Durastar Single Zone Outdoor Unit Split-Style Air Conditioner Installation Manual

Models: DRA1H06S2A, DRA1U09S2A, DRA1H09S2A, DRA1U12S2A, DRA1H12S2A, DRA1U18S2A, DRA1H18S2A, DRA1U24S2A, DRA1H24S2A, DRA1H33S2A

Refrigerant: R-454B

Voltage: 208/230V 1ph 60 HZ

Introduction

To ensure proper installation and operation of your Durastar air conditioner, please read this manual carefully. If you received a damaged product, contact the retailer immediately. For warranty service, contact Durastar customer service via email at QUESTIONS@DURASTAR.COM or by phone at 1-888-320-0706. Additional product guides and information are available at WWW.DURASTAR.COM.

Symbols Used in this Manual

Refrigerant Warning: R-454B is a flammable material. Follow handling instructions carefully and comply with national regulations.

Explanation of Symbols on the Unit:

Important Safety Precautions

WARNING: Turn off the air conditioner and disconnect the power before installing, cleaning, or repairing to avoid electric shock.

Improper handling can cause serious damage or injury. Follow these safety guidelines:

Electrical Safety:

Installation Safety:

Refrigerant Safety (A2L)

WARNING: Do not use means to accelerate defrosting or cleaning other than recommended. Store the appliance in a room without ignition sources. Do not pierce or burn. Be aware that flammable refrigerants may not have an odor. Comply with national refrigerant regulations.

A2L Refrigerant Safety Precautions:

Flammable Refrigerant Requirements

Installation space and ventilation requirements depend on refrigerant mass charge, installation location, and ventilation type. Piping material, routing, and installation must comply with codes and standards (e.g., ASHRAE 15, IAPMO, ICC, CSA B52). Field joints must be accessible for inspection. Protection devices, piping, and fittings should be protected from environmental effects. Piping should minimize hydraulic shock. Steel pipes require corrosion protection. Precautions against vibration and pulsation are necessary. Minimum floor area requirements must be met.

Pressure Testing:

  1. Pressure test the refrigerant piping to 500 PSI with OXYGEN-FREE NITROGEN (OFN).
  2. Maintain test pressure for at least 1 hour with no pressure decrease.
  3. During evacuation, the system must hold below 500 microns for 15 minutes after vacuum pump is off.

Field-made Refrigerant Joints: Must be tightness tested with a sensitivity of 0.18 oz (5 g) per year of refrigerant or better.

Qualifications of Workers:

Ventilated Area

Ensure adequate ventilation before working on the system to disperse any released refrigerant.

Cabling

Check wiring for wear, corrosion, excessive pressure, vibration, sharp edges, and other adverse environmental effects.

Detection of Flammable Refrigerants

Do not use sources of ignition when searching for leaks. Electronic leak detectors are acceptable, but sensitivity may need adjustment for flammable refrigerants. Ensure detectors are not ignition sources and are suitable for the refrigerant. Leak detection fluids are also suitable, but avoid those containing chlorine.

Note: Examples of leak detection fluids include bubble method and fluorescent method agents.

If a leak is suspected, remove all naked flames. If brazing is required for a leak, recover all refrigerant or isolate the system.

Evacuation

When breaking into the refrigerant circuit, follow best practices for flammable refrigerants:

Refrigerant charge must be recovered into correct cylinders. Purge the system with OXYGEN-FREE NITROGEN (OFN) to render it safe. Compressed air or oxygen must not be used. Vent the system to atmospheric pressure after the final OFN charge.

Recovery

When removing refrigerant for servicing or decommissioning, recover it safely. Ensure correct recovery cylinders are used.

Charging Procedures

Follow these requirements for charging:

Additional Precautions:

Refrigerant Pipe Length

The length of refrigerant piping affects performance and efficiency. Nominal efficiency is tested with 25 ft (7.6m) of piping. A minimum of 10 ft (3m) is required.

Capacity (BTU/h) Maximum Length Feet (Meters) Maximum Drop Height Feet (Meters)
6,000 - 12,000 82 Ft. (25 M) 49 Ft. (15 M)
18,000 98.5 Ft. (30 M) 66 Ft. (20 M)
24,000 - 33,000 164 Ft. (50 M) 82 Ft. (25 M)

Oil Traps

Oil traps are necessary when indoor and outdoor units are installed at significantly different heights.

Diagrams illustrating oil trap placement for different height configurations are provided.

Refrigerant Pipe Connection Instructions

Step 1: Cut Pipes

  1. Measure the distance between the indoor and outdoor units.
  2. Cut the pipe length slightly longer than the measured distance.
  3. Ensure the pipe is cut at a perfect 90° angle.
  4. Do not damage, deform, or dent the pipe while cutting.

Step 2: Remove Burrs

Step 3: Flare Pipe Ends

Pipe Extension Beyond Flare Form: A table provides minimum and maximum extension dimensions for different pipe diameters.

