TOSHIBA AIR CONDITIONER (SPLIT TYPE) Installation Manual
Outdoor Unit
Model names:
- RAV-GM2243AT8P-E
- RAV-GM2243AT8JP-E
- RAV-GM2803AT8P-E
- RAV-GM2803AT8JP-E
For commercial use
Contents
- Accessory parts
- Installation of R32 refrigerant air conditioner
- Installation conditions
- Refrigerant piping
- Air purging
- Electrical work
- Earthing
- Finishing
- Test run
- Annual maintenance
- Air conditioner operating conditions
- Functions to be implemented locally
- Troubleshooting
- Appendix
- Specifications
- Installation check list
Original instruction
Please read this Installation Manual carefully before installing the Air Conditioner.
- This Manual describes the installation method of the outdoor unit.
- For installation of the indoor unit, follow the Installation Manual attached to the indoor unit.
ADOPTION OF R32 REFRIGERANT
This air conditioner adopts the HFC refrigerant (R32) which does not destroy the ozone layer. This outdoor unit is designed exclusively for use with R32 refrigerant. Be sure to use in combination with a R32 refrigerant indoor unit.
Regulation of harmonic current
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1).
Model | Ssc (MVA) |
---|---|
RAV-GM2243AT8(J)P-E | 1.33 |
RAV-GM2803AT8(J)P-E | 1.41 |
This unit complies with EN 61000-3-11. However, the impedance of the power supply system to be connected to the unit at the incoming power point must be less than the Zmax given below. In order to meet this condition, consult with the supply authority as required.
Zmax = 0.65 (Ω)
In addition, it is recommended that voltage drops occurring during the unit's operation in the area at the power input shall be around 3.3% of the nominal power-supply voltage or less.
Center of gravity
Diagram showing center of gravity for the outdoor unit.
CAUTION
Cautions for outdoor unit installation space
- In the event that the outdoor unit is installed in a small space and refrigerant leaks, accumulation of highly concentrated refrigerant may cause a fire hazard. Therefore, be sure to follow the installation space instructions in the Installation Manual, and provide open space on at least one of the four outdoor unit sides.
- In particular, when both the discharge and intake sides face walls and obstacles are also placed on both sides of the outdoor unit, take steps to provide space wide enough for a person to pass (600 mm or more) on one side to prevent leaked refrigerant from accumulating.
Diagram illustrating required clearance around the outdoor unit.
To disconnect the appliance from main power supply
- This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
Do not wash air conditioners with pressure washers.
Electric leaks may cause electric shocks or fires.
1 Accessory parts
Part name | Qty | Shape | Usage |
---|---|---|---|
Installation Manual | 1 | Booklet | For hand this directly to the customer. |
Joint (Ø19.1 – Ø28.6 mm) | 1 | For connecting the pipe | |
Joint (Ø28.6- Ø28.6 mm) | 1 | For connecting the pipe | |
Drain nipple | 1 | ||
Waterproof rubber cap | 5 | ||
Protective bush | 1 | For protecting wires (pipe cover) | |
Guard material for passage part | 1 | For protecting passage part (pipe cover) | |
Rub-Sheet | 1 | For protecting small lizard. | |
Safety Manual | 1 | For hand over directly to the customer. |
INFORMATION
The main pipe on the gas side of this outdoor unit has a diameter of Ø28.6 mm, but a Ø19.1 mm flare connection is used where the valve is connected. Be sure to use the Ø19.1 mm pipe and joint provided as accessories for the pipe connection.
Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being installed in the wrong place.
Before proceeding to weld the refrigerant pipe, be sure to pass nitrogen through the pipe.
Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.
Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.
In the case of a simultaneous double twin system, use indoor unit with the same capacity for all four indoor units.
Model | Branch pipe kit | Combination indoor unit |
---|---|---|
RAV-GM2243 | RBC-DTWP101E | RM56 x 4 units |
RAV-GM2803 | RBC-DTWP101E | RM80 × 4 units |
P.C. Board settings are required for some of the indoor units if they are to be used in a twin, triple or double twin system. Refer to the instructions in the installation manual of the branch pipe kit, and ensure that the settings are selected correctly.
Combination with the indoor units.
Combination with the indoor units is possible only when units with the same type are combined. Combinations of units with different types cannot be used.
The concealed duct high static pressure type is used for a single connection (when connecting a single indoor unit to the outdoor unit).
Required tools / equipment and precautions for use
Prepare the tools and equipment listed in the following table before starting the installation work. Newly prepared tools and equipment must be used exclusively.
Tools / equipment | Use | How to use tools / equipment |
---|---|---|
Gauge manifold Charging hose Charging cylinder | Vacuuming / charging refrigerant and operation check | Conventional tools (R32 or R410A) |
Gas leak detector | Charging refrigerant | Conventional tools (R32 or R410A) |
Vacuum pump | Vacuum drying | Conventional tools (R32 or R410A) |
Vacuum pump with backflow prevention function | Vacuum drying | Usable if the backflow prevention adapter is installed. |
Flare tool | Flare machining of pipes | Conventional tools (R32 or R410A) |
Bender | Bending pipes | Conventional tools (R410A) |
Refrigerant recovery equipment | Refrigerant recovery | Conventional tools (R410A) |
Torque wrench | Tightening flare nuts | Conventional tools (R32 or R410A) |
Pipe cutter | Cutting pipes | Conventional tools (R32 or R410A) |
Refrigerant cylinder | Charging refrigerant | Conventional tools (R32 or R410A) |
Welding machine and nitrogen cylinder | Welding pipes | Conventional tools (R32 or R410A) |
Electronic refrigerant charging scale | Charging refrigerant | Prepared newly (Use for R32 only) |
2 Installation of R32 refrigerant air conditioner
CAUTION
R32 refrigerant air conditioner installation
This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer. Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter the R32 refrigerant air conditioner cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charge port on the main unit and installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for the R32 or R410A refrigerant units. For connecting pipes, use new and clean piping materials with high pressure fittings made for the R32 or R410A only, so that water and/or dust does not enter. When using existing piping, refer to "14. Appendix - [1] Existing piping".
3 Installation conditions
Before installation
Be sure to prepare to the following items before installation.
Item | Length of refrigerant pipe | Height difference (Indoor-outdoor) | Addition of refrigerant at the local site is unnecessary for refrigerant pipe lengths up to 30 m. If the refrigerant pipe length exceeds 30 m, add refrigerant in the amount given in "Charging additional refrigerant". | |
---|---|---|---|---|
connected to indoor/outdoor unit | Outdoor unit: Upper | Outdoor unit: Lower | Indoor unit: Upper | |
5 to 100 m | 30 m | 30 m | 30 m |
Caution during addition of refrigerant.
Charge the refrigerant accurately. Overcharging may cause serious trouble with the compressor.
Do not connect a refrigerant pipe that is shorter than 5 m. This may cause a malfunction of the compressor or other devices.
Airtight test
- Before starting an airtight test, further tighten the spindle valves on the gas and liquid sides.
