Honeywell X-Series Battery Powered Fire Alarms

Installation and Operating Instructions

Welcome and Product Overview

Thank you for purchasing a Honeywell fire alarm. These alarms are suitable for domestic premises, including static holiday homes, and leisure accommodation vehicles (LAVs). This manual provides essential safety information for installation and operation. It is advised to have a fire evacuation plan and ensure all occupants are familiar with alarm signals.

Honeywell offers three models of battery-powered fire alarms:

  • XH100: A heat alarm approved to BS5446-2:2003.
  • XS100: An optical smoke alarm approved to EN14604:2005, using optical detection.
  • XS100T: An optical-thermal smoke alarm approved to EN14604:2005, using dual detection for quicker response and fewer false alarms.

All models feature a sealed-in battery with a 10-year lifetime and warranty. They include clear status indicators: Green for Power, Yellow for Fault, and three large Red indicators for Alarm. All versions also have an audible alarm and a TEST/HUSH button.

Each fire alarm has a dot on its side indicating its type: a single dot for Optical Smoke Alarm, two dots for Heat Alarm, and three dots for Optical-Thermal Smoke Alarm.

Honeywell X-Series alarms can be wirelessly interconnected using an optional plug-in module (XW100). This ensures that if one alarm triggers, all interconnected units will sound a loud audible alarm (85dB), which is particularly useful in larger or multi-story dwellings.

Warnings: To prevent dust contamination during building work, remove or cover the alarm vents with a plastic bag or tape. Ensure the covering is removed daily. The alarm is permanently sealed for safety and should not be opened.

Fire Alarm Operation

Normal Operation: The Green POWER light flashes once per minute to indicate the unit is working, unless this feature has been disabled during installation (refer to installation instructions).

Alarm State: If smoke or heat is detected, the Red ALARM indicators will flash, and a loud audible alarm will sound continuously. Evacuate immediately and contact emergency services. If the alarm is believed to be false (e.g., from steam or cooking fumes), the TEST/HUSH button can silence it for 5 minutes while the air clears. Caution: Use a broom handle to press the button if the alarm is out of reach.

Fault State: A Yellow FAULT light flashes every minute with a short chirp, indicating the unit is not working properly or has reached its end-of-life. A wireless module fault is indicated by 3 chirps. If alarms are networked, a fault in one unit will cause others to flash and chirp every four hours. Faults must be investigated and cleared promptly. Check the 'Replace by...' date, battery, or potential sensor obstruction (dust).

Status Lights and Sound Meaning

StatusAlarm (Red)Power (Green)Fault (Yellow)SoundMeaning
NORMAL OPERATION*Flashes once every minute. *NB light can be switched off (see installation section)Normal operation. No smoke and/or heat present.
ALARM3 chirps and flashes continuously for 60 minutes. Pattern then repeats every 30 seconds.Smoke and/or heat detected.
REMOTE FIRE ALARM or REMOTE CARBON MONOXIDE ALARM**3 chirps continuously / 4 chirps continuously. Broadcasted on network.Fire detected by an interconnected fire alarm or Carbon monoxide leak detected by an interconnected Carbon Monoxide alarm.
REMOTE FAULT**4 chirps and 4 flashes every 4 hours. Broadcasted on network.A wireless connected unit is in fault.
WIRELESS MODULE FAULT**3 chirps and 3 flashes every minute. Not broadcasted on network.The wireless module is not working correctly. Refer to the wireless module manual.
FAULT*1 chirp and 1 flash every minuteThe unit has reached its end of life and must be replaced.

* Unless the light is switched off during installation.
** Only applicable when a wireless connection plug-in module is installed.
*** Unless muted by pressing the TEST/HUSH button.

Precautions During Use

The fire alarms require minimal maintenance, primarily cleaning the exterior with a damp cloth and mild detergent. For smoke alarms (XS100T, XS100), ensure side openings are clear of dust or dirt. Use a vacuum cleaner to remove dust and prevent contamination, which can inhibit operation.

Warning: Do not paint the detector.

During decorating or building work, cover or remove the alarm to protect it from damage, dust, or inadvertent operation. Ensure alternative safety measures are in place while the alarm is covered and inoperable. Remove protection when work stops for the day; failure to do so could be life-threatening.

Testing Your Alarm

Automatic Self-Test: The fire alarm performs a self-test every 10 seconds.

Monthly Test: Test the alarm monthly to verify all visual and audible signals. Press the TEST/HUSH button for 1 second for a full test cycle (reduced sound level). Hold the button for 10 seconds or more to test the full 85dB sound level. Caution: Use a broom handle if the alarm is out of reach.

Monthly Test with Wireless Function: To test wireless communication, press and hold the TEST/HUSH button on one alarm. After its full volume test, it enters a Remote Test state (red LED flash with chirp every 6 seconds), repeated by all interconnected alarms. Pressing the button again or waiting 10 minutes returns alarms to normal.