Tip: Thickness Comparison: Provides visual aids for thickness measurements.

Step 4: Connect Pipes

Connecting Piping to Indoor Unit: Align pipes and tighten flare nuts by hand, then with a torque wrench according to the provided table. A table specifies tightening torque and flare dimensions for different pipe sizes.

Caution: Do not use excessive torque.

Connecting Piping to Outdoor Unit: Remove the valve cover and protective caps. Align flared pipe ends and tighten flare nuts by hand, then with a torque wrench. Repeat for the remaining pipe.

System Evacuation

Preparations and Precautions: Air and foreign matter can cause system damage. Use a vacuum pump and manifold gauge to evacuate the system. Evacuation is required for initial installation and relocation.

Before Performing Evacuation:

Evacuation Instructions:

  1. Connect manifold gauge hoses.
  2. Pressurize the system to 600 PSIG with nitrogen.
  3. Wait 15 minutes and check for pressure changes.
  4. If pressure loss is greater than 5 PSIG, locate and fix leaks.
  5. If no pressure change, remove the nitrogen tank connection.
  6. Release system pressure.
  7. Connect the vacuum pump and micron gauge.
  8. Evacuate the system until the micron gauge reads 250 microns.
  9. Close the low pressure side and turn off the vacuum pump. The system must hold below 500 microns for 15 minutes.
  10. If pressure changes, locate and fix leaks.
  11. Remove the manifold gauge auxiliary hose.
  12. Open the system's valves gently.

Note on Adding Additional Refrigerant: Each outdoor unit is factory charged for up to 25 ft (7.5m). Systems with longer line sets require additional refrigerant. Refer to the submittal documents at WWW.DURASTAR.COM for calculations. Do not mix refrigerant types.

Final Checks

Before the Test Run:

Electrical Safety Checks: Ensure all electrical wiring complies with local and national regulations.

During Test Run:

Warning: All wiring must comply with electrical codes and be installed by a licensed electrician.

Test Run

Perform the test run for at least 30 minutes.

  1. Connect power to the unit.
  2. Turn the unit on using the remote controller or wired thermostat.
  3. Press the MODE button to select COOL (lowest temperature) and HEAT (highest temperature) modes.
  4. Run each function for 5 minutes and perform the following checks:
List of Checks to Perform Status
No electrical leakage [ ]
Unit is Properly Grounded [ ]
All Electrical Terminals are Properly Covered [ ]
Indoor and Outdoor Units are Solidly Installed [ ]
All Pipe Connection Points Do Not Leak, Indoor and Outdoor [ ]
Water Drains Properly from Drain Hose [ ]
All Piping is Properly Insulated [ ]
Unit Performs COOL Function Properly [ ]
Unit Performs HEAT Function Properly [ ]
Indoor Unit Louvers Move Properly [ ]
Indoor Unit Responds to Remote Controller or Thermostat [ ]

Double-check all pipe connections during operation. If the ambient temperature is below 60°F (16°C), use the MANUAL CONTROL button on the indoor unit to test the COOL function.

Troubleshooting

Safety Precautions: If the power cord is damaged, the unit emits abnormal sounds or a burning odor, a fuse blows, or water/objects fall into/out of the unit, turn off the unit immediately and contact an authorized service provider.

Common Issues:

Issue Possible Causes
Unit does not turn on when pressing ON/OFF button The unit has a 3-minute protection feature to prevent overloading. Restart after three minutes.
Unit changes from COOL/HEAT mode to FAN mode The unit may change settings to prevent frost formation. It will resume the selected mode once the temperature stabilizes.
Indoor unit emits white mist In humid regions, a large temperature difference can cause white mist.
Both indoor and outdoor units emit white mist White mist may be emitted due to moisture generated during defrosting in HEAT mode.
Indoor unit makes noises A rushing air sound may occur when louvers reset. A squeaking sound may occur due to thermal expansion/contraction of plastic parts.
Both indoor and outdoor units make noises Low hissing sound is normal, caused by refrigerant gas flow.
Outdoor unit makes noises The unit makes different sounds based on its operating mode.
Dust is emitted from either the indoor or outdoor unit Dust may accumulate during periods of non-use. Covering the unit during inactivity can mitigate this.
Unit emits a bad odor The unit may absorb ambient odors. Filters may be moldy and require cleaning.
Fan of the outdoor unit does not operate Fan speed is controlled to optimize operation.
Operation is erratic, unpredictable, or unit is unresponsive Interference from cell phone towers or boosters may cause malfunctions. Try disconnecting and reconnecting power, or restarting via the remote control.

