Trane Precedent Packaged Rooftop

Unit Overview - TSJ120A4S00

Unit Overview

ApplicationUnit SizeSupply Fan AirflowTotal Static PressureExternal Dimensions (in.)Operating WeightEERIEER/SEERElevation
HeightWidthLength
DX Cooling / Electric Heat10 Ton3700 cfm0.500 in H2O4.24 ft4.44 ft7.34 ft964.4 lb11.2014.800.00 ft

Unit Electrical

  • Voltage/phase/hertz: 460/60/3
  • MCA: 62.00 A
  • MOP: 70.00 A
  • Condenser Fan FLA: 1.40 A
  • Evaporator Fan FLA: 4.60 A
  • Electric Heat FLA: 0.00 A
  • Electric heat FLA (230V): 0.00 A
  • Compressor 1 RLA: 13.20 A
  • Compressor 2 RLA: 5.80 A
  • Compressor Power: 8.66 kW
  • System Power: 10.88 kW

Controls

  • Unit Controls: Symbio 700
  • Options Module: Indoor Options module

Cooling Section

Cooling Conditions

Value
Entering Dry Bulb80.00 F
Entering Wet Bulb67.00 F
Ambient Temp95.00 F
Leaving Coil Dry Bulb56.96 F
Leaving Coil Wet Bulb56.19 F
Leaving Unit Dry Bulb58.46 F
Leaving Unit Wet Bulb56.80 F
Saturated Discharge Temperature118.85 F
Saturated Suction Temperature50.50 F

Capacity

Value
Gross Total122.57 MBh
Gross Latent30.72 MBh
Gross Sensible91.85 MBh
Net Total119.56 MBh
Net Sensible88.85 MBh
Net Sensible Heat Ratio74.31%
Fan Motor Heat0.51 MBh
Refrig Charge-Circuit 110.1 lb

Heating Section

Output Heating Capacity: 122.94 MBh

Heating EAT: 65.00 F

Heating LAT: 95.26 F

Heating Temp Rise: 30.26 F

Fan Section

Indoor Fan Data

Value
Airflow ApplicationHorizontal
Design ESP0.500 in H2O
Component SP0.000 in H2O
Heat SP0.000 in H2O
Total SP0.500 in H2O
Supply Fan Count1.00 Number
Indoor Fan Drive TypeVariable Direct
Indoor Fan Quantity1.00 Number
Indoor Fan TypeBC Plenum

Indoor Fan Performance

Value
Airflow3700 cfm
Supply Motor Horsepower3.000 hp
Indoor Motor Operating Power1.015 hp
Indoor RPM1163 rpm

Outdoor Fan Data

Value
Outdoor Fan Drive TypeDirect
Outdoor Fan Quantity1.00 Number
Outdoor Fan TypePropeller

Field Installed Accessories

  • Electric heater: 36 kW electric heater
  • Options module: Indoor Options module
  • Fresh air selection: Manual outside damper 0-25%

Acoustics

Sound Path63 Hz125 Hz250 Hz500 Hz1 kHz2 kHz4 kHz8 kHz
Ducted Discharge86 dB83 dB77 dB71 dB66 dB63 dB62 dB63 dB
Ducted Inlet81 dB74 dB71 dB62 dB59 dB58 dB55 dB54 dB
Outdoor Noise86 dB87 dB93 dB90 dB88 dB84 dB80 dB74 dB

Note: Ducted Discharge and Ducted Inlet Sound in accordance with AHRI 260-2017

Note: Outdoor Sound in accordance with AHRI 270-2015

Dimensions

The unit is a packaged rooftop unit designed for DX Cooling and Electric Heat. Diagrams illustrate its physical layout and connection points.

Overall Unit Layout: The unit features access panels for the Evaporator Section, Control Box, and Compressor. It includes a Condenser Fan, Condenser Coil with Coil Guard, and designated holes for unit control wiring (7/8" dia.), service gauge ports (1 3/8" dia.), and unit power wiring.

Drainage: A condensate drain connection is provided, typically a 3/4"-14 NPT DIA. HOLE.

Airflow Openings:

  • Downflow Configuration: The plan view shows distinct SUPPLY and RETURN air openings. The dimensions indicate the placement and size of these openings relative to the unit's footprint.
  • Horizontal Configuration: A separate view shows the openings for horizontal airflow, again with SUPPLY and RETURN designations.

Key Dimensions:

  • Baserail Length: Approximately 88 1/2 inches.
  • Baserail Width: Approximately 53 1/4 inches.
  • Other dimensions include height (4.24 ft), width (4.44 ft), and length (7.34 ft) as noted in the Unit Overview.

Weights and Clearances

The unit requires specific clearances for proper operation and maintenance. The diagram indicates these zones.

  • Clearances: Specified clearances include 36 inches on multiple sides, 48 inches on one side, and 72 inches on another, depending on the airflow configuration (horizontal vs. downflow).
  • Approximate Installed Weight: 964.4 lb.
  • Corner Weights (for base unit only):
    • (A) Corner Weight: 341.0 lb
    • (B) Corner Weight: 318.0 lb
    • (C) Corner Weight: 183.0 lb
    • (D) Corner Weight: 196.0 lb

Note: Installed weight includes all selected options and accessories. Corner weights do not include options or accessories.

