Cat® D300 GC DIESEL GENERATOR SETS
Standby: 60 Hz, 208V, 480V & 600V
PACKAGE PERFORMANCE
Performance | Standby | Performance Strategy |
---|---|---|
Frequency | 60 Hz | EPA Certified for Stationary Emergency Application |
Genset Power Rating | 375 kVA | |
Gen set power rating with fan @0.8 power factor | 300 ekW | |
Emissions | EPA TIER 3 | |
Performance Number | DM8168 |
Engine Specifications
Engine Model | Cat® C9 In-line 6, 4-cycle diesel |
Bore x Stroke | 112mm x 149mm (4.4in x 5.9in) |
Displacement | 8.8 L (538 in³) |
Compression Ratio | 16.3:1 |
Aspiration | Turbocharged Air-to-Air Aftercooled |
Fuel Injection System | HEUI |
Governor | Electronic ADEM™ A4 |
Fuel Consumption
Standby | |
---|---|
100% load with fan | 86.0 L/hr (22.7 gal/hr) |
75% load with fan | 58.8 L/hr (15.5 gal/hr) |
50% load with fan | 43.8 L/hr (11.6 gal/hr) |
25% load with fan | 33.1 L/hr (8.7 gal/hr) |
Cooling System
Radiator air flow restriction (system) | 0.12 kPa (0.48 in. Water) |
Radiator air flow | 497 m³/min (17551 cfm) |
Engine coolant capacity | 14 L (3.69 gal) |
Radiator coolant capacity | 25 L (6.6 gal) |
Total coolant capacity | 45 L (11.88 gal) |
Inlet Air
Combustion air inlet flow rate | 24.6 m³/min (868.7 cfm) |
Max. Allowable Combustion Air Inlet Temp | 49 °C (120°F) |
Exhaust System
Exhaust stack gas temperature | 495 °C (923°F) |
Exhaust gas flowrate | 69.7 m³/min (2461 cfm) |
Exhaust system backpressure (maximum allowable) | 10.0 kPa (40.0 in. water) |
Heat Rejection
Heat rejection to jacket water | 120 kW (6838 Btu/min) |
Heat rejection to exhaust (total) | 320 kW (18223 Btu/min) |
Heat rejection to aftercooler | 92 kW (5239 Btu/min) |
Heat rejection to atmosphere from engine | 23 kW (1312 Btu/min) |
Heat rejection from alternator | 22 kW (1245 Btu/min) |
Emissions (Nominal)
Emissions | Standby |
---|---|
NOx | 2371.7 mg/Nm³ (4.27 g/hp-hr) |
CO | 216 mg/Nm³ (0.45 g/hp-hr) |
HC | 43.7 mg/Nm³ (0.11 g/hp-hr) |
PM | 24.8 mg/Nm³ (0.07 g/hp-hr) |
Alternator
Voltages | Standby |
---|---|
480V | 705 |
208V | 549 |
600V | 1117 |
Motor Starting Capability @30% Voltage Dip | 451 |
Current | 1041 |
Frame Size | M2774L4 |
Excitation | S.E |
Temperature Rise | 105°C |
WEIGHTS & DIMENSIONS – OPEN SET
Dim "A" mm (in) | Dim "B" mm (in) | Dim "C" mm (in) | Generator Set Weight kg (lb) | |
---|---|---|---|---|
Skid (Wide Base) | 3950 (155.5) | 1440 (56.7) | 1706 (67.2) | 2503 (5518.2) |
Integral Tank Base | 3950 (155.5) | 1430 (56.3) | 2202 (86.7) | 3143 (6929.1) |
FUEL TANK CAPACITY
Tank Design | Total Capacity Litre | Gallon | Useable Capacity Litre | Gallon |
---|---|---|---|---|
Integral | 2270 | 600 | 2059 | 544 |
DEFINITIONS AND CONDITIONS
- For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
- Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
- UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
APPLICABLE CODES AND STANDARDS:
AS1359, CSA C22.2 No.100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA 70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.
STANDBY: Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings also apply at IS03046 standard conditions.
Fuel Rates are based on fuel oil of 35° API [16° C (60° F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29° C (85° F) and weighing 838.9 g/litre (7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer requirements, contact your Caterpillar representative for details. For information regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.