Troubleshooting Table:

Problem Possible Causes Solution
Poor Cooling Performance Temperature setting higher than ambient room temperature Lower the temperature setting.
Heat exchanger is dirty Clean the affected heat exchanger.
Air filter is dirty Remove and clean the air filter.
Air inlet or outlet is blocked Turn off the unit, remove obstruction, and turn it back on.
Doors and windows are open Ensure all doors and windows are closed.
Excessive heat from sunlight Close windows and curtains during periods of high heat or bright sunshine. Block sunlight in the installation area. Reduce heat sources in the room.
Poor Heating Performance Outdoor temperature is extremely low This model is designed to work down to -13°F, but heating performance is impacted at temperatures below freezing.
Cold air entering through doors and windows Ensure all doors and windows are closed.
Excessive heat generated by sunlight Block sunlight in installation area. Reduce heat sources in the room.
Unit starts and stops frequently Low refrigerant due to leak or long-term use Check for leaks, re-seal if necessary, and top off refrigerant.
Too little refrigerant in the system Check for leaks and recharge the system.
Incompressible gas or moisture has entered the system Evacuate and recharge the system.
Compressor is broken Replace the compressor.
Voltage is too high or too low Install a manostat to regulate voltage.
Unit is not working Power failure Wait for power to be restored.
Power is turned off Turn on the power.
Fuse is burned out Replace the fuse.
Remote control batteries are dead Replace batteries.
Unit's 3-minute protection activated Wait three minutes after restarting.
Timer is activated Turn timer off.
Indicator lamps continue flashing or error code appears The unit may resolve the issue itself after about 10 minutes. If not, disconnect and reconnect power, then turn the unit on. If the problem persists, contact customer service.

Note: If problems persist after checks, turn off the unit and contact an authorized service center.

Wiring Diagrams

Wiring diagrams are provided for various Durastar models, including:

These diagrams illustrate the connections for the main control board, indoor unit, outdoor unit, power supply, sensors, motors, compressor, and other components.

Error and Operating Codes

A comprehensive list of error and operating codes is provided, along with their corresponding operation or malfunction descriptions. This includes codes related to defrost, cooling, fan speed, sensors, communication errors, refrigerant leaks, pressure protection, overcurrent, and temperature protection.

Job Site Information Sheet

A Job Site Information Sheet is included for recording site, contractor, outdoor unit (ODU), and indoor unit (IDU) information, as well as refrigerant line size and length. It also includes sections for outdoor and indoor electrical readings, and outdoor and indoor thermal readings.

Models: DRA1H06S2A, DRA1U09S2A, DRA1H09S2A, DRA1U12S2A, DRA1H12S2A, DRA1U18S2A, DRA1H18S2A, DRA1U24S2A, DRA1H24S2A, DRA1H33S2A, DRA1H06S2A Mini Split Single Zone Outdoor Unit, DRA1H06S2A, Mini Split Single Zone Outdoor Unit, Single Zone Outdoor Unit, Zone Outdoor Unit, Outdoor Unit

File Info : application/pdf, 40 Pages, 4.22MB

PDF preview unavailable. Download the PDF instead.

10782495 14430858 installation

References

Adobe PDF Library 17.0

Related Documents

Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering safety precautions, installation steps, troubleshooting, and specifications for models DRAW06F2A through DRAW33F2A using R-454B refrigerant.
Preview Durastar Wall Mounted Mini-Split Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners, covering operation, safety, maintenance, troubleshooting, and warranty for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, DRAW33F1B.
Preview Durastar Split-Style Air Conditioner Installation Manual for Outdoor Units
This installation manual provides comprehensive guidance for Durastar single-zone outdoor split-style air conditioners, including models DRA1U09S1B, DRA1U12S1B, DRA1U18S1B, and DRA1U24S1B. It covers safety precautions, installation steps, wiring, refrigerant piping, system evacuation, and troubleshooting.
Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering model numbers DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, and DRAW24F1B. Includes safety precautions, parts identification, step-by-step installation procedures, troubleshooting, and wiring diagrams.
Preview Durastar Slim Ducted Indoor Unit Owner's Manual
This manual provides comprehensive instructions for the Durastar Slim Ducted Indoor Unit Split-Style Air Conditioner, covering operation, maintenance, troubleshooting, and warranty information for models DRAD09F1A, DRAD12F1A, DRAD18F1A, and DRAD24F1A.
Preview Durastar DRAS12F1B Floor Mounted Mini-Split Air Conditioner Installation Manual
This installation manual provides detailed instructions for the Durastar DRAS12F1B floor-mounted split-style air conditioner. It covers safety precautions, installation steps, parts identification, troubleshooting, and wiring diagrams.
Preview Durastar Floor Console Indoor Unit Installation Manual | DRAS09F2A, DRAS12F2A, DRAS16F2A, R-454B
Comprehensive installation manual for Durastar Floor Console Indoor Units (DRAS09F2A, DRAS12F2A, DRAS16F2A) using R-454B refrigerant. Covers safety precautions, installation steps, troubleshooting, wiring diagrams, and error codes.
Preview Durastar DRAS12F1B Floor Mounted Indoor Unit Owner's Manual
Comprehensive owner's manual for the Durastar DRAS12F1B split-style air conditioner, covering installation, operation, maintenance, troubleshooting, and warranty information.