Product Overview
The Carrier XPOWER VRF system represents a significant advancement in climate control technology. It offers a sophisticated solution for heating and cooling diverse spaces with exceptional efficiency and reliability.
Visual Description: A prominent outdoor unit is depicted, featuring the Carrier logo and 'XPOWER' branding. The unit has a clean, white exterior with a textured ventilation grille, suggesting robust airflow management.
Carrier: Efficient, Dependable Performance
Carrier delivers efficient, dependable performance, inside and out.
Reliability
The operating sequence of the individual compressors is rotated, balancing their operating hours and distributing load evenly. Inverters reduce the risk of compressor failure and eliminate on/off power surges.
Functionality
A single VRF system can power up to 64 independent indoor units, depending on the system. This provides superior zoning because the refrigerant flow can vary from location to location, delivering only the necessary capacity to each zone.
Controllability
The entire system can be run from a central location or monitored remotely – perfect for diverse applications with a range of heating and cooling needs. Timely alerts aid in maintaining the system and keeping it running at its most efficient.
Key Features:
- ❄️ Efficient Cooling
- ☀️ Efficient Heating
- ? Energy Monitoring
- ? Fresh Air Ventilation
- ? User-Friendly Control Systems
- ? Environmentally Friendly
- ⚙️ Ease of Installation & Maintenance
Benefits for the User
- Infinite comfort: Achieved by fully controllable room temperature, a perfect alternative to traditional heating & cooling systems.
- Infinite efficiency: High levels of efficiency via optimal load adjustment.
- Infinite integration: Cooling, heating, and fresh air ventilation are all perfectly and conveniently attuned to one another within a single system.
- Infinite reliability: Hassle-free operation based on an intensive testing program for all systems.
Visual Description: The image shows two construction professionals, one pointing, suggesting teamwork and project oversight in a modern setting.
Benefits for the Consultant
- Absolute customisation: A wide range of indoor units ensure that customer requirements are fully addressed.
- Absolute control: Fully integrated controls network, allowing unlimited access to the system controls and its operation.
- Absolute flexibility: A high degree of system flexibility, aided by a fully flexible piping specification and an extremely compact modular design.
Benefits for the Installer
- Simple: One supplier – one point of contact for a total solution: cooling, heating, & controls.
- Versatile: Maximised installation flexibility.
- Convenient: Easy access for all service and maintenance needs.
- Assessable: Simplified and swift commissioning.
Visual Description: The image features a striking modern skyscraper, symbolizing large-scale, high-tech building projects where such systems are deployed.
Key Technologies
Innovative Compressor Technology
Xpower's infinitely variable, inverter-driven control continually adjusts the operating speed of the compressors in real-time. This ensures that the capacity output precisely matches the demand from the end user. The advantage of this control is further optimized by incorporating all inverter twin rotary compressors.
Diagram Description: An ambient temperature expansion chart is shown, indicating the operational ranges for Cooling (from -5°C to 52°C) and Heating (from -25°C to 15.5°C).
Diagram Description: A detailed cutaway illustration of a twin rotary compressor is presented, highlighting its internal mechanics and design.
Diagram Description: An illustration showcases the new dual vane technology and Diamond Like Carbon Coating applied to compressor components, emphasizing enhanced performance and efficiency.
Increased Compressor Displacement
Increased compressor displacement extends the compressor's capacity output. A single unit with two compressors can now achieve a capacity output of up to 20 HP, offering increased operation range and more precise control.
Dual Vane Technology
The new dual vane technology is unique to Xpower twin rotary compressors. Its new design minimizes pressure losses between high and low-pressure chambers, increasing system efficiency while further enhancing compressor reliability. The brand-new "Diamond Like Carbon Coating" ensures maximum operations without the fear of increased mechanical wear and tear.
Intelligent Flow Technology
This unique control continually adjusts the operation of both indoor and outdoor units, based on feedback from multiple sensors located throughout the system. Refrigerant flow to each indoor unit is precisely controlled by the outdoor unit, ensuring even distribution of capacity throughout the entire system. The evaporative and condensing temperatures are continually adjusted automatically to maintain an optimum indoor room temperature, regardless of the unit's load or its physical distance from the outdoor. This ensures optimum performance while maximizing system efficiency.