Circuit Breakers
Manually Operated Circuit Breakers
Current (A) | Frame | Number of Poles | Interrupting Ratings (kArms) 240V | 480V | 600V | Trip Units | (Lugs) Cable Size Range / Phase | Auxiliary Options |
---|---|---|---|---|---|---|---|---|
100 | H | 3 | 65 | 35 | 18 | Electronic LSI | 8-3/0 AWG | Form C (1NO + 1NC), Shunt Trip 24VDC |
250 | J | 3 | 65 | 35 | 18 | (2) 3/0 - 250 kcmil | Form C (1NO + 1NC), Shunt Trip 24VDC | |
400 | T5N | 3 | 65 | 25 | 18 | Electronic LSI | (3) 2/0 – 400 kcmil | 1 Form C + 1 Bell Alarm 250VAC/VDC, Shunt Trip 24VDC |
600 | T6N | 3 | 65 | 35 | 20 | (S or I) | (3) 2/0 – 400 kcmil | 1 Form C + 1 Bell Alarm 400VAC/250VDC, Shunt Trip 24VDC |
800 | T6N | 3 | 65 | 35 | 20 | or LSI | (3) 2/0 – 400 kcmil | 1 Form C + 1 Bell Alarm 400VAC/250VDC, Shunt Trip 24VDC |
1200 | T7S | 3 | 65 | 50 | 25 | (4) 2/0 - 500 kcmil | 1 Form C + 1 Bell Alarm 24VDC | |
1600 | R | 3 | 65 | 35 | 18 | (2) 3/0 - 250 kcmil | BUS BAR | |
2000 | R | 3 | 65 | 35 | 18 | Electronic LSI | BUS BAR | Form C (1NO + 1NC), Shunt Trip 24VDC |
2500 | R | 3 | 65 | 35 | 18 | BUS BAR | Form C (1NO + 1NC), Shunt Trip 24VDC | |
3000 | R | 3 | 65 | 35 | 18 | BUS BAR | Form C (1NO + 1NC), Shunt Trip 24VDC |
Electrically Operated Circuit Breakers
Current (A) | Frame | Number of Poles | Interrupting Ratings (kArms) 240V | 480V | 600V | Trip Units | (Lugs) Cable Size Range / Phase | Auxiliary Options |
---|---|---|---|---|---|---|---|---|
800 | T 7M-S | 3 | 65 | 50 | 25 | Electronic LSI | (4) 4/0 – 500 kcmil | 2 Form C + 1 Bell Alarm 24VDC |
1200 | T 7M-S | 3 | 65 | 50 | 25 | Electronic LSI | (4) 4/0 - 500 kcmil | 2 Form C + 1 Bell Alarm 24VDC |
2000 | T8M-S | 3 | 125 | 125 | 100 | Electronic LSI | BUS BAR | 2 Form C + 1 Bell Alarm 24VDC |
3000 | T8M-S | 3 | 125 | 125 | 100 | Electronic LSI | BUS BAR | 2 Form C + 1 Bell Alarm 24VDC |
Single Breaker Options (250 – 3000A)
Model | Current (A) | Operation |
---|---|---|
C9 ACERTTM | 250 | Manually Operated |
C9 ACERT | 400 | Manually Operated |
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 600 | Manually Operated |
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 800 | Manually Operated or Electrically Operated |
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 1200 | Manually Operated or Electrically Operated |
C13 ACERT, C15 ACERT, C18 ACERT | 1600 | Manually Operated |
C15 ACERT, C18 ACERT | 2000 | Manually Operated or Electrically Operated |
C18 ACERT | 2500 | Manually Operated |
C18 ACERT | 3000 | Manually Operated or Electrically Operated |
Multiple Breaker Options
Model | Main Breaker Box 1st Breaker (Amps) Manually Operated | Main Breaker Box 2nd Breaker (Amps) Manually Operated | Auxiliary Box Breaker (Amps) Manually Operated |
---|---|---|---|
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 250 | Manually Operated | |
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 400 | ||
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 600 | ||
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 800 | 250, 400, 600, 800, or 1200 | 3rd Breaker: 250 or 400 (Not available if 1st & 2nd Breaker = 1200A) |
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT | 1200 | ||
C13 ACERT, C15 ACERT, C18 ACERT | 1600 | ||
C15 ACERT, C18 ACERT | 2000 | Not Available | 2nd Breaker: 250 or 400 |
C18 ACERT | 2500 | ||
C18 ACERT | 3000 |
H-Frame Circuit Breakers
Long Time/Short Time Trip Curve
60A, 100A, 150A H-Frame
The time-current curve information is to be used for application and coordination purposes only.
Notes:
- There is a thermal-imaging effect that can act to shorten the long-time delay. The thermal imaging effect comes into play if a current above the long-time delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately 20 minutes is required between overloads to completely reset thermal-imaging.