- Pressurize the pipe with nitrogen gas charged from the service port to the design pressure (4.15 MPa) to conduct an airtight test.
- After the airtight test is completed, evacuate the nitrogen gas.
Air purge
- To purge air, use a vacuum pump.
- Do not use refrigerant charged in the outdoor unit to purge air. (The air purge refrigerant is not contained in the outdoor unit.)
Electrical wiring
Be sure to fix the power wires and indoor/outdoor connecting wires with clamps so that they do not come into contact with the cabinet, etc.
Earthing
WARNING Make sure that proper earthing is provided. Improper earthing may cause an electric shock. For details on how to check earthing, contact the dealer who installed the air conditioner or a professional installation company.
Proper earthing can prevent charging of electricity on the outdoor unit surface due to the presence of a high frequency in the frequency converter (inverter) of the outdoor unit, as well as prevent electric shock. If the outdoor unit is not properly earthed, you may be exposed to an electric shock.
Be sure to connect the earth wire. (grounding work)
Incomplete earthing can cause an electric shock. Do not connect earth wires to gas pipes, water pipes, lightning rods or earth wires for telephone wires.
Test run
Turn on the circuit breaker at least 12 hours before starting a test run to protect the compressor during startup.
ACAUTION Incorrect installation work may result in a malfunction or complaints from customers.
Installation location
WARNING
Install the outdoor unit properly in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury. This outdoor unit has a weight of about 117 kg. Pay special attention when installing the unit onto a wall surface.
CAUTION
Do not install the outdoor unit in a location that is subject to combustible gas leaks. Accumulation of combustible gas around the outdoor unit may cause a fire.
Install the outdoor unit in a location that meets the following conditions after the customer's consent is obtained.
- A well-ventilated location free from obstacles near the air intakes and air discharge.
- A location that is not exposed to rain or direct sunlight.
- A location that does not increase the operating noise or vibration of the outdoor unit.
- A location that does not produce any drainage problems from discharged water.
Do not install the outdoor unit in the following locations.
- A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area) (Special maintenance is required).
- A location subject to oil, vapor, oily smoke, or corrosive gases.
- A location in which organic solvent is used.
- Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air conditioner, it may spontaneously combust and start a fire.
- A location where high-frequency equipment (including inverter equipment, private power generator, medical equipment, and communication equipment) is used (Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due to noise from such equipment).
- A location in which the discharged air of the outdoor unit blows against the window of a neighboring house.
- A location where the operating noise of the outdoor unit is transmitted.
- When the outdoor unit is installed in an elevated position, be sure to secure its feet.
- A location in which drain water poses any problems.
CAUTION
- Install the outdoor unit in a location where the discharge air is not blocked.
- When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building, secure normal fan operation by using a duct or wind shield.
- When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper stairs or rooftop of a building, apply the wind-proofing measures referred to in the following examples.
Diagram showing installation to face the wall.
Diagram showing installation at a right angle to wind direction.
Diagram showing installation to prevent snow accumulation.
Necessary space for installation (Unit: mm)
Obstacle at rear side
Diagrams showing required clearances for single and serial installations with obstacles at the rear.
Obstacle in front
Diagrams showing required clearances for single and serial installations with obstacles in the front.
Obstacle also above unit
Diagram showing required clearance when there is an obstacle above the unit.
Obstacles in both front and rear of unit
Diagrams showing required clearances for standard and serial installations with obstacles in both front and rear.
Serial installation in front and rear
Diagrams showing required clearances for serial installations with obstacles in front and rear.
Installation of outdoor unit
Before installation, check the strength and horizontalness of the base so that abnormal sounds do not emanate.
According to the following base diagram, fix the base firmly with the anchor bolts. (Anchor bolt, nut: M10 x 4 pairs)
Diagram showing base diagram with anchor bolt locations.
As shown in the figure below, install the foundation and vibration-proof rubber pads to directly support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit.
Diagram showing correct and incorrect foundation support.
When installing the foundation for an outdoor unit with downward piping, consider the piping work.
Set the out margin of the anchor bolt to 15 mm or less.
Diagram showing anchor bolt margin.
For reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the cabinet or fan. It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner. For details, contact the dealer.
WARNING
- Be sure to install the outdoor unit in a place able to bear its weight. If strength is insufficient, the unit may fall down resulting in human injury.
- Perform specified installation work to protect against strong wind and earthquakes. If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
When water is to be drained through the drain hose, attach the following drain nipple and waterproof rubber cap, and use the drain hose (Inner dia.: 16 mm) sold on the market. Also seal knockout hole and the screws securely with silicone material, etc., to prevent water from leaking.
Some conditions may cause dewing or dripping of water.
When collectively draining discharged water completely, use a drain pan.
Diagram showing drain nipple and waterproof rubber cap installation.
4 Refrigerant piping
Refrigerant piping
R32 refrigerant
CAUTION
- Incomplete flaring may cause refrigerant gas leakage.
- Do not re-use flares. Use new flares to prevent refrigerant gas leakage.
- Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.
Use the following item for the refrigerant piping.
Material: Seamless phosphorous deoxidized copper pipe.
- Ø6.35, Ø9.52, Ø12.7 Wall thickness 0.8 mm or more
- Ø15.88 Wall thickness 1.0 mm or more
- Ø19.1 Wall thickness 1.2 mm or more
- Ø28.6 (half hard) Wall thickness 1.0 mm or more
REQUIREMENT
When the refrigerant pipe is long, provide support brackets at intervals of 2.5 to 3 m to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.
Remove service panel
Remove the screws at 3 locations and slide the service panel down. Next, detach the right-side claws followed by left-side claws to remove the service panel. When doing this, pulling the service panel towards the front could damage the claws. When attaching the service panel, attach the left claws followed by the right claws and lift the service panel upwards and secure it with screws in the 3 locations.
Knockout of pipe cover
The indoor / outdoor connecting pipes can be connected in 4 directions. Take off the knockout part of the pipe cover through which pipes or wires will pass through the base plate. Detach the pipe cover and tap on the knockout section a few times with the shank of a screwdriver. A knockout hole can easily be punched. After punching out the knockout hole, remove burrs from the hole and then install the supplied protective bush and guard material around the passage hole to protect wires and pipes. Be sure to attach the pipe covers after pipes have been connected. Cut the slits under the pipe covers to facilitate the installation. After connecting the pipes, be sure to mount the pipe cover. The pipe cover is easily mounted by cutting off the slit at the lower part of the pipe cover.
Diagram showing knockout procedure for pipe cover.
Diagram showing installation of protective bush and guard material.
Diagram showing attachment of rubber sheet.
Optional installation parts (Locally procured)
Parts name | Qty |
---|---|
A Liquid side: Ø12.7 mm Gas side: Ø28.6 mm | One each |
B Socket: Ø28.6 - Ø28.6 mm | 1 |
C Pipe insulating material (polyethylene foam, 10 mm thick) | 1 |
D Putty, PVC tape | One each |
Refrigerant piping connection
Flaring
- Cut the pipe with a pipe cutter. Be sure to remove burrs that may cause a gas leak.