Test/Measuring Mode Overview

Press button forUnit Mode
1 sGreen Flash + chirp
2 sYellow Flash + chirp
3 sRed Flash + chirp
4 sReduced volume alarm pattern
5 sPause
6s - 17sHigh volume alarm pattern
18+sPause, then Remote Test* (see note below)
Done even if button releasedWill go back to Normal mode as soon as button releasedButton may be released

*Remote Test: Test your wireless alarm communication.

Specifications

CategoryDetails
Reliability10-year lifetime and warranty
Detection PrincipleXS100T: Optical with thermal assistance; XS100: Optical; XH100: Thermal
ApprovalsXS100T, XS100: CE EN14604:2005/AC:2008, VdS Q-label (vfdb14-01), NF292; XH100: BS5446-2:2003, BSI Kitemarked
Other CompliancesRoHS, REACH, R&TTE, EMC
Self-test FunctionEvery 10 seconds
Operating EnvironmentTemperature: -10 °C to 55 °C; Humidity: 25-93% RH (non-condensing); IP Rating: IPX2D
Electrical & InterconnectionPower Supply: Long-life lithium battery, 3V sealed-in; Wireless: Optional XW100 module available
User InterfaceVisual Indicator: Green LED (Power), 3 large Red LEDs (Alarm), Yellow LED (Fault), Blue LED (Wireless, if installed); Audible: >85 dB @ 3 m with distinct fire alarm sound (3 chirps); Button: Test with reduced sound level, Alarm hush, Fault hush (24 hours)
ProductSize: Ø 116 mm x 42 mm; Weight: 190 g
PackagingType: Carton Box with Euro-hole hanger; Dimension: 119 x 119 x 55 mm; Scope of Supply: Fire alarm including sealed battery

Installation

Siting Recommendations

General recommendations for battery-powered fire alarms in residential premises are provided. It is crucial to follow country-specific regulations, such as British BS5839-6 or German DIN14676, which may require interconnected mains-powered alarms.

Preferred Locations: Alarms should ideally be fitted on the ceiling, as close to the center of the room as possible, but at least 50 cm (10 inches) from any wall or light fitting to avoid 'dead air' pockets. For optimal detection, place alarms where they can be heard when sleeping, such as in hallways outside bedrooms, to provide warning from fires on lower levels.

Where to Install Smoke Alarms (XS100T and XS100): Ideally, install a smoke alarm in every room except kitchens, bathrooms, and garages. A minimum of one alarm should be fitted on every level, including stairways. The XS100T is particularly recommended for exit routes and stairways due to its ability to detect heat build-up.

Where to Install Heat Alarms (XH100): Heat alarms are suitable for locations where smoke alarms cannot be used, such as kitchens, bathrooms, or garages, as they are unaffected by fumes, vapors, or condensation.

Where NOT to Install Alarms

Smoke Alarms (XS100T, XS100): Do not install in bathrooms or kitchens where steam or cooking fumes may cause false alarms, or in garages where exhaust fumes could trigger them.

Heat Alarms (XH100): Do not install in locations where local regulations mandate a Smoke alarm compliant with EN14604. Consult your local fire and rescue service if unsure.

Mounting the Alarm

The alarm pack contains: 1 x Fire Alarm, 1 x Ceiling mounting plate, Plugs and screws, and Instructions.

Ceiling Mounting: The alarm must be fixed horizontally to the ceiling using the enclosed mounting plate. The plate can be screwed using the central hole or two slots. Fitting the alarm to the plate switches it on.

Wall Mounting: In some circumstances, wall mounting may be advisable, especially in tall vertical spaces like stairwells, to ensure detection of rising smoke and heat.

First Time Switch On: Fit the alarm onto the mounting plate approximately 10 mm off center, press firmly, and slide sideways until the locking tab clicks. The unit will automatically switch on.

Tamper-Proof Ceiling Mounting: A tamper-proof clip can be used to lock the alarm to the mounting plate. This clip should be removed before installation. Once fitted, a screwdriver is required to remove the alarm.

Switching Off the Alarm: The alarm is switched off by removing it from the ceiling mounting plate. Press the tamper-proof tab and slide the alarm sideways. If the tamper-proof option is used, a small screwdriver may be needed.

Deactivating the Power Light Flashes

The green power light flashes every minute to show the batteries are OK. This can be annoying in bedrooms. To deactivate this, press the TEST/HUSH button five times within the first 30 seconds after fully mounting the alarm. Successful deactivation is confirmed by five green flashes and short chirps.

Conformance

The XS100 and XS100T are tested and approved to EN 14604 for Construction Products Regulations compliance. The XH100 is tested and approved to BS 5446-2 for heat alarms. All models (XS100T, XS100, XH100) comply with current EMC and ROHS directives. The XW100 radio module complies with the R&TTE directive.

The product also carries the CE mark, confirming compliance with applicable European Directives, and the NF – Smoke Alarm Devices mark, assuring safety and quality inspected by experts, confirming compliance with certification rules NF 292.

Troubleshooting and Getting Assistance

If the alarm fails to work after reading the instructions, contact the nearest customer service center or your local supplier. For repair or replacement, use original packaging or a solid box/padded envelope with a fault description. Switch off the alarm before transit. Notify postal services about sealed batteries. Proof of purchase is required for warranty claims.

