Test Report
General Information
Name of Sample | Air Conditioner |
Applicant | TCL Air Conditioner (Zhongshan) Co., Ltd. |
Classification of Test | Commission Test |
Report No. | PMC20191106004 |
Rating and Performance Tests for Air-conditioner
Applicant Name | TCL Air Conditioner (Zhongshan) Co., Ltd. |
Address | 59 Nantou Road West, Nantou, Zhongshan, Guangdong, China |
Manufacturer | TCL Air Conditioner (Zhongshan) Co., Ltd. |
Factory | Same as applicant |
Product name | Air conditioner |
Trademark | TCL |
Model / type reference | TAC-30CHS/X8 |
Rating and characteristics | 230V~60Hz |
Date of receipt of test item | 2019-11-06 |
Date(s) of test | 2019-11-06 |
Test specification/Standard | SASO 2663/2018, SASO GSO ISO 5151: 2010 |
To compile | 谭民杰 |
Audit | 王佳 |
The director of the approval | 张开结 |
Date of issue | 2019-11-06 |
This report is for the exclusive use of TCL's Client and is provided pursuant to the agreement between TCL and its Client. TCL's responsibility and liability are limited to the terms and conditions of the agreement. TCL assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the TCL name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by TCL. This test report relates only to the tested product, and shall not be reproduced except in full, without written approval of TCL.
This report by itself does not imply that the material, product, or service is or has ever been under an TCL certification program.
Test Case Verdicts
Test case verdicts | / |
Test case does not apply to the test object | N.A. |
Test item does meet the requirement | Pass |
Test item does not meet the requirement | Fail |
Procedure deviation | N.A. |
Non-standard test method | N.A. |
General remarks
The test results presented in this report relate only to the item tested.
The test report is invalid without the official stamp of TCL.
The test report is invalid without the signatures of Author and Reviewer.
Brief Description of the Tested Sample(s)
1. Ratings | |
Rated voltage/rated voltage range (V) | 230 |
Rated frequency (Hz) | 60 |
Rated input (W) | Cooling (T1): 2129, Cooling (T3): 2529, Heating: 1944 |
Rated capacity (Btu/h) | Cooling (T1): 26400, Cooling (T3): 22000, Heating: 7000W |
Rated current (A) | N/A |
2. Type of power supply | Single phase |
3. Construction of the unit | Split type |
4. Type of the unit considering if it has the air ducts | Single-duct |
5. The number of the indoor units if multi-split type | |
6. Type of the indoor unit if split type | Wall-mounted |
7. Type of outdoor unit if split type | Free-standing |
9. Supplementary heating element | No |
10. Operation function | Cooling mode and heating mode |
11. Type of the refrigerant | As attach page |
12. Mass of refrigerant (kg) | As attach page |
13. Compressor information | As attach page |
Photo of Nameplate
The document includes images of the nameplates for both the indoor and outdoor units of the TCL Split Type Air Conditioner.
Indoor Unit Nameplate Details:
- Model: TAC-30CHS/X8
- Capacity: 26400 Btu/h (7.75kW) Heating: 7000W
- Current: 9.4A
- Rated Current (IEC60335): 17.9A
- Power Input: 2129W
- Rated Power Input (IEC60335): 3300W
- EER/COP: 12.40 (Btu/h/W)
- Indoor Air Volume: 1500m³/h
- Maximum allowable pressure: 4.5MPa
- Noise: 51dB(A)
- Weight: 18kg
- Rated Voltage/Frequency: 230V~/60Hz
- Serial number: Made in China
Outdoor Unit Nameplate Details:
- Model: TAC-30CHS/X8
- Capacity: Cooling (T1): 26400 Btu/h (7.75kW), Cooling (T3): 22000 Btu/h (6.45kW), Heating: 7000W
- Current: 9.4A (T1), 11.2A (T3), 8.6A (Heating)
- Rated Current (IEC60335): 17.9A (T1), 17.9A (T3), 14.5A (Heating)
- Power Input: 2129W (T1), 2529W (T3), 1944W (Heating)
- Rated Power Input (IEC60335): 3300W (T1), 3300W (T3), 2700W (Heating)
- EER/COP: 12.40 (Btu/h/W) (T1), 8.0 (Btu/h/W) (T3), 3.60 (W/W) (Heating)
- Maximum allowable pressure: 4.5MPa
- Noise: 55dB(A)
- Weight: 60kg
- Rated Voltage/Frequency: 230V~/60Hz
- Refrigerant/Charge: R410A/2.000kg
- Outdoor Unit Water Proof Protection: IPX4
- Serial number: Made in China
Photo of Compressor
The compressor is a HIGHLY ASH215DG-C8DU, operating at 60Hz, 230V~, and is RoHS compliant. It uses R410A refrigerant. The serial number is HD72U2650030. It is manufactured by SHANGHAI HITACHI ELECTRICAL APPLIANCES CO., LTD.