- Insert a flare nut into the pipe, and then flare the pipe. Use the flare nuts supplied with the air conditioner or those for R32. Insert a flare nut into the pipe, and flare the pipe. Use the flare nuts supplied with the air conditioner or flare nuts for R32 or R410A. However, the conventional tools can be used by adjusting the projection margin of the copper pipe.
Outer dia. of copper pipe | R32 or R410A tool used | Conventional tool used |
---|---|---|
12.7 | 0 to 0.5 | 1.0 to 1.5 |
19.1 | 1.0 to 1.5 | 1.0 to 1.5 |
Flaring dia. size: A (Unit: mm)
Liquid side | Gas side | ||
---|---|---|---|
Outer diameter | Thickness | Outer diameter | Thickness |
Ø12.7 mm | 0.8 mm | Ø28.6 mm | 1.0 mm (half hard) |
CAUTION
Take note of these 4 important points below for piping work.
- Keep dust and moisture away from inside the connecting pipes.
- Tightly connect the connection between pipes and the unit.
- Evacuate the air in the connecting pipes using a VACUUM PUMP.
- Check for gas leaks at connection points.
Piping connection
Liquid side | Gas side | ||
---|---|---|---|
Outer diameter | Thickness | Outer diameter | Thickness |
Ø12.7 mm | 0.8 mm | Ø28.6 mm | 1.0 mm (half hard) |
CAUTION
Wrap the valves at the gas and the liquid side in wet cloth to keep it cool and prevent the heat from the torch from damaging it when connecting the pipe to the valve on the gas and the liquid line.
Diagram showing pipe connection with wet cloth.
CAUTION
Do not scratch the inner surface of the flared part when removing burrs. Flare processing under the condition of scratches on the inner surface of flare processing part will cause refrigerant gas leak. Check that the flared part is not scratched, deformed, stepped, or flattened, and that there are no chips adhered or other problems, after flare processing. Do not apply refrigerating machine oil to the flare surface.
Connecting the Gas Side Pipe
REQUIREMENT Be sure to use the Ø19.1 mm pipe and joint provided as accessories of the outdoor unit to connect the gas side Ø19.1 mm pipe and Ø28.6 mm pipe.
- When leading out the pipes toward the front, to one of the sides or toward the rear, use the Ø19.1 mm pipe and elbow provided as accessories of the outdoor unit, and adjust the bending direction. Cut the Ø19.1 mm pipe to the required length before using it.
- Align the provided Ø19.1 mm pipe with the pipe lead-out direction, and shape it so that its end comes out from the outdoor unit.
- On the outside of the outdoor unit, use the provided joints, and braze the Ø19.1 mm pipe and Ø28.6 mm pipe.
Diagram showing connection of gas side pipe.
REQUIREMENT Before proceeding to brazing the refrigerant pipe, be sure to pass nitrogen through the pipe to prevent oxidation inside it. If nitrogen is not passed through the pipe, the refrigerating cycle may become clogged by oxidized scales.
Tightening of connecting part
- Align the centers of the connecting pipes and fully tighten the flare nut with your fingers. Then fix the nut with a wrench as shown in the figure and tighten it with a torque wrench.
- As shown in the figure, be sure to use two wrenches to loosen or tighten the flare nut of the valve on the gas side. If you use a single crescent, the flare nut cannot be tightened to the required tightening torque. On the other hand, use a single crescent to loosen or tighten the flare nut of the valve on the liquid side.
Outer dia. of copper pipe | Tightening torque (Unit: N•m) |
---|---|
12.7 mm (diam.) | 50 to 62 |
19.1 mm (diam.) | 100 to 120 |
Branch Pipe
Carry out the refrigerant piping work using the branch pipe kit which is purchased separately. Branching pipe model name RBC-TWP101E, RBC-TRP100E, RBC-DTWP101E
Branch pipe installation
Diagrams illustrating correct and incorrect branch pipe installation.
CAUTION
- Do not cut the service connector cap or cover. The valve may break.
- If applying excessive torque, the nut may break according to some installation conditions.
After the installation work, be sure to check for gas leaks of the pipe connections with nitrogen. Therefore, using a torque wrench, tighten the flare pipe connecting sections that connect the indoor/outdoor units at the specified tightening torque. Incomplete connections may cause not only a gas leak, but also trouble with the refrigeration cycle. Do not apply refrigerant oil to the flared surface.
Length of straight sections on main pipe side of branch pipe
Provide a straight section with a length of at least 500 mm on the main pipe side of the branch pipe. (Same for both liquid side and gas side)
Diagram showing required straight section length.
Refrigerant pipe length
Single
Outdoor unit | Allowable pipe length (m) | Height difference (m) | ||||
---|---|---|---|---|---|---|
Total length l | Minimum | Maximum | Indoor unit: Upper | Outdoor unit: Upper | Indoor-outdoor H | |
GM2243 | 5 to 100 | 5 | 100 | 30 | 30 | 30 |
GM2803 | 5 to 100 | 5 | 100 | 30 | 30 | 30 |
Outdoor unit | Pipe diameter (mm) | Number of bent portions | |
---|---|---|---|
Gas side | Liquid side | ||
GM2243 | Ø28.6 | Ø12.7 | 10 or less |
GM2803 | Ø28.6 | Ø12.7 | 10 or less |
Figure of Single
Simultaneous twin, triple
Outdoor unit | Allowable pipe length (m) | Height difference (m) | Number of bent portions | ||||
---|---|---|---|---|---|---|---|
Total length l | Branch piping | Indoor unit: Upper | Outdoor unit: Upper | Indoor-indoor (Δh) | |||
GM2243 | 100 | 20 | 10 | 30 | 30 | 0.5 | 10 or less |
GM2803 | 100 | 20 | 10 | 30 | 30 | 0.5 | 10 or less |
Outdoor unit | Pipe diameter (mm) | Number of bent portions | |||
---|---|---|---|---|---|
Gas side | Liquid side | Main pipe Gas side | Liquid side | ||
GM2243 | Ø28.6 | Ø12.7 | Ø15.9 | Ø9.5 | 10 or less |
GM2803 | Ø28.6 | Ø12.7 | Ø15.9 | Ø9.5 | 10 or less |
Figure of Simultaneous twin
Figure of Simultaneous triple
Simultaneous double twin
Outdoor unit | Allowable pipe length (m) | Height difference (m) | |||||
---|---|---|---|---|---|---|---|
Total length | Branch piping | Indoor unit: Upper | Outdoor unit: Upper | Indoor-indoor (Δh) | |||
GM2243 | 100 | 15 | 20 | 6 | 30 | 30 | 0.5 |
GM2803 | 100 | 15 | 20 | 6 | 30 | 30 | 0.5 |
Outdoor unit | Pipe diameter (mm) | Number of bent portions | |||
---|---|---|---|---|---|
Gas side | Liquid side | Main pipe Gas side | Liquid side | ||
GM2243 | Ø28.6 | Ø12.7 | l2, l3: Ø15.9 l4 to l7: Ø12.7 | l2, l3: Ø9.5 l4 to l7: Ø6.4 | 10 or less |
GM2803 | Ø28.6 | Ø12.7 | l2, l3: Ø15.9 l4 to l7: Ø12.7 | l2, l3: Ø9.5 l4 to l7: Ø6.4 | 10 or less |
Figure of Simultaneous double twin
5 Air purging
Airtight Test
After completing the refrigerant piping work, perform an airtight test. Connect a nitrogen gas cylinder and pressurize the pipes with nitrogen gas as follows to conduct the airtight test.