Wiring Diagrams

Symbio 700 Wiring (Field Wiring Drawing)

The Symbio 700 control system connects to various components via terminal blocks. Key connections include:

  • ACNET: ACNET OUT (+/-) and ACNET IN (+/-) for network communication.
  • Zone Sensor: Connections for ZONE TEMP and COOLING SET POINT, with terminals labeled 1 through 7.
  • Building Automation System (BAS): Terminals for 24 VAC OUT, COMMON, and other control signals (e.g., 1Y, 2Y, 3Y, 4Y) for integration with a BAS.
  • Optional Remote Sensor: Connections for SPACE HUMIDITY and LOCAL OCCUPANCY, with 24 VDC OUT and COMMON terminals.
  • Thermostat: Connections for T-STAT Y1, W1/0, G/VAV CHANGEOVER, W2, Y2, X2, PULLDOWN-T, and GND, with 24 VAC OUT and COMMON terminals.
  • CO2 Sensor: Connections for CO2 IN and COMMON, with terminals labeled 1 through 3.

The diagram references specific terminal blocks like J17, J18, J19, J20, J21, J22, and J23 for the Symbio 700.

Optional Electric Heat Wiring (Field Wiring Drawing)

Connections for optional electric heat stages are shown:

  • Electric Heat Stage 1: Wired via terminal block P6 J6. Connections include COMMON, 1 BK (Black), and 2 2R, leading to HC1 A/B.
  • Electric Heat Stage 2: Wired via terminal block P7 J7. Connections include COMMON, 1 BK (Black), and 2 2R, leading to HC2 A/B.

Fan Performance Curves

The document includes fan performance curves illustrating the relationship between Airflow (CFM) and External Static Pressure (in H2O) for different fan operating conditions.

Configurations: Curves are provided for both Downflow and Horizontal airflow configurations, specifically for the TSJ072-120* model.

Parameters Displayed:

  • Airflow (CFM): The horizontal axis represents the volume of air moved.
  • External Static Pressure (in H2O): The vertical axis represents the resistance the fan must overcome.
  • Fan Speed (RPM): Various curves indicate performance at different fan speeds (e.g., 800 RPM to 1900 RPM).
  • Motor Horsepower (bhp): Dashed lines indicate the power consumption of the fan motor at different operating points (e.g., 1 bhp, 1.50 bhp, 2 bhp, 3.1 bhp, 4.6 bhp, 5 bhp).
  • Wet Coil (WO) and Airflow Percentage: Some curves are labeled with percentages (e.g., 45% WO, 50%, 60%, 70%, 80%, 90%) which likely relate to airflow modulation or operating conditions.

Note: The fan curves are applicable to TSJ/WSJ units. For YSJ units, additional static pressure must be accounted for when using a Gas Heat Exchanger.

PDF preview unavailable. Download the PDF instead.

10-ton-PACKAGE-UNIT Adobe PDF library 17.00 Adobe Illustrator(R) 24.0

Related Documents

Preview Trane Precedent™ Rooftop Air Conditioners | eFlex™ Technology Product Catalog
Explore the Trane Precedent™ series of packaged rooftop air conditioners, featuring eFlex™ Technology for cooling and gas/electric applications. This catalog details units from 3 to 10 tons (60 Hz), highlighting advanced controls, performance specifications, and key features for light commercial HVAC needs.
Preview Trane Precedent™ High Efficiency Packaged Rooftop Heat Pumps: Product Catalog
Discover the Trane Precedent™ series of high-efficiency packaged rooftop heat pumps, designed for exceptional reliability and advanced comfort control. This catalog details features, specifications, and applications for units ranging from 12.5 to 25 tons, highlighting Trane's commitment to quality and performance in commercial HVAC solutions.
Preview Installation Instructions: Symbio™ 700 Fresh Air Options Module for Trane Precedent™ Rooftop Units
Comprehensive installation guide for the Symbio™ 700 Fresh Air Options Module, designed for Trane and American Standard Precedent™ Packaged Rooftop Units (3 to 25 Tons). Includes safety warnings, parts list, specifications, and step-by-step installation procedures.
Preview Trane Foundation™ Packaged Rooftop Units: Installation, Operation, and Maintenance Guide
Comprehensive guide for Trane Foundation™ Packaged Rooftop Units (15-25 Tons, Cooling Only with Electric Heat). Covers installation, operation, maintenance, safety warnings, and technical specifications for models like EDK180-300.
Preview Trane Precedent™ Power Exhaust Kit Installation Instructions
Installation guide for Trane Precedent™ packaged rooftop units (3-25 Tons) with Power Exhaust Kits for Standard and Low Leak Economizers. Covers model numbers FIAPWRX*01*, FIAPWRX*02*, FIAPWRX*03*, including safety warnings, parts lists, wiring, and configuration.
Preview Trane Precedent Rooftop Units Low Leak Economizer Installation Instructions
Detailed installation instructions for Trane Precedent™ Packaged Rooftop Units with Symbio™ 700 Controls, covering Low Leak Economizer models FIAECON101 through FIAECON203. Includes safety warnings and procedures.
Preview Trane Precedent™ Packaged Heat Pump: Convertible 3-10 Tons | Features & Specs
Explore the Trane Precedent™ Packaged Heat Pump series, featuring convertible 3-10 ton capacities. Discover standard features, added flexibility, factory-installed options, and detailed specifications for efficient light commercial HVAC solutions.
Preview Trane Voyager Commercial Rooftop Air Conditioner Installation, Operation, and Maintenance Manual
Detailed guide for Trane Voyager Commercial Packaged Rooftop Air Conditioners (27.5-50 Tons). Covers installation, operation, maintenance, safety warnings, and system operation for units with ReliaTel™ Controls and eStage™.