Hyundai HY-CLM12KR-001 Portable Air Conditioner User Manual

Licensed by Hyundai Corporation, Korea.

Table of Contents

The refrigerant used in mobile air conditioners is the environmentally friendly hydrocarbon R290. This refrigerant is odorless, and compared to the alternative refrigerant, the R290 is an ozone-free refrigerant, and its effect is very low.

Please read the instructions before use and repair.

The drawings provided in this manual may not be the same as the physical objects. Please refer to the physical objects.

Maximum refrigerant charge amount (M): R290/230g

Minimum rated airflow: 400m3/h

I. Attention Matters

Warning matters:

  1. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
  2. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
  3. Do not pierce or burn.
  4. Be aware that refrigerants may not contain an odour.
  5. Appliance shall be installed, operated and stored in a room with a floor area larger than 12 m2.
  6. Keep any required ventilation openings clear of obstruction.
  7. Servicing shall be performed only as recommended by the manufacturer.
  8. The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
  9. Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.
  10. Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
  11. All working procedures that affect safety means shall only be carried out by competent persons.
  12. The appliance shall be stored so as to prevent mechanical damage from occurring.

⚠️ Caution, risk of fire, R290

Notes:

Transportation, marking and storage for units:

  1. Transport of equipment containing flammable refrigerants: Compliance with the transport regulations.
  2. Marking of equipment using signs: Compliance with local regulations.
  3. Disposal of equipment using flammable refrigerants: Compliance with national regulations.
  4. Storage of equipment/appliances: The storage of equipment should be in accordance with the manufacturer's instructions.
  5. Storage of packed (unsold) equipment: Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

II. Features and Components

1. Features

The Max operation temperature for the air conditioner is: Cooling: 35/24℃; Heating: 20/12℃; Temperature operation range: 7-35℃.

2. Component

Diagram showing the portable air conditioner unit. Key components labeled include: Mask, Top cover with a swing leaf, Front housing, Rear housing, and Omni-directional wheels at the base. The rear of the unit shows an EVA filter housing, an Air vent, a CON filter screen, a Drainage hole, a Handle, a Continuous drainage hole, a Power cord fixing board, and an Air inlet grille. Accessories shown are the Exhaust Pipe Assembly and the Window Sealing Plate Assembly, along with the Power cord and plug.

III. Control Setting

1. Control panel operation instructions

1) Operation interface:

The control panel features buttons and indicators for various functions. The main controls are:

Indicators include:

Numbered controls correspond to:

  1. Timing Key
  2. Wind Speed Selection Key
  3. Up Key
  4. Display window
  5. Down key
  6. Mode selection key
  7. Power key

Key Functions:

  1. Power Key: Press to turn the machine on or off.
  2. Mode Selection Key: Press to cycle through Cooling, Dehumidifying, and Fan modes.
  3. Up Key and Down Key: Used to adjust the setting temperature or timer value. Temperature adjustment is available in Cooling and Fan modes; timer adjustment is available in all modes.
  4. Wind Speed Selection Key: In Cooling and Fan modes, press to select High or Low wind speed. In Dehumidifying mode, this key is invalid, and the fan operates at a low speed.
  5. Timing Key: Press to set a timer for operation. When the timing symbol flashes, use Up/Down keys to select a value from 1-24 hours, adjusted by one-hour increments.
  6. Sleep Mode: In Cooling mode, press UP and Fan keys simultaneously to activate Sleep mode for energy-saving and quiet operation.

2. Operation instructions of remote control

1) The remote control Panel:

The remote control has buttons for Power, Mode, Up (+), Down (-), Fan Speed, Timer, Cleaning (louver swing), Celsius/Fahrenheit (°C/°F), and Sleep Mode.

Instructions of key operation:

  1. Power: Press the power button to turn the machine on or off.
  2. Mode: Press to switch between Cooling, Dehumidification, Fan, and Heating (if applicable) modes.
  3. Up: Press the '+' button to increase temperature and timing set value.
  4. Down: Press the '-' button to reduce temperature and timing set value.
  5. Fan: Press the fan speed button to select high, medium, or low wind speed output circularly.
  6. Timer: Press to set the timing value. Timing can be set from 1-24 hours, adjusted by one hour increments.
  7. Cleaning: Press this button to make the louver swing up and down.
  8. °C/°F: Press to switch between Celsius and Fahrenheit temperature display.
  9. Sleep Mode: Press to turn on the sleep mode.