Diagram showing airtight test setup.
CAUTION
Never use oxygen, flammable gas, or noxious gas for the airtight test.
Gas leak check
- Pressurize to 0.5 MPa (5 kg/cm²G) for 5 minutes or longer. Major leaks can be discovered.
- Pressurize to 1.5 MPa (15 kg/cm²G) for 5 minutes or longer. Micro leaks can be discovered.
- Pressurize to 4.15 MPa (42 kg/cm²G) for 24 hours. (However, note that when the ambient temperature differs during pressurization and after 24 hours, the pressure will change by approximately 0.01 MPa (0.1 kg/cm²G) per 1°C, so this should be compensated.)
If the pressure drops in steps 1 through 3, check the connections for leakage. Check for leaks with foaming liquid, etc., take steps to fix the leaks such as brazing the pipes again and tightening the flare nuts, and then perform the airtight test again. After the airtight test is completed, evacuate the nitrogen gas.
Air purge
With respect to the preservation of the terrestrial environment, adopt "Vacuum pump" to purge air (Evacuate air in the connecting pipes) when installing the unit.
Do not discharge the refrigerant gas to the atmosphere to preserve the terrestrial environment. Use a vacuum pump to discharge the air (nitrogen, etc.) that remains in the set. If air remains, the capacity may decrease.
For the vacuum pump, be sure to use one with a backflow preventer so that the oil in the pump does not backflow into the pipe of the air conditioner when the pump stops. (If oil in the vacuum pump is put in an air conditioner including R32, it may cause trouble with the refrigeration cycle.)
Diagram showing air purge setup.
Vacuum pump
As shown in the figure, connect the charge hose after the manifold valve is closed completely.
Attach the connecting port of the charge hose with a projection to push the valve core (setting pin) to the charge port of the set.
Open Handle Low fully.
Turn ON the vacuum pump. (*1)
Loosen the flare nut of the packed valve (Gas side) a little to check that the air passes through. (*2)
Retighten the flare nut.
Execute vacuuming until the compound pressure gauge indicates -101 kPa (-76 cmHg). (*1)
Close Handle Low completely.
Turn OFF the vacuum pump.
Leave the vacuum pump as it is for 1 or 2 minutes, and check that the indicator of the compound pressure gauge does not return.
Open the valve stem or valve handle fully. (First, at liquid side, then gas side)
Disconnect the charge hose from the charge port.
Tighten the valve and caps of the charge port securely.
*1: Use the vacuum pump, vacuum pump adapter, and gauge manifold correctly referring to the manuals supplied with each tool before using them. Check that the vacuum pump oil is filled up to the specified line of the oil gauge.
*2: When air is not charged, check again whether the connecting port of the discharge hose, which has a projection to push the valve core, is firmly connected to the charge port.
Pump down process
- Turn off the Air Conditioner system.
- Connect the charge hose from the manifold valve to the service port of the packed valve at gas side.
- Turn on the Air Conditioner system in cooling operation more than 10 minutes.
- Check the operating pressure of the system should be normal value. (Ref. with product specification)
- Release the valve rod cap of both service valves.
- Use the Hexagon wrench to turning the valve rod of Liquid side fully close. (*Make sure no entering air into the system)
- Continue operate Air Conditioner system until the gauge of manifold dropped into the range of 0.5 - 0 kgf/cm².
- Use the Hexagon wrench to turning the valve rod of Gas side fully close. And turn off the Air Conditioner system immediately thereafter.
- Remove the gauge manifold from the service port of the packed valve.
- Securely tighten the valve rod cap to the both service valves.
CAUTION
Should be check the compressor operating condition while pumping down process. It must not any abnormal sound, more vibration. It is abnormal condition appears and must turn off the Air Conditioner immediately.
How to open the valve
Fully open the valves of the outdoor unit. (First fully open the valve on the liquid side, and then fully open the valve on the gas side.)
* Do not open or close the valves when the ambient temperature is -20°C or less. Doing so may damage the valve O-rings and result in refrigerant leakage.
Liquid side
Open the valve with a 4 mm hexagon wrench.
Gas side
Diagram showing valve operation.
Valve handling precautions
- Open the valve stem until it strikes the stopper. It is unnecessary to apply further force.
- Securely tighten the cap with a torque wrench.
Valve size | Cap tightening torque |
---|---|
Ø12.7 mm | 50 to 62 N-m (5.0 to 6.2 kgf.m) |
Ø19.1 mm | 100 to 120 N-m (10 to 12 kgf.m) |
Charge port | 14 to 18 N•m (1.4 to 1.8 kgf・m) |
Insulating the Pipes
The temperatures at both the liquid side and gas side will be low during cooling so in order to prevent condensation, be sure to insulate the pipes at both of these sides. Insulate the pipes separately for the liquid side and gas side. Insulate the branch pipes by following the instructions in the installation manual provided with the branch pipe kit. Use the insulating material provided as an accessory to insulate the Ø19.1 mm pipe at the gas side. Seal the area where the Ø19.1 mm pipe and Ø22.2 to Ø28.6 mm pipe are connected so that no gaps are left.
REQUIREMENT Be sure to use an insulating material which can withstand temperatures above 120°C for the gas side pipe since this pipe will become very hot during heating operations.
Replenishing refrigerant
This model is a 30 m chargeless type that does not need to have its refrigerant replenished for refrigerant pipes up to 30 m. When a refrigerant pipe longer than 30 m is used, add the specified amount of refrigerant.
Refrigerant replenishing procedure
- After vacuuming the refrigerant pipe, close the valves and then charge the refrigerant while the air conditioner is not working.
- When the refrigerant cannot be charged to the specified amount, charge the required amount of refrigerant from the charge port of the valve on the gas side during cooling.
Requirement for replenishing refrigerant
Replenish liquid refrigerant. When gaseous refrigerant is replenished, the refrigerant composition varies, which disables normal operation.
Charging additional refrigerant
Formula for calculating the amount of additional refrigerant (Formula will differ depending on the diameter of the liquid connecting side pipe.) l₁ to l₇ are the lengths of the pipes shown in the figures above (unit: m).
