ISONE® 2.1 Rectangular Fire Damper
Model: 11040048 | ISONE2.1 400X300 FTE70 DECLENCHEUR MANU
Fire and Fire/Smoke Dampers
Key Product Advantages
- Single damper model suitable for all partition types, simplifying selection.
- Ergonomic reset handle for rapid, 2-second operation.
- Optional stainless steel axis for challenging environments.
- Optional remote command box (0.7m or 3m).
- Aldes SecurONE application for damper data collection and sharing.
- Unique mechanism design, from basic to fully equipped, ensuring ease of selection, installation, and maintenance.
- Babyastall kit available for simplified installation in lightweight partitions.
Product Description
Fire dampers designed for tertiary buildings, including public access buildings (ERP) and high-rise buildings (IGH). These dampers restore the fire resistance of partitions penetrated by ventilation ducts.
Standard features include a thermal trip fuse with a 70°C default release temperature. They can be controlled by a 24/48VDC fail-safe (emission) or 24VDC/48VDC fail-secure (rupture) electromagnetic coil. The reset motor operates on 24-48 VDC.
The ISONE® 2.1 dampers offer fire resistance ratings of up to 120 minutes on all common partition types.
Available sizes:
- ISONE® 2.1 Rectangular PM: Width (W) from 200x100 mm to 800x600 mm.
- ISONE® 2.1 Rectangular GM: Width (W) up to 1500x500 mm or 1000x1000 mm.
Application Areas
- New construction
- Renovation projects
- Tertiary premises
Installation
- Installation without sealing on lightweight partitions is possible, even with a post-mounted frame.
- Recessed mounting is suitable for:
- Concrete walls/slabs and cellular concrete.
- Plaster tile walls.
- Plasterboard type A (1-hour fire rating) and type F (2-hour fire rating).
- Remote mounting is supported using PROMAT / GEOSTAF systems with the EASYNSTAL kit.
- Installation on lightweight partitions is facilitated by dedicated installation tabs.
- The Easynstall kit simplifies the installation of rectangular dampers in lightweight type A partitions (60 minutes fire rating).
- An adapter piece is available for connection to oblong ducts.
- Installation must comply with EXAP EN 15882-2:2015, rules X.45 and X.46 for extended dimensions.
- Ensure adherence to fire classification reports during the installation process.
Main Characteristics
- Certified and compliant with NF S 61937-5 and NF537 standards.
- CE marked according to EN 15650: 1812-CPR-1837.
- Standard leakage class C according to EN 1751.
- Fire resistance rating EI 120 S -500 Pa achieved on concrete walls/slabs, cellular concrete, and plasterboard type F, including PROMAT/Geostaff remote mounting.
- Complies with EXAP EN 15882-2:2015, rules X.45 and X.46.
- Available in a size range from 200x100 mm to 1500x500 / 1000 mm.
Additional Characteristics
- 100% upgradeable mechanism.
- Unique damper design adaptable to all partition types.
- Installation on lightweight partitions with a post-mounted frame.
- Reset handle clearly indicates the damper's position.
- Features a large electrical connection box.
- Optional stainless steel axis for use in hostile environments.
- Easynstall kit available for straightforward installation in lightweight partitions.
- Optional remote command box.
- Designed for low pressure drop.
Dimensional Data
Reference | E (mm) | F (mm) | G (mm) | H (mm) | L (mm) | ZA (mm) |
---|---|---|---|---|---|---|
11040048 | 25 | 169 | 71 | 300 | 400 | Y/2 - 122 |
ISONE® 2.1 Rectangular Size Range:
- ISONE® 2.1 GM: Widths from 800x600 mm up to 1500x500 mm / 1000x1000 mm.
- ISONE® 2.1 PM: Widths from 200x100 mm to 800x600 mm.
Installation Diagram Descriptions
Diagram illustrating the installation of an ISONE® 2.1 rectangular fire damper on a concrete wall, requiring a minimum opening of X+80 mm by Y+80 mm.
Diagram showing the installation of an ISONE® 2.1 rectangular fire damper on a concrete slab, requiring a minimum opening of X+145 mm by Y+145 mm.
Diagram depicting the installation of an ISONE® 2.1 rectangular fire damper on a plaster tile partition (120 minutes fire resistance), requiring a minimum opening of X+70 mm by Y+70 mm.
Diagram illustrating the installation of an ISONE® 2.1 rectangular fire damper on a lightweight partition (120 minutes fire resistance), requiring a minimum opening of X+70 mm by Y+70 mm.
Diagram showing the installation of an ISONE® 2.1 rectangular fire damper on a lightweight partition (60 minutes fire resistance) using the Easynstall kit, requiring a minimum opening of X+70 mm by Y+70 mm.
Principle of Operation
The ISONE® 2.1 fire damper comprises the following key components:
- 1: Installation tab
- 2: Frame plate
- 3: ISONE® 2.1 PM mechanism
- 4: Blade (25mm thickness for PM model, 50mm for GM model)
- 5: 30mm connection flange