Diagram Description: A bar chart illustrates capacity distribution across four hypothetical units (A, B, C, D) relative to a 'Target Capacity' line. It demonstrates how excess capacity in units A & B can be redistributed to units C & D, ensuring perfect operation throughout the entire system.
Xpower's "IFT" technology ensures that any surplus capacity can be re-distributed to achieve optimum performance and efficiency throughout the entire system. This technology ensures that the flow of refrigerant to the FCUs is precisely proportional to the demand of each individual indoor unit. Where demand exceeds the output of the CDU, the refrigerant is evenly distributed throughout the indoor network, ensuring stable capacity regardless of the unit's location within the building.
Infinite Variable Control
The control system has the ability to adjust the compressor rotational speed in near-seamless 0.1 Hz steps. When matched with Xpower's newest Twin Rotary compressors, this control allows the system to respond precisely to the capacity needs of the end user, while minimizing energy losses.
Diagram Description: A graph plots Compressor Speed (Hz) against Capacity. A marker highlights the 0.1 Hz step capability, illustrating precise control adjustments.
Innovation Heat Exchanger and Fan Blade Design
The new 3-row heat exchanger design features a reduced pipe size (from 8mm to 7mm) and an increased total number of passes, improving both system performance and efficiency. A 4-sided heat exchanger ensures maximum possible flow rate across the entire coil, maximizing system efficiency. The 3-way variable heat exchanger design allows the CDU to select the most efficient heat exchanger size, precisely matching the indoor capacity load. A new sub-cooling heat exchanger increases system operating performance and allows for a total piping length of up to 1,000 m.
Diagram Description: An illustration shows a 4-way heat exchanger within a machine room, depicting balanced airflow.
Diagram Description: A diagram illustrates a variable heat exchanger, differentiating between 'Max. operation' (100% total capacity) and 'Min. operation' (20% total capacity), indicating 'Use' and 'Nonuse' scenarios, such as cooling operation in high outdoor temperatures.
Outdoor Fan
The new outdoor fan blade includes a unique profile, ensuring smoother, uninterrupted airflow. The new propeller design reduces sound pressure levels while maximizing airflow volume. The outdoor fan motor now incorporates a 3-phase motor to maximize performance and efficiency, while reducing the minimum circuit amps value of the outdoor unit.
Diagram Description: An illustration of the outdoor fan highlights its advanced blade shapes, with labels pointing to "New anti-eddy projections on the back of the fan" and "New profiles of the reverse-arc shaped wings" for better airflow management.
Expanded Installation Flexibility
The new compact design of the Outdoor units provides increased performance that defies their compact module size. This delivers greater freedom in layout design, minimizes weight-related restrictions, and allows for quicker installation. The compact design features a reduced footprint.
Capacity up to 20HP can be covered with a single module, reducing pipe work and overall installation time. The system can be expanded to a maximum combination of 56 HP in one system, supporting up to 64 connectable indoor units.
The maximum piping length is 1,000 m, with a farthest equivalent length of 235 m. The maximum vertical distance between indoor units reaches up to 40 meters.
Diagram Description: A system diagram illustrates a 56 HP outdoor unit connected to up to 64 indoor units.
Diagram Description: A diagram indicates the total piping length capability of 1,000 meters.
Diagram Description: A diagram shows the farthest equivalent piping length can reach 235 meters.
Diagram Description: A diagram illustrates the maximum vertical distance between indoor units, which is 40 meters.