Single
Diameter of connecting pipe (liquid side) | Amount of additional refrigerant per meter (g/m) | Amount of additional refrigerant (g) |
---|---|---|
α | Amount of refrigerant charged for main pipe | |
Ø12.7 | 80 | α x (l-30) |
Simultaneous twin
Diameter of connecting pipe (liquid side) | Amount of additional refrigerant per meter (g/m) | Amount of additional refrigerant (g) | |
---|---|---|---|
α | β | Amount of refrigerant charged for main pipe + amount of refrigerant charged for branch piping | |
Ø12.7 | 80 | 40 | α x (l₁-28) + β x (l₂ + l₃-4) |
Figure of Simultaneous twin
Simultaneous triple
Diameter of connecting pipe (liquid side) | Amount of additional refrigerant per meter (g/m) | Amount of additional refrigerant (g) | |
---|---|---|---|
α | β | Amount of refrigerant charged for main pipe + amount of refrigerant charged for branch piping | |
Ø12.7 | 80 | 40 | α x (l₁-28) + β x (l₂ + l₃ + l₄-6) |
Figure of Simultaneous triple
Simultaneous double twin
Outdoor unit | Diameter of connecting pipe (liquid side) | Amount of additional refrigerant per meter (g/m) | Amount of additional refrigerant (g) | ||||
---|---|---|---|---|---|---|---|
α | β | γ | Amount of refrigerant charged for main pipe + amount of refrigerant charged for first branch piping + amount of refrigerant charged for second branch piping | ||||
GM2243 | Ø12.7 | 09.5 | Ø6.4 | 80 | 40 | 20 | α x (l₁-28) + β x (l₂ + l₃ - 4) + γ x (l₄ + l₅ + l₆ + l₇) |
GM2803 | Ø12.7 | 09.5 | Ø9.5 | 80 | 40 | 40 | α x (l₁-28) + β x (l₂ + l₃ - 4) + γ x (l₄ + l₅ + l₆ + l₇) |
Figure of Simultaneous double twin
Gas leak inspection
Use a leak detector manufactured specially for HFC refrigerant (R32, R410A, R134a, etc.) to perform the R32 gas leak inspection. * Leak detectors for conventional HCFC refrigerant (R22, etc.) cannot be used, as the sensitivity drops to approximately 1/40 when used for HFC refrigerant. • R32 has a high working pressure, so failure to perform the installation work properly may result in gas leaks such as when the pressure rises during operation. Be sure to perform leak tests on the piping connections.
Diagram showing gas leak inspection points.
6 Electrical work
WARNING
- Using the specified wires, ensure that the wires are connected, and fix wires securely so that the external tension to the wires does not affect the connecting part of the terminals. Incomplete connection or fixation may cause a fire, etc.
- Be sure to connect the earth wire. (Grounding work) Incomplete earthing may lead to electric shock. Do not connect earth wires to gas pipes, water pipes, lightning rods or earth wires for telephone wires.
- The appliance shall be installed in accordance with national wiring regulations. Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
Remove the service panel, and the terminal cover. A conduit pipe can be installed through the hole for wiring. If the hole size does not fit the wiring pipe to be used, drill the hole again to an appropriate size. Be sure to clamp the power wires and indoor/outdoor connecting wires with a cord clamp along the connecting pipe so that the wires do not touch the compressor or discharge pipe. (The compressor and the discharge pipe become hot.)
Diagram showing electrical wiring connections.
CAUTION An installation fuse must be used for the power supply line of this air conditioner. Incorrect / incomplete wiring may lead to an electrical fire or smoke. Prepare an exclusive power supply for the air conditioner. This product can be connected to the mains power. Fixed wire connections: A switch that disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring. Be sure to use the cord clamps attached to the product. Do not damage or scratch the conductive core or inner insulator of the power and indoor/outdoor connecting wires when peeling them. Use the power and indoor/outdoor connecting wires with specified thicknesses, specified types and protective devices required.
Wiring between indoor unit and outdoor unit
The dashed lines show on-site wiring.
Diagram showing wiring between indoor and outdoor units.
Power and Wiring Specifications
Model (RAV-) | Power supply | Maximum running current | Installation fuse rating | Power wire* | Indoor/outdoor connecting wires* |
---|---|---|---|---|---|
Number of wire x wire size | Number of wire x wire size | ||||
GM2243 type | 380-415 V 3N ~ 50 Hz, 380 V 3N~ 60 Hz | 16 A | 17 A | 5 x 2.5 mm² or more (H07 RN-F or 60245 IEC 66) | 4 x 1.5 mm² or more (H07 RN-F or 60245 IEC 66) |
GM2803 type | 380-415 V 3N ~ 50 Hz, 380 V 3N~ 60 Hz | 25 A | 25 A | 5 x 2.5 mm² or more (H07 RN-F or 60245 IEC 66) | 4 x 1.5 mm² or more (H07 RN-F or 60245 IEC 66) |
* For the service device (such as emergency breaker), incorrect connection may cause a failure.
Connect the indoor/outdoor connecting wires to the identical terminal numbers on the terminal block of each unit. Incorrect connection may cause a failure.
How to wire
- Connect the indoor/outdoor connecting wires to the terminal as identified with their respective numbers on the terminal block of the indoor and outdoor units. H07 RN-F or 60245 IEC 66 (1.5 mm² or more)
- When connecting the connecting wire to the outdoor unit, prevent water from coming into the outdoor unit.
- Secure the power supply wire and indoor/outdoor connecting wires using the cord clamp of the outdoor unit.
- For interconnecting wires, do not use a wire joined to another on the way. Use wires long enough to cover the entire length.
- Wiring connections differ in conformance to EMC standards, depending whether the system is twin, triple or double twin. Connect wires according to respective instructions.
CAUTION
Fuse must be used in installation for the power supply line of this air conditioner. Incorrect/incomplete wiring may lead to an electrical fire or smoke. Prepare an exclusive power supply for the air conditioner. This product can be connected to the mains power. Fixed wire connections: A switch that disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.
Wiring diagram
Diagrams for single system, simultaneous twin system, simultaneous triple and double twin system wiring.
7 Earthing
WARNING
Be sure to connect the earth wire. (Grounding work) Incomplete earthing may cause an electric shock.
Connect the earth wire properly following applicable technical standards. Connecting the earth wire is essential to preventing electric shock and to reducing noise and electrical charges on the outdoor unit surface due to the high-frequency wave generated by the frequency converter (inverter) in the outdoor unit. If you touch the charged outdoor unit without an earth wire, you may experience an electric shock.
8 Finishing
After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, cover them with finishing tape and clamp them to the wall with off-the-shelf support brackets or their equivalent. Keep the power wires and system interconnection wires off the valve on the gas side or pipes that have no heat insulator.
9 Test run
- Turn on the circuit breaker at least 12 hours before starting a test run to protect the compressor during startup. To protect the compressor, power is supplied from the 380-415 VAC input to the unit to preheat the compressor.
- Check the following before starting a test run:
- That all pipes are connected securely without leaks.
- That the valve of gas and liquid side are full open. If the compressor is operated with the valve closed, the outdoor unit will become overpressurized, which may damage the compressor or other components. If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may cause a burst or injury.
