Easy UPS 3S IP40 Kit for UPS

Model Numbers: E3SOPT031, E3SOPT032

Latest updates available on the Schneider Electric website: 8/2025

Legal Information

This document provides general descriptions and technical characteristics for Schneider Electric products. It is not a substitute for detailed site-specific planning. Users must conduct their own risk analysis and evaluation for specific applications. Schneider Electric trademarks are the property of Schneider Electric SE. Other brands are trademarks of their respective owners. This document is protected by copyright and may not be reproduced or transmitted without prior written permission from Schneider Electric, except for a personal, non-exclusive license for consultation.

Schneider Electric reserves the right to make changes to this document without notice. Schneider Electric and its subsidiaries assume no liability for errors or omissions or for unintended use or misuse of the information contained herein.

Important Safety Instructions - SAVE THESE INSTRUCTIONS

Read these instructions carefully before installing, operating, servicing, or maintaining the equipment. Pay attention to safety messages that warn of potential hazards.

Safety Alert Symbol

The safety alert symbol (⚠️) indicates potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death.

DANGER

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE

NOTICE is used to address practices not related to physical injury and can result in equipment damage.

Qualified Personnel

Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. A qualified person is defined as someone with skills and knowledge related to electrical equipment construction, installation, and operation, and who has received safety training to recognize and avoid hazards. Per IEC 62040-1, this includes inspection, installation, and maintenance by a skilled person.

Safety Precautions

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

All safety instructions in this document must be read, understood, and followed. Failure to do so will result in death or serious injury.

NOTICE: RISK OF OVERHEATING

Respect space requirements around the UPS system and do not cover ventilation openings when the UPS is in operation. Failure to follow these instructions can result in equipment damage.

Electrical Safety

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Warning Label for Autostart:

Autostart is enabled. The UPS will automatically restart when the mains supply returns.

Specifications

Model List

Load Derating for UPS with IP40 Kit Installed

NOTICE: RISK OF OVERHEATING

A UPS with an IP40 kit may require load derating. Read all instructions in the installation manual before installing or working on this UPS. Failure to follow these instructions can result in equipment damage.

UPS commercial reference UPS rating Maximum continuous load at 30°C (PF=1) Maximum continuous load at 40°C (PF=0.9) Operating temperature and load derating
E3SUPS10K3IB 10 7 kVA/7 kW 7 kVA/6.3 kW 0°C to 30°C (PF=1): 70% derating.
30°C to 40°C (PF=0.9): 70% derating.
E3SUPS15K3IB 15 10.5 kVA/10.5 kW 10.5 kVA/9.45 kW
E3SUPS20K3IB 20 14 kVA/14 kW 14 kVA/12.6 kW
E3SUPS10KHB 10 7 kVA/7 kW 7 kVA/6.3 kW
E3SUPS15KHB 15 10.5 kVA/10.5 kW 10.5 kVA/9.45 kW
E3SUPS20KHB 20 14 kVA/14 kW 14 kVA/12.6 kW
E3SUPS30K3IB 30 21 kVA/21 kW 21 kVA/18.9 kW
E3SUPS30KHB 30 21 kVA/21 kW 21 kVA/18.9 kW
E3SUPS40KHB 40 28 kVA/28 kW 28 kVA/25.2 kW

Torque Specifications

Bolt size Torque
M4 1.2 Nm

Installation Procedure

NOTE: This procedure describes installing the IP40 kit after power and signal cabling are completed. Rear access is required.

DANGER: UPS must be completely turned off while the kit is being installed.

Failure to follow these instructions will result in death or serious injury.

  1. Follow the UPS installation manual to install the UPS.
  2. Install the IP40 Front Protection on the UPS (see page 11).
  3. Install the IP40 Rear Protection on the UPS (see page 15).
  4. Install the IP40 Side Protection on the UPS (see page 17).

Install the IP40 Front Protection on the UPS

DANGER: The UPS must be turned completely OFF before performing this procedure.

Failure to follow these instructions will result in death or serious injury.

