Aldes ISONE® 2.1 Rectangular Fire Damper
Model: 11040067 | ISONE2.1 600X400 FTE70 MANUAL RELEASE
Product Overview
The Aldes ISONE® 2.1 fire damper is designed for use in tertiary buildings (ERP, IGH) to restore the fire resistance rating of partitions traversed by ventilation ducts. It offers ease of selection with a single model for various partitions and fire ratings.
Key Product Advantages
- Single damper model for all partition types: simplifies selection.
- Ergonomic, quick reset handle: operates in 2 seconds.
- Optional stainless steel spindle for demanding environments.
- Optional remote control box (0.7m or 3m).
- ALDES SecurONE application compatibility for data management.
- Unique, versatile mechanism: easy to select, install, and maintain.
- Kit Babyastall available for straightforward installation in lightweight partitions.
Product Description
This fire damper is equipped with a default thermal release fusible link at 70°C. It can be controlled by an electromagnetic coil (24/48VDC normally open, 24VCC or 48VCC normally closed) and features a 24-48 VCC/VDC reset motor. It provides fire resistance up to 120 minutes on standard partitions.
Available Sizes
- ISONE® 2.1 Rectangular PM: Dimensions (LxH) range from 200x100 mm to 800x600 mm.
- ISONE® 2.1 Rectangular GM: Dimensions (LxH) range from L≥800, H≥600, up to 1500x500 mm or 1000x1000 mm.
Application Areas
Suitable for new construction, renovation projects, and tertiary premises.
Installation
Installation is designed to be flexible:
- Can be installed without sealing on lightweight partitions, even with a post-mounted frame.
- Recessed mounting is possible on concrete walls/slabs, cellular concrete, plasterboard walls, and plasterboard type A (1h) and type F (2h) partitions.
- Remote mounting is supported using the PROMAT / GEOSTAF system with the EASYNSTAL kit.
- Installation tabs facilitate positioning on lightweight partitions.
- The Easynstall kit simplifies installation in lightweight type A partitions (60 minutes).
- An adaptation piece is available for connecting to oblong ducts.
- Extended reservation dimensions are available as per EXAP EN 15882-2:2015, rules X.45 and X.46.
- Installation must adhere to fire classification reports.
Key Features
- Certified and compliant with NF S 61937-5 and NF537 standards.
- CE marked according to EN 15650: 1812-CPR-1837.
- Standard Class C airtightness according to EN 1751.
- Fire resistance rating of EI 120 S -500 Pa achieved on concrete walls/slabs, cellular concrete, type F plasterboard, and with PROMAT/Geostaff remote mounting.
- Complies with EXAP EN 15882-2:2015, rules X.45 and X.46.
- Available in sizes from 200x100 mm up to 1500x500 / 1000 mm.
Complementary Features
- 100% upgradeable mechanism.
- Single damper design adaptable to all wall types.
- Installation on lightweight partitions with a post-mounted frame is supported.
- Reset handle clearly indicates the damper's position.
- Features a large electrical connection box.
- Optional stainless steel spindle for use in corrosive or hostile environments.
- Kit Easynstall for simplified installation in lightweight partitions.
- Optional remote control box available.
- Designed for low pressure drop.
Dimensional Data
Reference: 11040067
Dimension | Value (mm) |
---|---|
E | 25 |
F | 169 |
G | 71 |
H | 400 |
L | 600 |
ZA | Y/2 - 122 |
Installation Clearances
Diagrams illustrate required opening sizes and minimum clearances for installation:
- Concrete Wall/Slab: Requires openings of X+80 x Y+80 mm or X+145 x Y+145 mm, with minimum clearances.
- Plasterboard Partitions (120 min): Requires openings of X+70 x Y+70 mm.
- Lightweight Partitions (120 min): Requires openings of X+70 x Y+70 mm.
- Lightweight Partitions (60 min with Kit Easynstall): Requires openings of X+70 x Y+70 mm and minimum clearances of ≥98 mm.
Principle of Operation
The ISONE® 2.1 fire damper operates as follows:
- 1: Installation Tab: Used for securing the damper within the partition.
- 2: Fire Plate: A component related to fire containment.
- 3: ISONE® 2.1 PM Mechanism: The core operating and reset mechanism.
- 4: Blade: The damper blade, available in 25mm thickness (PM model) or 50mm thickness (GM model), which closes to prevent fire spread.
- 5: 30mm Connection Flange: For connecting ventilation ducts.