Technical Specifications
Model name | Unit Size | 008167HTMM | 010167HTMM | 012167HTMM | 014167HTMM | 016167HTMM | 018167HTMM | 020167HTMM | ||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | HP | kW | Btu/h | kW | Btu/h | kW | Btu/h | ||
Cooling capacity (*1) | 8 | 22.4 | 76,000 | 10 | 28.0 | 96,000 | 12 | 33.5 | 114,000 | 14 | 40.0 | 136,000 | 16 | 45.0 | 152,000 | 18 | 50.4 | 172,000 | 20 | 56.0 | 190,000 | |||||||||||||||||||||||||||||
Cooling capacity (*2) | 20.3 | 25.2 | 86,000 | 26.8 | 91,000 | 32.5 | 110,000 | 36.0 | 122,000 | 42.8 | 146,000 | 44.8 | 152,000 | |||||||||||||||||||||||||||||||||||||
Heating capacity (*1) | 25.0 | 31.5 | 107,000 | 37.5 | 127,000 | 45.0 | 152,000 | 50.0 | 170,000 | 56.0 | 190,000 | 63.0 | 214,000 | |||||||||||||||||||||||||||||||||||||
Power supply (V/PH/HZ) | 380/3/60 | |||||||||||||||||||||||||||||||||||||||||||||||||
Voltage range (*3) | Minimum V | 342 | ||||||||||||||||||||||||||||||||||||||||||||||||
Maximum V | 418 | |||||||||||||||||||||||||||||||||||||||||||||||||
Electrical characteristic (*1) | Cooling Running current A | 8.5 | 11.2 | 14.0 | 17.1 | 21.0 | 21.1 | 26.3 | ||||||||||||||||||||||||||||||||||||||||||
Cooling Power input kW | 5.09 | 6.60 | 8.66 | 10.4 | 12.7 | 12.9 | 16.3 | |||||||||||||||||||||||||||||||||||||||||||
EER kW/kW | 4.38 | 4.26 | 3.85 | 3.84 | 3.50 | 3.91 | 3.41 | |||||||||||||||||||||||||||||||||||||||||||
EER Btu/Wh | 14.95 | 14.55 | 13.15 | 13.10 | 13.35 | 13.1 | 11.65 | |||||||||||||||||||||||||||||||||||||||||||
Cooling Power input (*2) | kW | 6.90 | 9.20 | 9.44 | 12.2 | 13.1 | 15.0 | 15.7 | ||||||||||||||||||||||||||||||||||||||||||
EER kW/kW | 2.93 | 2.74 | 2.83 | 2.64 | 2.73 | 2.86 | 2.84 | |||||||||||||||||||||||||||||||||||||||||||
EER Btu/Wh | 10.00 | 9.35 | 9.65 | 9.00 | 9.30 | 9.75 | 9.70 | |||||||||||||||||||||||||||||||||||||||||||
Heating Running current (*1) | A | 9.4 | 12.3 | 15.8 | 18.6 | 21.7 | 23.6 | 28.0 | ||||||||||||||||||||||||||||||||||||||||||
Power input KW | 5.66 | 7.45 | 9.72 | 11.1 | 13.2 | 14.3 | 17.4 | |||||||||||||||||||||||||||||||||||||||||||
COP kW/kW | 4.42 | 4.23 | 3.86 | 4.05 | 3.79 | 3.92 | 3.62 | |||||||||||||||||||||||||||||||||||||||||||
COP Btu/Wh | 15.00 | 14.35 | 13.05 | 13.70 | 12.90 | 13.30 | 12.30 | |||||||||||||||||||||||||||||||||||||||||||
Starting current A | Soft Start | Soft Start | Soft Start | Soft Start | Soft Start | Soft Start | Soft Start | |||||||||||||||||||||||||||||||||||||||||||
Dimension | Height mm | 1800 | ||||||||||||||||||||||||||||||||||||||||||||||||
Width mm | 990 | 990 | 990 | 1210 | 1210 | 1600 | 1600 | |||||||||||||||||||||||||||||||||||||||||||
Depth mm | 780 | |||||||||||||||||||||||||||||||||||||||||||||||||
Weight | Heat pump kg | 242 | 242 | 242 | 299 | 299 | 370 | 370 | ||||||||||||||||||||||||||||||||||||||||||
Colour | Silky shade (Munsell 1Y8.5/0.5) | |||||||||||||||||||||||||||||||||||||||||||||||||
Compressor | Type | Hermetic Twin Rotary | ||||||||||||||||||||||||||||||||||||||||||||||||