  1. Open the front door of the UPS.
  2. Remove the supporting brackets on the front door. Save the M4 screws for reuse.
  3. Remove the M4 screws on the left side of the fan cover and the battery compartment cover. Save the M4 screws for reuse.
  4. Cut the cable tie on the front door.
  5. Take out the silicone strips from the IP40 kit. Peel off the protective films from the silicone strips and attach them to the UPS in the indicated positions using the reused M4 screws.
  6. Remove the existing air filter from the UPS.
  7. Install the new air filter on the UPS:
    • Fix the new air filter with the reused M4 screws.
    • Ensure that the silicone strips are pressed under the air filter.
  8. Install the small bracket:
    • Remove the screws next to the front door display cover. Save the M4 screws for reuse.
    • Install the small bracket on the UPS with the reused M4 screws.
  9. Close the front door.

Install the IP40 Rear Protection on the UPS

DANGER: The UPS must be turned completely OFF before performing this procedure.

Failure to follow these instructions will result in death or serious injury.

  1. Remove the M4 screws from the rear panels. Save the screws for reuse. NOTE: Do not remove the rear panels from the UPS.
  2. Install the new IP40 protection over the existing rear panels using the reused M4 screws.

Install the IP40 Side Protection on the UPS

DANGER: The UPS must be turned completely OFF before performing this procedure.

Failure to follow these instructions will result in death or serious injury.

  1. Remove the left and right side panels from the UPS. Save the M4 screws for reuse.
  2. Attach the protective sponge strips on both the left and right sides of the UPS.
  3. Reinstall the left and right side panels on the UPS using the reused M4 screws.
Models: E3SOPT031, E3SOPT032, E3SOPT031, E3SOPT031 E3SOPT032 Easy UPS 3S for Internal Batteries, E3SOPT031 E3SOPT032, Easy UPS 3S for Internal Batteries, 3S for Internal Batteries, Internal Batteries

File Info : application/pdf, 20 Pages, 3.07MB

PDF preview unavailable. Download the PDF instead.

990-66302 EN

References

PDFlib PDI 10.0.2p2 (C /Win64)

Related Documents

Preview Backfeed Box Installation Guide for Easy UPS 3S, 3S Pro, and 3M
This document provides installation instructions for the Schneider Electric Backfeed Box, designed for use with Easy UPS 3S, Easy UPS 3S Pro, and Easy UPS 3M systems. It includes safety precautions, specifications, and detailed steps for mounting and wiring.
Preview Schneider Electric Wall-Mounted Maintenance Bypass Panel Installation Guide
Comprehensive installation guide for Schneider Electric's Wall-Mounted Maintenance Bypass Panel, compatible with Galaxy VS, Easy UPS 3S, Easy UPS 3S Pro, and Easy UPS 3M. Includes safety instructions, specifications, and installation procedures.
Preview Schneider Electric Parallel Maintenance Bypass Panel Installation Guide for Easy UPS 3S and 3S Pro
This document provides detailed installation instructions for the Schneider Electric Parallel Maintenance Bypass Panel, designed for use with Easy UPS 3S and Easy UPS 3S Pro systems. It covers safety precautions, system overview, specifications, and step-by-step installation procedures.
Preview Easy UPS 3-Phase Modular 50-250 kW Installation Guide
This document provides installation instructions for the Easy UPS 3-Phase Modular, covering models from 50 kW to 250 kW. It includes safety precautions, electrical specifications, and installation procedures for various configurations.
Preview Schneider Electric Easy UPS 3M & 3L Battery Breaker Kit Installation Guide
Installation guide for Schneider Electric's Easy UPS 3M and Easy UPS 3L Battery Breaker Kits (models E3MBBK60K80H, E3MBBK100K200H). Covers safety, specifications, trip settings, and wiring.
Preview Schneider Electric Easy UPS 3S End of Life Instructions & Disassembly Guide
Detailed guide for the end-of-life management and disassembly of Schneider Electric Easy UPS 3S (10-40 kVA, 208V, 400V). Includes component identification, safety precautions, and recyclability information.
Preview Easy UPS 3S 10-40 kVA Operation Manual
This document provides operational guidance for the Schneider Electric Easy UPS 3S, covering models from 10 to 40 kVA. It details safety instructions, system overviews, user interface, operating procedures, configuration, testing, troubleshooting, and maintenance.
Preview Schneider Electric Easy UPS 3S 208 V UL Earthing Principles
This document outlines the earthing principles for Schneider Electric's Easy UPS 3S 208 V UL models with internal batteries, providing detailed diagrams for various configurations.