Summary of Test Results
Test Method | Enthalpy Test Room | ||||||
---|---|---|---|---|---|---|---|
COOLING CAPACITY (T1) |
|
||||||
COOLING CAPACITY (T3) |
|
||||||
HEATING CAPACITY |
|
Test Result:
Pass
Note: If failed, it shall be indicated which part it was fail in.
Sample Information
Brand | TCL | ||||||||||
Model No. | KT3FR-63GW/YXA(E/6)(AVY00) | ||||||||||
Serial number | Indoor: G440N0200100G3250002, Outdoor: G440W0200100G3250002 | ||||||||||
Air-Conditioner Type | Split air conditioner | ||||||||||
Air Distribution | Two way (Up-down) | ||||||||||
Type of system | R410A | ||||||||||
Heat transfer | Cooling only and heat pump type | ||||||||||
Voltage(V) | 230 | ||||||||||
Phase | 1ph | ||||||||||
Hz | 60 | ||||||||||
Compressor |
| ||||||||||
Indoor Fan motor |
| ||||||||||
Outdoor Fan motor |
| ||||||||||
Evaporator |
| ||||||||||
Condenser |
| ||||||||||
Refrigerant | Type: R410A | ||||||||||
Mass of Refrigerant (kg) | 2.000 | ||||||||||
Dimensions | Indoor(mm): Width : 1186 Depth:340 Height:258, Outdoor(mm): Width :953 Depth:433 Height:808 |
Cooling Capacity Test (T1) Data
Test Duration(min) | 90 |
Power supplied | 220-240V |
Applied voltage (V) | 230.0 |
Frequency (Hz) | 60 |
Current (A) | 9.50 |
Power Consumption (W) | 2120 |
Power factor | 97.0% |
Fan speed settings | High speed |
Dry bulb temperature, indoor (°C) | 27.02 |
Wet bulb temperature, indoor (°C) | 19.03 |
Dry bulb temperature, outdoor (°C) | 35.01 |
Wet bulb temperature, outdoor (°C) | 23.98 |
Barometer (Pa) | 100.21 |
Indoor cooling capacity (Btu/h) | 26500 |
Sensible cooling capacity(Btu/h) | 21200 |
Latent cooling capacity (dehumidifying capacity) (Btu/h) | 5300 |
Static pressure(Pa) | 232 |
Volume flow rate of air(m3/hr) | 1503 |
Cooling capacity (Btu/h) | 26500 |
EER(Btu/h)/W | 12.50 |
Cooling Capacity Test (T3) Data
Test Duration(min) | 90 |
Power supplied | 220-240V |
Applied voltage (V) | 230.0 |
Frequency (Hz) | 60 |
Current (A) | 11.30 |
Power Consumption (W) | 2520 |
Power factor | 97.0% |
Fan speed settings | High speed |
Dry bulb temperature, indoor (°C) | 29.00 |
Wet bulb temperature, indoor (°C) | 19.00 |
Dry bulb temperature, outdoor (°C) | 46.02 |
Wet bulb temperature, outdoor (°C) | 24.01 |
Barometer (Pa) | 100.40 |
Indoor cooling capacity (Btu/h) | 22200 |
Sensible cooling capacity(Btu/h) | 20202 |
Latent cooling capacity (dehumidifying capacity) (Btu/h) | 1998 |
Static pressure(Pa) | 243 |
Volume flow rate of air(m3/hr) | 1578 |
Cooling capacity (Btu/h) | 22200 |
EER(Btu/h)/W | 8.81 |
Heating Capacity Test (H1) Data