- Operate the air conditioner in the correct procedure as specified in the Owner's Manual.
10 Annual maintenance
For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor / outdoor units are strongly recommended. As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor / outdoor units will need to be cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified service person. Failure to clean the indoor / outdoor units regularly will result in poor performance, icing, water leaking and even compressor failure.
11 Air conditioner operating conditions
For proper performance, operate the air conditioner under the following temperature conditions:
Dry bulb temp. | Wet bulb temp. | |
---|---|---|
Cooling operation | -20 °C to 46 °C | -27 °C to 15 °C |
Heating operation | -20 °C to 46 °C | -27 °C to 15 °C |
If air conditioner is used outside of the above conditions, safety protection may work.
12 Functions to be implemented locally
Handling existing pipe (Refer to 14 Appendix)
When using the existing pipe, carefully check for the following:
- Wall thickness (within the specified range)
- Scratches and dents
- Water, oil, dirt, or dust in the pipe
- Flare looseness and leakage from welds
- Deterioration of copper pipe and heat insulator
Cautions for using existing pipe
- Do not reuse a flare nut to prevent gas leaks. Replace it with the supplied flare nut and then process it to a flare.
- Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean. If discolored oil or much residue is discharged, wash the pipe.
- Check welds, if any, on the pipe for gas leaks.
When the pipe corresponds to any of the following, do not use it. Install a new pipe instead.
- The pipe has been opened (disconnected from indoor unit or outdoor unit) for a long period.
- The pipe has been connected to an outdoor unit that does not use refrigerant R22, R410A or R407C.
- The existing pipe must have a wall thickness equal to or larger than the following thicknesses.
Reference outside diameter (mm) | Wall thickness (mm) | Material |
---|---|---|
6.4 | 0.8 | |
9.5 | 0.8 | |
12.7 | 0.8 | |
15.9 | 1.0 | Half hard |
19.1 | 1.2 | |
22.2 | 1.0 | |
28.6 | 1.0 | Half hard |
Do not use any pipe with a wall thickness less than these thicknesses due to insufficient pressure capacity.
Refrigerant recovery
When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit, the recovery operation can be performed by operating the SW01 and SW02 switches on the P.C. Board of the outdoor unit. A cover for the electric parts has been installed in order to provide protection from electric shocks while work is being performed. Operate the service switches and check the LED displays with this electric parts cover in place. Do not remove this cover while the power is still on. DANGER The entire P.C. Board of this air conditioner system is a high-voltage area. When operating the service switches with the power of the system left on, wear electrically insulated gloves.
Diagram showing LED displays and service switches.
There are four LEDs display patterns. O: ON, : OFF, : Rapid flashing (5 times/sec.), ◇: Slow flashing (1 time/sec.)
Diagram showing LED display initial status.
In the initial LED display status, D805 is lighted as shown on the right. If the initial status is not established (if D805 is flashing), hold down the SW01 and SW02 service switches simultaneously for at least 5 seconds to return the LED displays to the initial status.
Diagram showing LED displays indicated when step 3 is taken.
Diagram showing LED displays indicated when step 6 is taken.
In order to reduce standby power, the LED indication may be turned off even when the power is on. When either SW01 or SW02 is pressed, the LED is displayed.
Existing piping
Steps taken to support existing piping
- Set the circuit breaker to the ON position to turn on the power.
- Check that the LED displays are placed in their initial status. If not, place them in the initial status.
- Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 5)
- Press SW01 four times to set the LED displays (D800 to D805) to the "LED displays for existing piping settings" shown below. (Fig. 6)
Diagram showing LED displays indicated when step 3 is taken.
Diagram showing LED displays for existing piping settings.
- Press SW02 to set D805 to rapid flashing. (Each time SW02 is pressed, D805 is switched between rapid flashing and OFF.) (Fig. 7)
- Hold down SW02 for at least 5 seconds, and check that D804 flashes slowly and that D805 lights. (Fig. 8)
Diagram showing LED displays indicated when step 5 is taken.
Diagram showing LED displays indicated when step 6 is taken.
- Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status. The existing piping is now supported by taking the above steps. In this status, the heating capacity may decrease during heating depending on the outside air temperature and indoor temperature.
* If there is any reason to doubt whether establishing support was successful in the course of this operation, hold down SW01 and SW02 simultaneously for at least 5 seconds to return to the initial status, and then repeat the setting steps.
How to check the existing piping settings
You can check whether the existing piping settings are enabled.
- Check that the LED displays are placed in their initial status. If not, place them in the initial status.
- Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 9)
- Press SW01 four times to set the LED displays (D800 to D805) to the "LED displays for existing piping settings" shown below. If the setting is enabled, D802 lights and D804 and D805 flash rapidly. (Fig. 10)
Diagram showing LED displays indicated when step 2 is taken.
Diagram showing LED displays for existing piping settings.
- Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
When restoring the factory defaults
To restore the factory defaults in situations such as when relocating the units, follow the steps below.
- Check that the LED displays are placed in their initial status. If not, place them in the initial status.
- Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 11)
- Press SW01 20 times to set the LED displays (D800 to D805) to the "LED displays restored to factory defaults" shown below. (Fig. 12)
Diagram showing LED displays indicated when step 2 is taken.
Diagram showing LED displays restored to factory defaults.
- Hold down SW02 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 13)
- Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
Diagram showing LED displays indicated when step 4 is taken.
13 Troubleshooting
You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. Board of the outdoor unit in addition to using the check codes displayed on the wired remote controller of the indoor unit. Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote controller of the indoor unit are described in the Installation Manual of the indoor unit.
LED displays and check codes
No. | Error | LED (D800-D805) | Display | |||||
---|---|---|---|---|---|---|---|---|
D800 | D801 | D802 | D803 | D804 | D805 | |||
1 | Normal | O | O | O | O | O | O | |
2 | Discharge temperature sensor (TD) error | O | O | O | O | O | ||
3 | Heat exchanger temperature sensor (TE) error | O | O | O | O | O | ||
4 | Heat exchanger temperature sensor (TL) error | O | O | O | O | O | ||
5 | Outside temperature sensor (TO) error | O | O | O | O | O | ||
6 | Suction temperature sensor (TS) error | O | O | O | O | O | ||
7 | Heatsink temperature sensor (TH) error | O | O | O | O | O | ||
8 | Miss-mounting of sensor (TE, TS) | O | O | O | O | O | O | |
9 | EEPROM error | O | O | O | O | O | O | |
10 | Compressor breakdown | O | O | O | O | O | O | |
11 | Compressor lock | O | O | O | O | O | O | |
12 | Current detection circuit error | O | O | O | O | O | O | |
13 | Case thermostat activated | O | O | O | O | O | O | |
14 | Unset model type | O | O | O | O | O | O | |
15 | Communication error between MCUs | O | O | O | O | O | O | |
16 | Discharge temperature sensor error | O | O | O | O | O | O | |
17 | High pressure SW error | O | O | O | O | O | O | |
18 | Power supply voltage error | O | O | O | O | O | O | |
19 | Heatsink overheating error | O | O | O | O | O | O | |
20 | Gas leak detected | O | O | O | O | O | O | |
21 | 4-way valve reversal error | O | O | O | O | O | O | |
22 | High pressure protective activated | O | O | O | O | O | O | |
23 | Fan system error | O | O | O | O | O | O | |
24 | Compressor driver device short circuit | O | O | O | O | O | O | |
25 | Position detection circuit error | O | O | O | O | O | O |
O: ON, : OFF, Rapid flashing (5 times/sec.)
