, Outdoor-, Supply-, and Exhaust air temperatures via the control unit E28 display (in the Temperature menu).
Let the compressor run. Measure the hotgas- and liquid line temperature with a strap-on temperature detector.
Keep the compressor running. Read the following values via the frequency converter display (refer to "Frequency converter, quick guide" in Operating and Maintenance Instructions). Set parameters for reading, then close the Topvex SoftCooler door for at least 5 minutes before reading: Output frequency (Param d001), Output current (Param d002), Condenser pressure (Param d004).Output frequency: ________ Hz
Output current: ________ Hz
Condenser pressure: ________ bar

Note: Important! Restore the cooling operation to "Auto": Log in to control unit E28 (2222), Select menu Hand/Auto, Select Cooler type/coil, Set Cooler to Auto.

PDF preview unavailable. Download the PDF instead.

TOPVEX SOFTCOOLER SR INSTALLATION INSTRUCTIONS CE EN 208765 A004 20190426 191857671 PDFlib PDI 9.0.6 (C /Win64) PTC Arbortext Publishing Engine

Related Documents

Preview Topvex SoftCooler SR09, SR11 Access Control System Installation Instructions
Comprehensive installation instructions for the Systemair Topvex SoftCooler SR09 and SR11 access control system, covering product information, technical data, installation procedures, and commissioning.
Preview Topvex SoftCooler SR09, SR11 Operation and Maintenance Instructions
Comprehensive operation and maintenance instructions for the Systemair Topvex SoftCooler SR09 and SR11 air handling units, covering safety, components, installation, function, cooling flow, maintenance, and alarms.
Preview Systemair Topvex SR07/SR09/SR11 E Compact Air Handling Unit - Installation Instructions
Comprehensive installation instructions for the Systemair Topvex SR07, SR09, and SR11 E Compact Air Handling Units, covering dimensions, electrical connections, functions, operation, and commissioning.
Preview Systemair Topvex SoftCooler SR09, SR11: Operation and Maintenance Manual
This manual provides detailed information on the operation, installation, and maintenance of the Systemair Topvex SoftCooler SR09 and SR11 access control systems. It covers system components, functions, technical specifications, and troubleshooting.
Preview Systemair Topvex SoftCooler SR09/SR11 Operation and Maintenance Instructions
This document provides comprehensive operation and maintenance instructions for the Systemair Topvex SoftCooler SR09 and SR11 access control systems. It covers product description, installation, function descriptions, cooling flow charts, maintenance procedures, and alarm management.
Preview Systemair Topvex SoftCooler SR09/SR11 Access and Operation Manual
Comprehensive manual for Systemair's Topvex SoftCooler SR09 and SR11 air handling units, detailing installation, operation, maintenance, technical specifications, and troubleshooting.
Preview Systemair Topvex SR07, SR09, SR11 E Compact Air Handling Unit: Operation and Maintenance Manual
Comprehensive operation and maintenance instructions for the Systemair Topvex SR07, SR09, and SR11 E compact air handling units. Covers installation, setup, operation, troubleshooting, and maintenance procedures.
Preview Systemair Topvex SR/TR03/TR04/TR06 Air Handling Unit Installation Guide
Comprehensive installation instructions for Systemair's Topvex SR/TR03, SR/TR04, and SR/TR06 compact air handling units. Covers product information, technical data, transport, storage, and installation procedures.