Recyclable Packaging

The Green Dot logo [Green Dot Recycling Symbol] signifies membership in an organization that collects and recycles packaging. The packaging is widely recycled using local facilities.

End of Life

This product complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC. Components with this symbol should not be treated as household waste. Waste electrical products must be recovered and disposed of at specialist WEEE facilities. Contact your local authority, distributor, or manufacturer for more information on WEEE recycling.

Disclaimer

Honeywell fire alarms are designed to alert users to smoke or fire but are not intended to remedy fires or locate their source. Honeywell is not liable for fire investigation or service call costs resulting from an alarm. Dust and insect contamination is unpredictable, considered normal wear and tear, and is not covered by the warranty.

Warranty

Honeywell warrants the fire alarm for ten years from the purchase date or until the expiry date on the unit, whichever comes first. Honeywell will repair or replace defective parts at its discretion. The warranty does not cover defects due to unreasonable use, neglect, improper storage, failure to maintain according to the manual, or tampering. This warranty does not replace statutory rights.

What to Do in Case of a Fire Alarm

  • Raise the alarm by shouting or banging metal objects.
  • Evacuate immediately using the nearest exit. Do not stop for belongings or pets.
  • Use your escape route and meet at an agreed point.
  • Close doors to slow fire spread. Check doors for warmth with the back of your hand; do not open if warm.
  • Crawl low if there is smoke for better air and visibility.
  • Once outside, call the Fire Brigade from a safe location, providing your name and address.
  • Do not re-enter the building. Inform firefighters if someone is still inside.
  • Wait for the Fire Brigade in a safe place and provide them with information about the fire and building.

Contact Information

France Customer Service Centre:
Honeywell Environmental Controls
ZI de Borly
72, chemin de la Noue
74380 Cranves Sales
France
Tel: 08 10 59 60 63
www.honeywell-confort.com

General Information:
www.homesafety.honeywell.com
www.honeywellanalytics.com
www.honeywell.com

Acts for and on behalf of Life Safety Distribution AG, Javastrasse 2, 8604 Hegnau, Switzerland by its Authorised Representative Honeywell Inc.

Please Note: While efforts have been made to ensure accuracy, no responsibility is accepted for errors or omissions. Data, legislation, and standards may change. Retain product documentation for the lifetime of the product.

Document Reference: MAN0982_Issue 1_01/15_EN © 2015 Honeywell Analytics

PDF preview unavailable. Download the PDF instead.

xs100-man0982-nl01r0115 Adobe PDF Library 11.0 Adobe InDesign CC 2014 (Windows)

Related Documents

Preview Notifier FSP-951-SELFT Intelligent Photoelectric Self-Test Smoke Sensor Installation and Maintenance Instructions
Detailed installation and maintenance instructions for the Notifier FSP-951-SELFT Intelligent Photoelectric Self-Test Smoke Sensor, covering specifications, wiring, testing, and cleaning procedures.
Preview Honeywell IMPACT Wireless Smoke Detector FDC-100: Installation and Maintenance Guide
Comprehensive installation and maintenance instructions for the Honeywell IMPACT Wireless Smoke Detector (Model FDC-100). Learn about product features, technical specifications, app setup, installation, and troubleshooting.
Preview Honeywell SK-DUCT-W Duct Smoke Detector: Installation and Maintenance Manual
Comprehensive installation and maintenance guide for the Honeywell SK-DUCT-W Duct Smoke Detector, covering specifications, installation procedures, wiring, testing, cleaning, sensor replacement, and optional accessories.
Preview Esserbus Transponder IQ8FCT XS | Honeywell Technical Specification
Technical datasheet for the Honeywell Esserbus Transponder IQ8FCT XS, a fire control transponder and technical alarm module for fire safety systems. Details features, specifications, and accessories.
Preview Honeywell Silent Knight 6820/6820EVS Addressable Fire Alarm Control Panel Manual
Comprehensive manual for the Honeywell Silent Knight 6820/6820EVS addressable fire alarm control panel, detailing installation, operation, programming, and system features for fire safety and emergency communication.
Preview Honeywell XLS3000 Intelligent Addressable Fire Alarm System | Datasheet
Discover the Honeywell XLS3000 Intelligent Addressable Fire Alarm System, designed for robust fire detection and life safety in medium to large-scale facilities. This datasheet details its advanced features like FlashScan technology, Intelligent Sensing, modular design, and extensive device support for comprehensive building protection.
Preview Manual de Usuario Honeywell HS-6270: Seguridad y Comodidad para el Hogar
Guía completa para el usuario del sistema Honeywell HS-6270, que cubre la configuración, funciones de seguridad, comunicación y solución de problemas para mejorar la seguridad y la felicidad en el hogar.
Preview Honeywell FAAST Aspirating Smoke Detection Applications Guide
Comprehensive guide to Honeywell's FAAST Aspirating Smoke Detection (ASD) systems, detailing principles, applications in data centers, telecommunications, clean rooms, and duct monitoring, along with installation and maintenance best practices, adhering to EN 54-20, NFPA, and BS 6266 standards.