Motor output kW | 2.1 x 2 | 3.1 x 2 | 3.9 x 2 | 4.8 x 2 | 5.8 x 2 | 6.5 x 2 | 7.6 x 2 | |||||||||||||||||||||||||||||||||||||||||||
Fan unit | Type | Propeller fan | ||||||||||||||||||||||||||||||||||||||||||||||||
Motor output kW | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0x2 | 1.0x2 | |||||||||||||||||||||||||||||||||||||||||||
Air volume m3/h | 9700 | 9700 | 12200 | 12200 | 12600 | 17300 | 17900 | |||||||||||||||||||||||||||||||||||||||||||
Max. external static pressure Pa | 60 | 60 | 50 | 50 | 40 | 50 | 40 | |||||||||||||||||||||||||||||||||||||||||||
Heat exchanger Name | Finned tube | |||||||||||||||||||||||||||||||||||||||||||||||||
Refrigerant Charge Heat pump kg | 11.5 | 11.5 | 11.5 | 11.5 | 11.5 | 11.5 | 11.5 | |||||||||||||||||||||||||||||||||||||||||||
High-pressure switch Pa | OFF:3.2 ON:4.15 | |||||||||||||||||||||||||||||||||||||||||||||||||
Protective devices | (*4) | Included | ||||||||||||||||||||||||||||||||||||||||||||||||
MCA (*5) A | 20.5 | 21.5 | 26.1 | 31.0 | 35.8 | 40.6 | 44.9 | |||||||||||||||||||||||||||||||||||||||||||
Power supply wiring MOCP (*6) A | 25.0 | 25.0 | 32.0 | 40.0 | 40.0 | 50.0 | 63.0 | |||||||||||||||||||||||||||||||||||||||||||
Piping connections | Type Gas | Brazing | ||||||||||||||||||||||||||||||||||||||||||||||||
Diameter mm | 19.1 | 22.2 | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | |||||||||||||||||||||||||||||||||||||||||||
Type Liquid | Flare | Flare | Flare | Flare | Flare | Flare | Flare | |||||||||||||||||||||||||||||||||||||||||||
Diameter mm | 12.7 | 12.7 | 12.7 | 15.9 | 15.9 | 15.9 | 15.9 | |||||||||||||||||||||||||||||||||||||||||||
Type Balance | Flare | Flare | Flare | Flare | Flare | Flare | Flare | |||||||||||||||||||||||||||||||||||||||||||
Diameter mm | 9.5 | 9.5 | 9.5 | 9.5 | 9.5 | 9.5 | 9.5 | |||||||||||||||||||||||||||||||||||||||||||
Max. number of connected indoor units | 13 | 16 | 20 | 23 | 27 | 30 | 33 | |||||||||||||||||||||||||||||||||||||||||||
Sound pressure level | Cooling dB(A) | 55 | 57 | 59 | 60 | 62 | 60 | 61 | ||||||||||||||||||||||||||||||||||||||||||
Heating dB(A) | 56 | 58 | 61 | 62 | 64 | 61 | 62 | |||||||||||||||||||||||||||||||||||||||||||
Sound power level | Cooling dB(A) | 74 | 74 | 80 | 80 | 81 | 81 | 82 | ||||||||||||||||||||||||||||||||||||||||||
Heating dB(A) | 74 | 74 | 82 | 82 | 83 | 83 | 84 | |||||||||||||||||||||||||||||||||||||||||||
Operation temperature range | Cooling CDB | -5 to 52 | -5 to 52 | -5 to 52 | -5 to 52 | -5 to 52 | -5 to 52 | -5 to 52 | ||||||||||||||||||||||||||||||||||||||||||
Heating(*7) CWB | -25 to 15.5 | -25 to 15.5 | -25 to 15.5 | -25 to 15.5 | -25 to 15.5 | -25 to 15.5 | -25 to 15.5 |
Note:
(*1) Rated conditions: Cooling: Indoor 27 degC Dry Bulb /19 degC Wet Bulb, Outdoor 35 degC Dry Bulb. Heating: Indoor 20 degC Dry Bulb, Outdoor 7 degC Dry Bulb / 6 degC WetBulb. Based on equivalent piping length of 7.5m and piping height difference of 0m.