IV. Protection function

3.1 Frost Protection Function:

In Cooling, Dehumidifying, or economic power saving mode, if the temperature of the exhaust pipe becomes too low, the machine will automatically enter protection status. If the exhaust pipe temperature rises to a certain level, it will revert to normal operation.

3.2 Overflow Protection Function:

When water in the water pan exceeds the warning level, the machine will sound an alarm, and the "FULL" indicator light will flash. You need to move the drainage pipe to a sewer or other drainage area to empty the water. After the water is emptied, the machine will automatically return to its original state.

3.3 Automatic Defrosting:

(Cooling models have this function) The machine has an automatic defrosting function, achieved through four-way valve reversing.

3.4 Protection Function of the Compressor:

To increase the service life of the compressor, it has a 3-minute delay booting protection function after the compressor is turned off.

V. Installation and adjustment

1. Installation:

Warning: Before using the mobile air conditioning, keep it upright for at least two hours. The air conditioning can be easily moved in the room. During movement, ensure the air conditioning remains upright and is placed on a flat surface. Do not install or use the air conditioning in a bathroom or other humid environments.

1.1 Install the heat pipe assembly (as shown in Figure 1):

Illustration of the heat pipe assembly installation. It shows the exhaust joint of the heat pipe being inserted into a vent slot on the back panel of the air conditioner unit.

  1. Take out the outer connector assembly and the exhaust pipe assembly, and remove any plastic bags.
  2. Insert the heat pipe assembly (the end with the exhaust joint) into the back panel vent slot (push to the left) and complete the assembly.

1.2 Installation of window sealing plate components:

Diagrams illustrating the window sealing plate assembly. It is shown as an adjustable panel designed to fit into a partially opened window. The assembly has sections that can be extended to contact the window frame, creating a seal around the exhaust hose which passes through it. It can be oriented horizontally or vertically.

  1. Half open the window and mount the window sealing plate assembly to the window. Components can be placed horizontally or vertically.
  2. Pull various components of the window sealing plate assembly open, adjust their opening distance to bring both ends of the assembly into contact with the window frame, and fix the components.

Notes: 1) The flat end of the exhaust pipe joints must be snapped securely into place.

1.3 Install the body:

Diagram showing the portable air conditioner unit placed away from walls and objects. Minimum clearance distances of 50 cm are indicated on the sides and rear.

  1. Move the machine with the installed heat pipe and fittings in front of the window. Ensure the distance between the body and walls or other objects is at least 50 cm.

Illustrations demonstrating the connection of the exhaust pipe to the window sealing plate. The flat end of the exhaust pipe joint is shown being snapped into the corresponding hole in the window sealing plate assembly.

Elongate the exhaust pipe and snap the flat end of the exhaust pipe joints into the hole of the window sealing plate assembly.

Notes: 1) The flat end of the exhaust pipe joints must be snapped securely into place. 3) The pipe cannot be distorted nor have substantial turning (greater than 45°). Keep the ventilation of the exhaust pipe not blocked.

VI. Drainage Instructions

This machine has two drainage methods: manual drainage and continuous drainage.

1. Manual drainage:

  1. When the machine stops after the water is full, turn off the machine power and unplug the power plug.
  2. Place a water container below the side water outlet behind the body.
  3. Unscrew the drainage cover and unplug the water plug; the water will automatically flow into the water container.

Notes: 1) Keep the drainage cover and the water plug properly. 2) During drainage, the body can be tilted slightly backwards. 3) If the water container cannot hold all the water, before the container is full, replace the water plug as soon as possible to prevent water from flowing to the floor or carpet. 4) When the water is discharged, replace the water plug and tighten the drainage cover.

2. Continuous drainage (Optional):

(Only applicable to dehumidifying mode) As shown in the figure:

Diagram illustrating drainage. For manual drainage, a water container is placed below the side water outlet at the rear of the unit. For continuous drainage, a drainage pipe is connected to the water outlet and directed to a bucket.

  1. Unscrew the drainage cover and unplug the water plug.
  2. Set the drainage pipe into the water outlet.
  3. Connect the drainage pipe to the bucket.

Important Notice: The length of the exhaust hose shall be 280~1,500mm. Do not use extension tubes or replace it with other different hoses, as this may cause a malfunction. The exhaust host must not be blocked; otherwise, it may cause overheating.