- Total clearing times shown include the response times of the trip unit, the circuit breaker opening, and the extinction of the current.
- Curves apply from -35°C to +70°C (-31°F to +158°F) ambient temperature.
Instantaneous Trip Curve
60A, 100A, 150A H-Frame
The time-current curve information is to be used for application and coordination purposes only.
Notes:
- There is a thermal-imaging effect that can act to shorten the long-time delay. The thermal imaging effect comes into play if a current above the long-time delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately 20 minutes is required between overloads to completely reset thermal-imaging.
- Total clearing times shown include the response times of the trip unit, the circuit breaker opening, and the extinction of the current.
- In = Maximum dial setting of Ir.
- 60A H-Frame: In = 60A = Max Ir setting
- 100A H-Frame: In = 100A = Max Ir setting
- 150A H-Frame: In = 150A = Max Ir setting
- Curves apply from -35°C to +70°C (-31°F to +158°F) ambient temperature.
J-Frame 250 A Typical Peak Let-Through Curves
ELECTRONIC MOLDED CASE CIRCUIT BREAKERS J-FRAME CURRENT LIMITING CIRCUIT BREAKERS 250 A FRAME AT 240, 480 AND 600 V, 30 150-250 A
J-Frame 150-250 A (JD, JG, JJ, JL, and JR) Thermal-Magnetic Trip
JD, JG, JJ, JL, JR MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 50-5 CRI CURT BREAKFORMATION
This curve is to be used the application and coordewtion purposes only. The curatay fastur of the bottin of the page should be wond curing coordination stades. All cherveis baped on 4 annookd start Taminationsaremadewithconductions of appropriate krigthandrat ings.
Ground Fault Module GFM250JD Trip Curve
Pickup Levels ±10%
Circuit Breaker Wil Instantaneous Trip Above 2500 A
T5 400/600 - PR221DS
Tmax T5 Ekip E L-S-I Functions
T6 600/800 -PR221DS
L-1 Functions
T6 600/800 -PR221DS
L-S Functions
Tmax T7 PR231/P Functions
L-S Functions
T6 800 - PR222DS and PR222DS/PD-A
L-S-I Functions
T7 1000/1200 - PR232/P
L-S-I Functions
T7 1000/1200 - PR332/P
L-S-I Functions
T8 1600/2000/2500/3000 - PR232/P-T8
L-S-I Functions
P, R, NS-Frame Long-Short Trip Curve and NW-Frame Long-Short Trip Curve
Long-time Pickup and Delay Short-time Pickup and I2t OFF Delay
The time-current curve information is to be used for application and coordination purposes only. Curves apply from -30°C to +60°C ambient temperature.
Notes:
- There is a thermal-imaging effect that can act to shorten the long-time delay. The thermalimaging effect comes into play if a current above the long-time delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately 20 minutes is required between overloads to completely reset thermal-imaging.
- The end of the curve is determined by the interrupting rating of the circuit breaker.
- With zone-selective interlocking on, short-time delay utilized and no restraining signal, the maximum unrestrained short-time delay time band applies regardless of the setting.
- Total clearing times shown include the response times of the trip unit, the circuit breaker opening, and the extinction of the current.
- For a withstand circuit breaker, instantaneous can be turned OFF. See Page 22 for instantaneous trip curve. See tables on pages 03-18 for instantaneous override values.
- Overload indicator illuminates at 100%.
P, R, NS-Frame Instant Curve and NW-Frame Instant Trip Curve
Instantaneous Pickup 2x-15x and OFF
The time-current curve information is to be used for application and coordination purposes only. Curves apply from -30° to +60°C ambient temperature.
Notes:
- The end of the curve is determined by the interrupting rating of the circuit breaker.
- Total clearing times shown include the response times of the trip unit, the circuit breaker opening, and the extinction of the current.
- The instantaneous region of the trip curve shows maximum total clearing times. Actual clearing times in this region can vary depending on the circuit breaker mechanism design and other factors. The actual clearing time can be considerably faster than indicated. Contact your local Sales Office for additional information.
- For a withstand circuit breaker, instantaneous can be turned OFF. See tables on pages 03-18 for instantaneous override values.
- See page 22 for long-time pickup, long-time delay, short-time pickup, and short time delay trip curves.
P, R, NS-Frame Ground Curve and NW-Frame Ground Fault Trip Curve
Ground-fault I²t OFF and ON In ≤ 400 A
The time-current curve information is to be used for application and coordination purposes only. Curves apply from -30°C to +60°C ambient temperature.