(*2) Rated conditions: Cooling: Indoor 27 degC Dry Bulb /19 degC Wet Bulb, Outdoor 46 degC Dry Bulb. Based on equivalent piping length of 7.5m and piping height difference of 0m.
(*3) Voltage range: Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(*4) Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / Compressor case thermostat / PC board fuse
(*5) MCA: Minimum Circuit Amps. Select wire size based on the larger value of MCA.
(*6) MOCP: Maximum Overcurrent Protection (Amps)
(*7) Low ambient heating (-20degC or less) for extended periods of time is not allowed.
Carrier reserves the right to change features and / or specifications without notice and without incurring any liability.
Outdoor Lineup
Model (60Hz) - Single Units
Model | 38VT008167HTMM | 38VT010167HTMM | 38VT012167HTM | 38VT014167HTMM | 38VT016167HTMM | 38VT018167HTMM | 38VT020167HTMM |
---|---|---|---|---|---|---|---|
Capacity (HP) | 8 | 10 | 12 | 14 | 16 | 18 | 20 |
Cooling Capacity (35C) (kW) | 22.4 | 28.0 | 33.5 | 40.0 | 45.0 | 50.4 | 56.0 |
Cooling Capacity (46C) (kW) | 20.3 | 25.2 | 26.8 | 32.5 | 36.0 | 42.8 | 44.8 |
Heating Capacity (35C) (kW) | 25.0 | 31.5 | 37.5 | 45.0 | 50.0 | 56.0 | 63.0 |
Max. number of connected indoor units (Qty) | 13 | 16 | 20 | 23 | 27 | 30 | 33 |
Model (60Hz) - Combination Models
Model | 38VT022S67HTMM | 38VT024S67HTMM | 38VT026S67HTMM | 38VT028S67HTMM | 38VT030S67HTMM | 38VT032S67HTMM | 38VT034S67HTMM |
---|---|---|---|---|---|---|---|
Combination Models | 38VT012167HTMM 38VT010167HTMM |
38VT012167HTMM 38VT012167HTMM |
38VT014167HTMM 38VT012167HTMM |
38VT014167HTMM 38VT014167HTMM |
38VT016167HTMM 38VT014167HTMM |
38VT016167HTMM 38VT016167HTMM |
38VT018167HTMM 38VT016167HTMM |
Capacity (HP) | 22 | 24 | 26 | 28 | 30 | 32 | 34 |
Cooling Capacity (35C) (kW) | 61.5 | 67.0 | 73.5 | 80.0 | 85.0 | 90.0 | 95.4 |
Cooling Capacity (46C) (kW) | 52.0 | 53.0 | 59.3 | 65.0 | 65.0 | 72.0 | 78.8 |
Heating Capacity (35C) (kW) | 69.0 | 75.0 | 82.5 | 90.0 | 95.0 | 100.0 | 106.0 |
Max. number of connected indoor units (Qty) | 37 | 40 | 43 | 47 | 50 | 54 | 57 |
Model (60Hz) - Higher Capacity Combination Models
Model | 38VT036S67HTMM | 38VT038S67HTMM | 38VT040S67HTMM | 38VT042S67HTMM | 38VT044S67HTMM | 38VT046S67HTMM | 38VT048S67HTMM |
---|---|---|---|---|---|---|---|
Combination Models | 38VT018167HTMM 38VT018167HTMM 38VT014167HTMM |
38VT020167HTMM 38VT018167HTMM 38VT014167HTMM |
38VT020167HTMM 38VT020167HTMM 38VT014167HTMM |
38VT014167HTMM 38VT016167HTMM 38VT016167HTMM |
38VT016167HTMM 38VT014167HTMM 38VT016167HTMM |
38VT016167HTMM 38VT016167HTMM 38VT016167HTMM |
38VT016167HTMM 38VT016167HTMM 38VT016167HTMM |
Capacity (HP) | 36 | 38 | 40 | 42 | 44 | 46 | 48 |
Cooling Capacity (35C) (kW) | 100.8 | 106.4 | 112.0 | 120.0 | 125.0 | 130.0 | 135.0 |
Cooling Capacity (46C) (kW) | 85.6 | 87.6 | 89.6 | 97.5 | 101.0 | 104.5 | 108.0 |
Heating Capacity (35C) (kW) | 112.0 | 119.0 | 126.0 | 135.0 | 140.0 | 145.0 | 150.0 |
Max. number of connected indoor units (Qty) | 60 | 64 | 64 | 64 | 64 | 64 | 64 |
Model (60Hz) - Highest Capacity Combination Models
Model | 38VT050S67HTMM | 38VT052S67HTMM | 38VT054S67HTMM | 38VT056S67HTMM |
---|---|---|---|---|
Combination Models | 38VT018167HTMM 38VT016167HTMM 38VT016167HTMM |
38VT0181167HTMM 38VT018167HTMM 38VT016167HTMM |
38VT020167HTMM 38VT020167HTMM 38VT014167HTMM |
38VT020167HTMM 38VT020167HTMM 38VT016167HTMM |
Capacity (HP) | 50 | 52 | 54 | 56 |
Cooling Capacity (35C) (kW) | 140.4 | 145.8 | 152.0 | 157.0 |