14 Appendix
[1] Existing piping
Work instructions
The existing R22 and R407C piping can be reused for our digital inverter R32 product installations.
WARNING
Confirming the existence of scratches or dents on the existing pipes and confirming the reliability of the pipe strength are conventionally referred to the local site.
If the specified conditions can be cleared, it is possible to update existing R22 and R407C pipes to those for R32 models.
Basic conditions needed to reuse existing pipes
Check and observe the presence of three conditions in the refrigerant piping works.
- Dry (There is no moisture inside of the pipes.)
- Clean (There is no dust inside of the pipes.)
- Tight (There are no refrigerant leaks.)
Restrictions for use of existing pipes
In the following cases, the existing pipes should not be reused as they are. Clean the existing pipes or exchange them with new pipes.
- When a scratch or dent is heavy, be sure to use new pipes for the refrigerant piping works.
- When the existing pipe thickness is thinner than the specified "Pipe diameter and thickness," be sure to use new pipes for the refrigerant piping works.
* The operating pressure of R32 is high. If there is a scratch or dent on the pipe or a thinner pipe is used, the pressure strength may be inadequate, which may cause the pipe to break in the worst case.
Pipe diameter and thickness (mm) | Material | |
---|---|---|
Reference outside diameter (mm) | Wall thickness (mm) | |
6.4 | 0.8 | |
9.5 | 0.8 | |
12.7 | 0.8 | |
15.9 | 1.0 | Half hard |
19.1 | 1.2 | |
22.2 | 1.0 | |
28.6 | 1.0 | Half hard |
If the pipe diameter is Ø12.7 mm or less and the thickness is less than 0.7 mm, be sure to use new pipes for the refrigerant piping works.
3. When the outdoor unit was left with the pipes disconnected, or the gas leaked from the pipes and the pipes were not repaired and refilled. There is the possibility of rain water or air, including moisture, entering the pipe.
4. When refrigerant cannot be recovered using a refrigerant recovery unit. There is the possibility that a large quantity of dirty oil or moisture remains inside the pipes.
5. When a commercially available dryer is attached to the existing pipes. There is the possibility that copper green rust has been generated.
6. When the existing air conditioner is removed after refrigerant has been recovered. Check if the oil is judged to be clearly different from normal oil. • The refrigerator oil is copper rust green in color: There is the possibility that moisture has mixed with the oil and rust has been generated inside the pipe. • There is discolored oil, a large quantity of residue, or a bad smell. A large quantity of shiny metal dust or other wear residue can be seen in the refrigerant oil.
7. When the existing air conditioner has a history of the compressor failing and being replaced. • When discolored oil, a large quantity of residue, shiny metal dust, or other wear residue or mixture of foreign matter is observed, trouble will occur.
8. When temporary installation and removal of the air conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air conditioner is other than the following oil (Mineral oil), Suniso, Freol-S, MS (Synthetic oil), alkyl benzene (HAB, Barrel-freeze), ester series, PVE only of ether series. • The winding-insulation of the compressor may deteriorate.
NOTE The above descriptions are results have been confirmed by our company and represent our views on our air conditioners, but do not guarantee the use of the existing pipes of air conditioners that have adopted R32 or R410A in other companies.
Branching pipe for simultaneous operation system
In the concurrent twin system, when has specified that branching pipe is to be used, it can be reused. Branching pipe model name: RBC-TWP101E, RBC-TRP100E, RBC-DTWP101E On the existing air conditioner for simultaneous operation system (twin, triple, double twin system), there are cases of branch pipes being used that have insufficient compressive strength. In such case, please change the piping to a branch pipe for R32 or R410A.
Curing of pipes
When removing and opening the indoor or outdoor unit for a long time, cure the pipes as follows: Otherwise rust may be generated when moisture or foreign matter due to condensation enters the pipes. The rust cannot be removed by cleaning, and new pipes are necessary.
Placement location | Term | Curing manner |
---|---|---|
Outdoors | 1 month or more | Pinching |
Outdoors | Less than 1 month | Pinching or taping |
Indoors | Every time |
Diagram showing pipe curing methods.
[2] Minimum floor area: Amin (m²)
Diagram showing relationship between refrigerant quantity and minimum floor area.
M (kg) | Amin (m²) | Total Piping refrigerant quantity* unit | Floor standing mounted unit Amin (m²) | Wall mounted unit Amin (m²) | Ceiling mounted unit Amin (m²) |
---|---|---|---|---|---|
30 | 5.08 | 214.51 | 23.83 | 15.96 | |
31 | 5.16 | 221.43 | 24.60 | 16.47 | |
32 | 5.24 | 228.46 | 25.38 | 16.99 | |
33 | 5.32 | 235.60 | 26.18 | 17.52 | |
34 | 5.4 | 242.85 | 26.98 | 18.06 | |
35 | 5.48 | 250.21 | 27.80 | 18.61 | |
36 | 5.56 | 257.68 | 28.63 | 19.17 | |
37 | 5.64 | 265.25 | 29.47 | 19.73 | |
38 | 5.72 | 272.94 | 30.33 | 20.30 | |
39 | 5.8 | 280.74 | 31.19 | 20.88 | |
40 | 5.88 | 288.65 | 32.07 | 21.47 | |
41 | 5.96 | 296.67 | 32.96 | 22.07 | |
42 | 6.04 | 304.79 | 33.87 | 22.67 | |
43 | 6.12 | 313.03 | 34.78 | 23.28 | |
44 | 6.2 | 321.38 | 35.71 | 23.90 | |
8HP | 45 | 6.28 | 329.84 | 36.65 | 24.53 |
10HP | 46 | 6.36 | 338.40 | 37.60 | 25.17 |
47 | 6.44 | 347.08 | 38.56 | 25.82 | |
48 | 6.52 | 355.87 | 39.54 | 26.47 | |
49 | 6.6 | 364.76 | 40.53 | 27.13 | |
50 | 6.68 | 373.77 | 41.53 | 27.80 | |
51 | 6.76 | 382.88 | 42.54 | 28.48 | |
52 | 6.84 | 392.11 | 43.57 | 29.17 | |
53 | 6.92 | 401.45 | 44.61 | 29.86 | |
54 | 7 | 410.89 | 45.65 | 30.56 | |
55 | 7.08 | 420.45 | 46.72 | 31.27 | |
56 | 7.16 | 430.11 | 47.79 | 31.99 | |
57 | 7.24 | 439.89 | 48.88 | 32.72 | |
58 | 7.32 | 449.77 | 49.97 | 33.45 | |
59 | 7.4 | 459.77 | 51.09 | 34.20 | |
60 | 7.48 | 469.87 | 52.21 | 34.95 |
* Total refrigerant quantity: Refrigerant quantity precharged at factory + Additional refrigerant quantity charged during installation
Diagram showing relationship between refrigerant quantity and minimum floor area.