Attachments
Jacket Water Heater (WHHH01/WHHH03)
Appropriate when the generator set is to be sited in a low ambient environment, the heater maintains the engine coolant at a temperature [typically 38°C (100°F)] which facilitates rapid starting and load acceptance. The heater assembly uses UL compliant components (to UL1030) and has CSA certification which is to both CSA and UL Standards.
The heater itself is powered by a 240V for 60 Hz AC auxiliary supply. A thermostatic controller is included to regulate the output temperature to within safe limits. When the generator set is not running the heater is automatically connected to the AC supply through a power relay mounted in the control panel.
Upon receiving a start signal the AC supply is automatically disconnected by the power relay and automatically reconnected when the start signal is removed, and the engine has stopped.
Features
- Uniform heat distribution
- Reduces wear from cold spots
- Improves startability
- Thermostatically controlled and protected
- 6' (1.8m) cord length (577-1758)
- 16.4' (5.0m) cord length (578-9355).
- Ensures generator is at optimal starting temperature and ready to accept load
- Durable pump with non-magnetic impeller that does not attract metal debris
- Robust die cast aluminum housing improves sealing of the hoses, eliminates leaking and breakage
- Corrosion resistant steel brackets for superior strength and durability
- Reduces thermal stress on coolant hoses
- Element designed for long life with maximum heat transfer
- IP44 Ingress Protection Rating
- No evaporation of coolant from hoses
- Reduces low coolant level alarms because coolant does not boil
Part No | Outlet Location | Watts | Volts | Amps | Regulating Thermostat | Safety Thermostat |
---|---|---|---|---|---|---|
577-1758/578-9355 | Right | 2700 | 240 | 11.25 | On 90°F (32°C) Off 115°F (46°C) | 210°F (98°C) |
BATTERY CHARGER
The intelligent battery charger has been developed with safety, usability, optimised battery performance and maximum battery lifetimes in mind.
A comprehensive range of input and output protections ensures a continued safe charging environment also enabling the use of the charger as a power supply.
Features
- Intelligent two, three and four stage charging profiles
- Configurable to suit most battery types (12V/24V)
- Adjustable current limit
- Can be used as a battery charger, power supply or both at the same time
- Automatic or Manual boost and storage charge functions to help maintain battery condition
- Digital Microprocessor Technology
- Temperature compensation for battery charging
- Low Output Ripple and superb line regulation
- Three LED Indicators
- AC input Under voltage
- AC input Over voltage
- Battery charger output Over voltage
- Battery charger output Over current
- Optional battery temperature compensation with over temperature protection
- Output short circuit and Inversion polarity with auto recovery
- Configurable charge termination
- UL1236/UL1564 Compliant
Automatic Boost Mode
- Boosts and equalises cell charge improving battery performance and life
Power Save Mode
- Once the battery is fully charged the chargers switch to Eco-Power to save energy
Communication
- Can be integrated into external systems through MODBUS RTU using RS485
- Fully configurable via PC Software
Benefits
- Fully flexible to maximise the life of the battery
- Suitable for a wide range of battery types
- Switched mode design
- Minimum 86% efficiency throughout full operating range
- No external intervention for boost mode
- Multiple chargers can be linked together to provide larger current output
- Can be permanently connected to battery and mains (utility) supply. No need to disconnect through high load conditions.
GFCI Receptacles
Features and Benefits
- Automatically tests the GFCI every time the reset button is pushed in. The GFCI will not reset if the GFCI circuit is not functioning properly.
- By blocking reset of the GFCI if protection has been compromised, SmartLockPRO reduces the possibility of end-users incorrectly assuming that a reset GFCI outlet is providing ground fault protection when it actually is not.
- A line-load reversal diagnostic feature is provided which prevents the GFCI from being reset and stops power from being fed to the GFCI receptacle face or through to downstream devices. A green LED indicator on the GFCI's face also illuminates to alert the installer to the line-load wiring reversal.
Weather-Resistant GFCIS
- Meet UL 498 requirements for weather-resistant receptacles.
Tamper-Resistant GFCIs
- Shutter mechanism inside the receptacle blocks access to the contacts unless a two-prong plug is inserted, helping ensure foreign objects will be locked out.