Test Duration(min) | 90 |
Power supplied | 220-240V |
Applied voltage (V) | 230 |
Frequency (Hz) | 60 |
Current (A) | 8.65 |
Power Consumption (W) | 1930 |
Power factor | 97.0% |
Fan speed settings | High speed |
Dry bulb temperature, indoor (°C) | 20.00 |
Wet bulb temperature, indoor (°C) | 15.00 |
Dry bulb temperature, outdoor (°C) | 7.01 |
Wet bulb temperature, outdoor (°C) | 6.00 |
Barometer (Pa) | 100.58 |
Indoor heating capacity (W) | 7050 |
Sensible heating capacity (W) | 7050 |
Latent heating capacity (dehumidifying capacity) (W) | / |
Static pressure(Pa) | 234 |
Volume flow rate of air(m3/hr) | 1509 |
Heating capacity (W) | 7050 |
COP W/W | 3.65 |
Functional Performance - Cooling
Operability at Maximum cooling conditions at T3 conditions | Tested: Pass |
Minimum cooling at T3 conditions | Tested: Pass |
Freeze-up drip at T3 conditions (non-ducted AC) | Tested: Pass |
Condensate control and enclosure sweat performance | Tested: Pass |
Capacity Tests at Below Condition
Mode | Indoor air temperature | Outdoor air temperature | Test voltage | ||
---|---|---|---|---|---|
Dry bulb | Wet bulb | Dry bulb | Wet bulb | ||
Cooling mode (T1) | 27 | 19 | 35 | 24 | 230V, 60Hz |
Cooling mode (T3) | 29 | 19 | 46 | 24 | 230V, 60Hz |
Temperature (H1) | 20 | 15 | 7 | 6 | 230V, 60Hz |
Conclusion
Cooling capacity test (for condition T1)
Mode | Rated | Tested | Verifyi ng | Required EER | Verdict |
---|---|---|---|---|---|
Cooling capacity, Btu/h | 26400 | 26500 | 0.4% | >=25080 | Pass |
Cooling power input, W | 2129 | 2120 | -0.4% | <=2235 | Pass |
EER, Btu/Wh | 12.40 | 12.50 | 0.8% | >=11.80 | Pass |
Cooling capacity test (for condition T3)
Mode | Rated | Tested | Verifyi ng | Required EER | Verdict |
---|---|---|---|---|---|
Cooling capacity, Btu/h | 22000 | 22200 | 0.9% | >=20900 | Pass |
Cooling power input, W | 2529 | 2520 | -0.4% | <=2655 | Pass |
EER, Btu/Wh | 8.70 | 8.81 | 1.3% | >=8.30 | Pass |
Heating capacity
Mode | Rated | Tested | Verifyi ng | Required EER | Verdict |
---|---|---|---|---|---|
Heating capacity, W | 7000 | 7050 | 0.7% | >=6650 | Pass |
Heating power input, W | 1944 | 1930 | -0.7% | <=2041 | Pass |
COP, W/W | 3.60 | 3.65 | 1.5% | >=3.42 | Pass |
Estimated annual energy consumption (kWh/Y): 5748
Energy class: (base on rated EER at T1) D
* Verifying limit for test T1:
- Cooling capacity: ≥ 0.95 x rated capacity
- Cooling power input: ≤ 1.05x rated
- Heating capacity: ≥ 0.95 x rated capacity
- Heating power input: ≤ 1.05x rated
- EER: ≥ 0.95 x rated
- COP: ≥ 0.95 x rated