15 Specifications
Model | Sound pressure level (dB(A)) | Weight (kg) | |
---|---|---|---|
Cooling | Heating | ||
RAV-GM2243AT8P-E | 58 | 60 | 117 |
RAV-GM2243AT8JP-E | 58 | 60 | 117 |
RAV-GM2803AT8P-E | 61 | 63 | 117 |
RAV-GM2803AT8JP-E | 61 | 63 | 117 |
Product information of ecodesign requirements. (Regulation (EU) 2016/2281) http://ecodesign.toshiba-airconditioning.eu/en
Declaration of conformity
Manufacturer: CARRIER AIR CONDITIONING (THAILAND) CO., LTD. 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANGPATHUMTHANI, PATHUMTHANI 12000, THAILAND
TCF holder: Carrier Solutions UK Ltd. Porsham Close, Belliver Industrial Estate, PLYMOUTH, Devon, PL6 7DB, United Kingdom
Hereby declares that the machinery described below:
Generic Denomination: Air Conditioner
Model / type: RAV-GM2243AT8P-E, RAV-GM2243AT8JP-E RAV-GM2803AT8P-E, RAV-GM2803AT8JP-E
Commercial name: Digital Inverter Series Air Conditioner
Complies with the provisions of the Machinery Directive (Directive 2006/42/EC) and the regulations transposing into national law
Name: Kazunari Watanabe Position: GM, Quality Assurance Dept. Date: 18 Nov, 2024 Place Issued: Thailand
NOTE This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer's consent.
Declaration of conformity
Manufacturer: CARRIER AIR CONDITIONING (THAILAND) CO., LTD. 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANGPATHUMTHANI, PATHUMTHANI 12000, THAILAND
TCF holder: Carrier RLC Europe S.A.S Immeuble Le Cristalia 3 rue Joseph Monier 92500 Rueil-Malmaison FRANCE
Hereby declares that the machinery described below:
Generic Denomination: Air Conditioner
Model / type: RAV-GM2243AT8P-E, RAV-GM2243AT8JP-E RAV-GM2803AT8P-E, RAV-GM2803AT8JP-E
Commercial name: Digital Inverter Series Air Conditioner
Complies with the provisions of the Supply of Machinery (Safety) Regulations 2008
Name: Kazunari Watanabe Position: GM, Quality Assurance Dept. Date: 18 Nov, 2024 Place Issued: Thailand
NOTE This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer's consent.
Warnings on refrigerant leakage
Check of concentration limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R32 which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R32 is almost non-existent.
If a conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg) ≤ Concentration limit (kg/m³)
Min. volume of the indoor unit installed room (m³)
Refrigerant Concentration Limit shall be in accordance with local regulations.
16 Installation check list
After finishing installation work, please check items below and hand this sheet to user to keep it in a safe place together with Owner and Installation Manuals
Note: Please put a mark "✔" in the box you checked.
Check items | Symptom | Check | Remark: All check items, please refer procedure from manufacturing Installation Manual |
---|---|---|---|
Piping work Connecting pipes are cleaned and no dent | Insufficient Air conditioner capacity | Check | |
Use vacuum pump for completed vacuuming | Compressor malfunction | Check | |
No any gas leakage or clogging is found | Compressor rupture or Burst | Check | |
Service valves are fully open before operation | Check | ||
Wiring work Electrical wires are connected correctly | Burnt out, No operation | Check | |
Use breaker to connect to main power supply | Burnt out, No abnormal protection | Check | |
Wiring insulators are in good condition | Burnt out, Electrical leakage | Check | |
Use the specified size/rating wires | Burnt out | Check | |
Ground wire must be Installation per manufacturing Installation Manual | Electrical leakage or shock | Check | |
Drainage work Drain hose is properly connected | Water leakage or dropping | Check | |
Drain hose is well insulated | Water or dew dropping | Check |
Model name
Check date
Checked by
File Info : application/pdf, 26 Pages, 10.31MB
DocumentDocumentReferences
Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)Related Documents
![]() |
Toshiba R32 RAV Outdoor Conversion for R410a Updated: Product Bulletin Product bulletin detailing the conversion of Toshiba R32 RAV Digital and Super Digital Inverter outdoor units for use with R410a refrigerant, including guidance and technical specifications compliant with F-Gas regulations. |
![]() |
RAV Systeme Classic Serie Air Conditioning Product Catalog 2025 Comprehensive product catalog for RAV Systeme's Classic Series air conditioning units, featuring Toshiba HVAC technology. Details include technical specifications, indoor and outdoor unit options, features, dimensions, and accessories. |
![]() |
TOSHIBA R-32 Digital Inverter Heat Pumps Product Bulletin Product bulletin detailing TOSHIBA's new R-32 Digital Inverter heat pumps for light commercial applications, including specifications for various indoor unit types like Compact Cassette, 4-Way Cassette, Slim Ducted, and Ducted systems, as well as twin system configurations. |
![]() |
TOSHIBA Digital Inverter R32 Light Commercial System - Engineering Data Book & Specifications Comprehensive engineering data book and technical specifications for TOSHIBA Digital Inverter R32 Light Commercial Air Conditioning Systems. Includes detailed performance data, dimensions, wiring diagrams, and model information for various indoor and outdoor units. |
![]() |
Toshiba Air Conditioner Installation Manual This installation manual provides detailed instructions for the proper installation of Toshiba split-type air conditioners, specifically the R32 refrigerant models in the RAV-HM_FT series. It covers safety precautions, required tools, installation steps, electrical connections, and testing procedures to ensure safe and efficient operation. |
![]() |
Toshiba Air Conditioner Owner's Manual - RAV-HM Series Owner's manual for Toshiba RAV-HM series concealed duct type air conditioners, covering operation, maintenance, troubleshooting, and specifications. Includes model details for RAV-HM561BTP-E through RAV-HM1601BTP-E. |
![]() |
Toshiba Air Conditioner Owner's Manual for Wireless Remote Controller This manual provides comprehensive instructions for the Toshiba Air Conditioner's wireless remote controller, covering setup, operation, maintenance, and troubleshooting for indoor units. It details various modes like cooling, heating, fan, dry, auto, Hi POWER, and QUIET operations, along with timer functions and group control. |
![]() |
Toshiba Air Conditioner Owner's Manual for Wireless Remote Controller Comprehensive owner's manual for Toshiba split-type air conditioners with wireless remote control. Covers installation, operation, maintenance, troubleshooting, and specifications for models like RAV-HM301KRTP-E. |