VII. Maintenance

Cleaning: Before cleaning and maintenance, turn off the machine and unplug the plug.

1. Clean the surface:

Clean the surface of the machine with a wet soft cloth. Do not use chemicals such as benzene, alcohol, gasoline, etc.; otherwise, the surface of the air conditioning will be damaged or even the whole machine will be damaged.

2. Clean the filter screen:

If the filter screen is clogged with dust, and the effectiveness of the air conditioning is reduced, be sure to clean the filter screen once every two weeks.

Diagram showing the front panel of the air conditioner partially removed to access the filter screen. Components like retaining screws and wedging blocks are indicated.

Illustration of the filter screen being cleaned, shown submerged in water.

3. Clean the upper filter screen frame:

  1. Unscrew one screw fixed by the EVA filter net and back shell with a screwdriver, and take out the EVA filter net.
  2. Put the EVA filter screen into warm water with neutral detergent (about 40°C / 104°F) and dry it in the shade after rinsing clean.

VIII. Unit Storage:

  1. Unscrew the drainage cover, unplug the water plug, and discharge the water in the water pan into other water containers or directly tilt the body to discharge the water.
  2. Turn on the machine, adjust it to low-wind ventilation mode, and maintain this state until the drainage pipe becomes dry, to keep the inside of the body dry and prevent mildew.
  3. Turn off the machine, unplug the power plug, and wrap the power cord around the wrapping post; install the water plug and the drainage cover.
  4. Remove the exhaust pipe and keep it properly.
  5. Cover the air conditioning with a plastic bag. Put the air conditioning in a dry place, keep it out of the reach of children, and take dust control measures.
  6. Remove batteries of the remote control and keep them properly.

Note: Ensure that the body is placed in a dry place and keep all machine components properly.

IX. Troubleshooting

Do not repair or disassemble the air conditioning by yourself. Unqualified repair will lead to failure of the warranty card, and may cause damage to users or their properties.

ProblemsReasonsSolutions
The air conditioning does not work.There is no electricity.Turn it on after connecting it to a socket with electricity.
The overflow indicator displays "FL".Discharge the water inside.
The ambient temperature is too low or too high.Recommend to use the machine in at the temperature of 7-35 °C (44-95 °F).
The cooling effect is not good.In cooling mode, the room temperature is lower than the set temperature; in heating mode, the room temperature is higher than the set temperature.Change the set temperature.
In dehumidification mode, the ambient temperature is low.The machine is placed in a room with an ambient temperature of greater than 17 °C (62 °F).
There is direct sunlight.Pull the Curtain.
Doors or windows are open; there are a lot of people; or in cooling mode, there are other sources of heat.Close doors and windows, and add new air conditioning.
Big NoiseThe filter screen is dirty.Clean or replace the filter screen.
Compressor does not work.The air inlet or outlet is blocked.Clear obstructions.
The air conditioning is not placed on a flat surface.Put the air conditioning on a flat and hard place (to reduce noise).
The remote control does not work.Overheat protection starts.Wait for 3 minutes until the temperature is lowered, and then restart the machine.
The distance between the machine and the remote control is too far.Let the remote control get close to the air conditioning, and make sure that the remote control directly faces to the direction of the remote control receiver.
The remote control is not aligned with the direction of the remote control receiver.Replace batteries.
Displays 'E1'.The pipe temperature sensor is abnormal.Check the pipe temperature sensor and related circuitry.
Displays 'E2'.The room temperature sensor is abnormal.Check the room temperature sensor and related circuitry.

Note: If problems not listed in the table occur or recommended solutions do not work, please contact the professional service organization.

1. Information on servicing:

1) Checks to the area: Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.

2) Work procedure: Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.

3) General work area: All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

4) Checking for presence of refrigerant: The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

5) Presence of fire extinguisher: If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

6) No ignition sources: No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "No Smoking" signs shall be displayed.

7) Ventilated area: Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

8) Checks to the refrigeration equipment: Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer's technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:

9) Checks to electrical devices: Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include:

2. Repairs to sealed components:

  1. During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
  2. Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.

3. Repair to intrinsically safe components:

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

4. Cabling:

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges, or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

5. Detection of flammable refrigerants:

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

6. Leak detection methods:

The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants, but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut-off valves) in a part of the system remote from the leak. Oxygen-free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

7. Removal and evacuation:

When breaking into the refrigerant circuit to make repairs or for any other purpose, conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be "flushed" with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.