Product Features
- Grounding: GFCI ground fault
- Feature: Weather and tamper-resistant
- Amperage: 20 Amp
- Voltage: 125 Volt
- Trip Level: Class A, 5mA plus or minus 1mA
- NEMA: 5-20R
- Pole: 2
- Wire: 3
- Color: White
Standards and Certifications
- NEMA: WD-6
- ANSI: C-73
- UL498: File E13399
- CSA C22.2 No. 42: File LR-57811
- UL 943: File E48380
- NOM: 057
Receptacles contained in a weather resistant box and in-use cover.
INTEGRAL FUEL TANKS
INTEGRAL FUEL TANKS D250 GC – D600 GC
FEATURES
- UL Listed for United States (UL 142) and Canada (CAN/ULC S601)
- Facilitates compliance with NFPA 30 code, NFPA 37 and 110 standards and CSA C282 code
- Dual wall
- Low fuel level warning standard, customer configurable warning or shutdown
- Primary tank leak detection switch in containment basin
- Tank design provides capacity for thermal expansion of fuel
- Fuel supply dip tube is positioned so as not to pick up fuel sediment
- Fuel return and supply dip tube is separated by an internal baffle to prevent immediate re-supply of heated return fuel
- Pressure washed with an iron phosphate solution
- Interior tank surfaces coated with a solvent-based thin-film rust preventative
- Heavy gauge steel gussets with internal lifting rings
- Primary and secondary tanks are leak tested at 20.7 kPa (3 psi) minimum
- Compatible with open packages and enclosures
- Gloss black polyester alkyd enamel exterior paint
- Welded steel containment basin (minimum of 110% of primary tank capacity)
- Direct reading fuel gauge with variable electrical output
- Emergency vents on primary and secondary tanks are sized in accordance with NFPA 30.
INTEGRAL
- Integral diesel fuel tank is incorporated into the generator set base frame
- Robust base design includes linear vibration isolators between tank base and engine generator.
OPTIONS
- Audio/visual fuel level alarm panel
- 5gal (18.9 L) spill containment*
- Locking Fuel Fill
- Overfill prevention Valve*
*Applicable for D350GC-D600GC Models only
Integral Fuel Tank Base Useable Capacities with Fuel Tank Dimensions & Weights
Standby ekW | Width mm | Width in | Width mm | Width in |
---|---|---|---|---|
250-300 | 1430 | 56.3 | ||
350-400 | 1630 | 64.1 | ||
450-500 | 1630 | 64.1 | ||
550-600 | 1865 | 73.4 |
A. Open Set & Sound Attenuated Enclosure
Tank Design Feature Code | Total Capacity Litre | Gallon | Useable Capacity Litre | Gallon | Dry Weight kg | lb | Tank Only Height 'H' mm | in | Length 'L' mm | in | Overall Package Height with Tank Open mm | in | Enclosure mm | in |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Integral Tank FTDW035 | 2270.7 | 599.8 | 2059.9 | 543.9 | 970 | 2138 | 762.4 | 30.0 | 3958 | 155.8 | 2202 | 86.7 | 2487 | 97.9 |
FTDW036 | 2820 | 744.9 | 2553 | 674.4 | 1165 | 2568 | 818.8 | 32.2 | 4815 | 189.5 | 2584 | 101.7 | 2644 | 104 |
FTDW037 | 3671 | 969.7 | 3323 | 877.8 | 1331 | 2934 | 668.2 | 26.3 | 4622 | 181.9 | 2456 | 96.7 | 2721 | 107.1 |
FTDW038 | 4292 | 1133.8 | 3889 | 1027.3 | 1657 | 3653 | 816.4 | 32.1 | 4980 | 196.1 | 2560 | 100.7 | 2721 | 107.1 |
B. Estimated Run Time (Hours)
Tank Design | Feature Code | ekW | 100% | 75% | 50% | |||
---|---|---|---|---|---|---|---|---|
Hrs | L/hr | Hrs | L/hr | Hrs | L/hr | |||
Integral Tank FTDW035 | 250 | 28.1 | 73.3 | 35 | 58.8 | 47 | 43.8 | |
300 | 24 | 86.0 | 30.8 | 66.8 | 40 | 51.5 | ||
FTDW036 | 350 | 27.1 | 94.3 | 31.2 | 81.9 | 42.4 | 60.2 | |
400 | 24.1 | 105.9 | 28.1 | 90.7 | 38.6 | 66.2 | ||
FTDW037 | 450 | 25.2 | 131.7 | 31.3 | 106.1 | 42.0 | 79.1 | |
500 | 24.3 | 137 | 30.1 | 110.5 | 46.6 | 71.3 | ||
FTDW038 | 550 | 25.7 | 151.1 | 32.9 | 118.1 | 45.2 | 86.1 | |
600 | 24.1 | 161.6 | 30.0 | 129.6 | 42.4 | 91.7 |
ENCLOSURES
SOUND ATTENUATED LEVEL 2 ENCLOSURES D250GC – D600GC 60 Hz
FEATURES
- Robust/Highly Corrosion Resistant Construction
- Factory installed on skid base or tanks base
- Environmentally friendly, polyester powder baked paint
- Enclosure constructed with 18-gauge steel
- Interior zinc plated fasteners
- Internally mounted exhaust silencing system
- Comply with ASCE/SEI 7 for Wind loads up to 100mph
- Designed and tested to comply with UL 2200 Listed generator set package
- Excellent Access
- Large cable entry area for installation ease.