Cooling Capacity (46C) (kW) | 114.8 | 121.6 | 122.1 | 125.6 |
Heating Capacity (35C) (kW) | 156.0 | 162.0 | 171.0 | 176.0 |
Max. number of connected indoor units (Qty) | 64 | 64 | 64 | 64 |
Indoor Lineup
The Carrier XPOWER VRF system supports a wide range of indoor unit types to suit various installation requirements:
Type | Cooling Capacity (kW) | Cooling Capacity (HP) |
---|---|---|
4-way air discharge cassette type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Compact 4-way cassette type (620 x 620) | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
2-way air discharge cassette type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
1-way air discharge cassette type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Slim duct type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Concealed duct high static pressure type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Concealed duct type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Ceiling type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
High wall type Series 3 | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
High wall type Series 4 | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Floor standing concealed type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Floor standing cabinet type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Console type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Floor standing type | 2.2, 2.8, 3.6, 4.5, 5.6, 7.1, 8.0, 9.0, 11.2, 14.0, 16.0, 22.4, 28.0 | 0.8, 1.0, 1.25, 1.7, 2.0, 2.5, 3.0, 3.2, 4.0, 5.0, 6.0, 8.0, 10.0 |
Controls
Comfort, economic efficiency, and safety can be further maximized with modern control mechanisms. Whether wired or remotely controlled units, web-based control devices, or elegant touch screen systems, the important thing is to achieve the right temperature at the right time and at the right place. It's about balance – and Carrier has it just right.
Wired Remote Controls
- Lite-Vision Plus: A sophisticated wired controller.
- Remote Controller with weekly timer: Offers scheduling capabilities.
- Simple wired remote controller: Provides basic control functions.
Wireless Remote Controls
- Infrared Remote Control: Standard wireless control.
- Receiver kit for installation on the wall or ceiling: Enables wireless control integration.
- Receiver kit to be installed directly in the frame of the indoor unit: Compact integration for wireless control.
- Receiver kit to be installed directly in the frame of the indoor unit: Another option for seamless integration.
Central Controllers
- Central remote controller: Advanced control for multiple units.
- Schedule Timer: For programmed operation cycles.
BMS Controllers
- Touch Screen controller: Intuitive interface for comprehensive management.
- Smart BMS Manager: For building management system integration.
Connectable Open Network
- BACnet®: Standard protocol for building automation.
- LonWORKS®: Another open network protocol.
- Modbus®: Widely used industrial communication protocol.
Contact Information and Certifications
Certifications: ISO9001, ISO14001, TIS18001, OHSAS
Company: Arabian Air-Conditioning Company Ltd. (Carrier Distributor)
Locations:
- Riyadh: Tel: 011 2180022
- Jeddah: Tel: 012 2375000
- Makkah: Tel: 012 5482230
- Madinah: Tel: 014 8464163
- Dammam: Tel: 013 8577710
- Al Hofuf: Tel: 013 5828595
Website: www.carrierksa.com
The manufacturer reserves the right to change the product specifications, data and images without notice.
Revision: REV-06-2020