8. Charging procedures:

In addition to conventional charging procedures, the following requirements shall be followed:

Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow-up leak test shall be carried out prior to leaving the site.

9. Decommissioning:

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.

  1. Become familiar with the equipment and its operation.
  2. Isolate system electrically.
  3. Before attempting the procedure, ensure that:
    • Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
    • All personal protective equipment is available and being used correctly.
    • The recovery process is supervised at all times by a competent person.
    • Recovery equipment and cylinders conform to the appropriate standards.
  4. Pump down refrigerant system, if possible.
  5. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
  6. Make sure that the cylinder is situated on the scales before recovery takes place.
  7. Start the recovery machine and operate in accordance with manufacturer's instructions.
  8. Do not overfill cylinders (No more than 80% volume liquid charge).
  9. Do not exceed the maximum working pressure of the cylinder, even temporarily.
  10. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
  11. Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

10. Labelling:

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

11. Recovery:

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e., special cylinders for the recovery of refrigerant). Cylinders shall be complete with a pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained, and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult the manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

Fuse parameters of the machine:

Type: 5ET or SMT Voltage: 250V Current: 3.15 A

X. Addendum

Schematic diagram for air conditioning:

(The specific technical parameters of the machine shall be subject to the nameplate on the product)

Schematic diagram of the air conditioning refrigeration cycle. It depicts four main components: Compressor, Condense (Condenser), Evaporat (Evaporator), and Capillary (Expansion device). Arrows indicate the flow of refrigerant through these components.

Treatment:

Don't put the abandoned machine with other unsorted waste together. Such waste shall be placed separately for other special use. ♻️

Declaration of conformity EU:

Market Maker Brand Licensing hereby declares that this equipment conforms to the essential requirements and other relevant provisions of Directive 2014/53/UE. The declaration of Conformity can be viewed at the following address: http://www.mms-support.net/OTA/ECD_MMBL_ HY-CLM12KR-001.pdf

PDF preview unavailable. Download the PDF instead.

c21d65ab-a331-4abe-b17e-22abdcb22342 Microsoft Word 2010

Related Documents

Preview Hyundai Window Air Conditioner HYWINAC17TA User Manual
User manual for the Hyundai Window Air Conditioner, model HYWINAC17TA (1.7KW). Includes safety warnings, installation guide, operation instructions, cleaning and care, specifications, and troubleshooting.
Preview Hyundai HVC502800 Air Cooler User Manual
This user manual provides essential information for operating, installing, maintaining, and safely using the Hyundai HVC502800 air cooler. It includes safety precautions, component identification, operational controls, water tank guidelines, and warranty details.
Preview Hyundai Portable Aircon HYD14KPACWA HYD18KPACWA Wi-Fi Function User Manual
User manual for Hyundai Portable Air conditioners HYD14KPACWA and HYD18KPACWA, detailing Wi-Fi module specifications, app installation, registration, login, device connection, and troubleshooting.
Preview Hyundai Air Conditioners Catalogue: Efficient Cooling Solutions
Explore the Hyundai range of advanced air conditioners, including inverter split and window models. Discover energy-efficient, reliable, and smart cooling solutions for your home, backed by 27 years of trust.
Preview Hyundai Portable Air Conditioner H-PAC-07C1UR8 H-PAC-09C1UR8 - User Manual & Specifications
Comprehensive instruction manual and technical specifications for the Hyundai portable air conditioner models H-PAC-07C1UR8 and H-PAC-09C1UR8. Learn about operation, maintenance, safety precautions, and warranty.
Preview HYUNDAI ASCI-126LBW3B Residential Air Conditioner Technical Specifications
Detailed technical specifications for the HYUNDAI ASCI-126LBW3B Residential Air Conditioner, including basic features, fan system, compressor, electrical data, connections, and dimensions. Provided by HYUNDAI Air Solution.
Preview Hyundai Electronics Split System Inverter Air Conditioner Wi-Fi Function User Manual
User manual for Hyundai Electronics Split System Inverter Air Conditioners (HYSSAC35PWA, HYSSAC52PWA, HYSSAC72PWA). Learn how to connect, register, and control your air conditioner using the Smart Life app via Wi-Fi or Bluetooth.
Preview Hyundai HY-T26 True Wireless Earphones User Manual and Specifications
User manual and specifications for Hyundai HY-T26 True Wireless Earphones, covering setup, operation, safety, warranty, and FCC compliance.