- Accommodates side mounted single or multiple breakers.
- Two doors on both sides.
- Vertically hinged allow 180° opening rotation
- Radiator fill cover.
- Security and Safety
- Lockable access doors which give full access to control panel and breaker.
- Cooling fan and battery charging alternator fully guarded.
- Fuel fill, oil fill and battery can only be reached via lockable access.
- Externally mounted emergency stop button (Optional).
- Designed for spreader bar lifting to ensure safety.
- Stub-up area is rodent proof.
Sound Attenuated Level 2
- Caterpillar white paint
- UL Listed integral fuel tank with 24 hours running time capacity (Optional).
- DC lighting package (Optional)
Enclosure Package Operating Characteristics
Enclosure Type | Standby ekW | Cooling Air Flow Rate m³/s | cfm | Ambient Capability* °C | °F | Sound Pressure Levels (dBA) at 7m (23 ft) 100% Load |
---|---|---|---|---|---|---|
Level 2 Sound Attenuated Enclosure (Steel) | 250 | 6.4 | 13561 | 57 | 135 | 74 |
300 | 6.4 | 13561 | 51 | 125 | 74 | |
350 | 7.4 | 15680 | 57 | 134 | 71 | |
400 | 7.4 | 15680 | 53 | 127 | 71 | |
450 | 8.4 | 17692 | 54 | 130 | 73 | |
500 | 8.4 | 17692 | 50 | 122 | 73 | |
550 | 11.2 | 23731 | 56 | 133 | 73 | |
600 | 11.2 | 23731 | 53 | 127 | 73 |
*Cooling system performance at sea level. Consult your Cat® dealer for site specific ambient and altitude capabilities.
Note: Sound level measurements are subject to instrumentation, installation and manufacturing variability, as well as ambient site conditions.
DIMENSIONS
Sound Attenuated Enclosure on Skid Base
Sound Attenuated Enclosure on a UL Listed Integral Fuel Tank Base
WEIGHTS & DIMENSIONS
Enclosure Type | Standby Ratings, ekW | Length, L mm | in | Width, W mm | in | Height, H mm | in | Package Weights kg | Ib |
---|---|---|---|---|---|---|---|---|---|
Sound Attenuated Enclosure on Skid Base | 250 | 3958 | 155.8 | 1440 | 56.7 | 1991 | 78.4 | 2857 | 6298.6 |
300 | 4633 | 182.4 | 1630 | 64.2 | 2227 | 87.7 | 2945 | 6492.6 | |
350 | 3983 | 8781.0 | |||||||
400 | 4017 | 8856.0 | |||||||
450 | 4823 | 189.8 | 1630 | 64.2 | 2777 | 109.3 | 4408 | 9718.0 | |
500 | 4457 | 9826.0 | |||||||
550 | 4980 | 196.1 | 1865 | 73.4 | 2723 | 107.2 | 4754 | 10480.8 | |
600 | 4837 | 10663.8 | |||||||
Sound Attenuated Enclosure on UL Listed Integral Fuel Tank Base | 250 | 3958 | 155.8 | 1440 | 56.7 | 2487 | 97.9 | 3497 | 7709.6 |
300 | 4633 | 182.4 | 1630 | 64.2 | 2644 | 104.1 | 3585 | 7903.6 | |
350 | 4765 | 10505.0 | |||||||
400 | 4799 | 10580.0 | |||||||
450 | 4823 | 189.8 | 1630 | 64.2 | 2777 | 109.3 | 5345 | 11783.7 | |
500 | 5394 | 11891.7 | |||||||
550 | 4980 | 196.1 | 1865 | 73.4 | 2723 | 107.2 | 5973 | 13168.2 | |
600 | 6056 | 13351.2 |