Installation Instructions
Symbio™ 700 Customer Connection Module
Precedent™ Packaged Rooftop Units
3 to 25 Tons
Model Number: FIASCCM001*
Used With: Precedent™ with Symbio™ 700 Controls
▲ SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
September 2024
ACC-SVN282A-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
- ▲ WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
- ▲ CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
- NOTICE: Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
▲ WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
▲ WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
- Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
- When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
- If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
▲ WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
- All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
- Non-Trane personnel should always follow local regulations.
▲ WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
General Information
- Carefully review installation instructions.
- This kit is used with ventilation override (Precedent™ only), remote minimum position, external auto/stop features, humidstat, and alarm indicator.
- This kit is also used with condensate overflow only when digit 39 = A.
Inspection
- Unpack all components of the kit.
- Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company.
Specifications
Operating Temperature Range | -40 to 70°C (24 Vac) | |
LEDS | Color | Description |
Green | Status | |
Red | Status | |
Agency | Green | TX |
Yellow | RX | |
UL/CSA 60730 listed | ||
UL94-5V Flammability | ||
FCC Part 15, Class B Emissions |
Parts List
Figure 1. Kit contents
A diagram showing the components of the kit: a main circuit board (1), screws (2), a harness (3), and an information label (4).
Table 2. Kit parts list
Item | Description | Qty |
1 | Customer Connection module | 1 |
2 | Screws | 4 |
3 | Harness IMC communication (product dependent) | 2 |
4 | Information label | 1 |
Installation
▲ WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
- Confirm power to the unit has been disconnected and locked out.
- For Precedent™ units, open the access panel to gain access to the right side of the main unit control box.
- Install the customer connection module and secure the board with four screws (provided in kit). Confirm P5 connector is aligned to the top right position for B/C/D cabinet installations. 3 to 5 ton products (A cabinet) P5 connector is aligned to the lower right position.
Figure 2. Precedent B/C/D - customer connection module
A diagram showing the Precedent B/C/D unit with the customer connection module installed.
Figure 3. Precedent A cabinet - customer connection module
A diagram showing the Precedent A cabinet with the customer connection module installed.
- On the customer connection module, set the address rotary switches to 78. This is required to integrate the customer connection module with the Symbio™ controller. After installation is complete, the Symbio 700 UC configuration will need to be updated to enable this installed feature. UC configuration needs to be updated to enable this installed feature using Symbio Service and Installation Mobile application or Symbio 700 User Interface.
- Connect the harness included in kit (harness with blue connector) to customer connection module P5 and adapter board J19 per unit diagram. Note: The unit wiring diagram is located on the control box high voltage door.
- Close the access panel.
- Apply the information label next to the unit nameplate.
- Connect power to the unit. Refer to the troubleshooting section in the unit installation guide, if needed.