Backfeed Box Installation

For Easy UPS 3S, Easy UPS 3S Pro, and Easy UPS 3M

Model Numbers: SP3OPT008, SP3OPT009, SP3OPT010

Latest updates are available on the Schneider Electric website

Publication Date: 7/2025

Legal Information

The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions.

This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.

The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.

This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.

Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.

Important Safety Instructions

Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE is used to address practices not related to physical injury.

Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. Schneider Electric assumes no responsibility for any consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

Safety Precautions

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

NOTICE: RISK OF OVERHEATING

Electrical Safety

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Specifications

Backfeed Contactor Specifications

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

The SP3OPT008, SP3OPT009, and SP3OPT010 must only be used with the UPSs listed in the compatibility matrices below.

Easy UPS 3S Compatibility Matrix

UPS ratingEasy UPS 3S 3:1Easy UPS 3S 3:3
Single mains systemInput1 x SP3OPT0091 x SP3OPT008
Input current limitation (A)65 A, 3 phases (input current limitation)
172 A, 1 phase (bypass current)(1)
89 A, 3 phases
Dual mains systemInput1 x SP3OPT0081 x SP3OPT008
Input current limitation (A)65 (3 phases)89 (3 phases)
Bypass1 x SP3OPT009
172 (1 phase)
1 x SP3OPT008
77 (3 phases)

(1) Current includes the overload capacity of 125% continuous for Easy UPS 3S in static bypass mode.

Easy UPS 3S Pro Compatibility Matrix

UPS ratingEasy UPS 3S Pro 3:3
Single mains systemInput1 x SP3OPT008
Input current limitation (A)81 A (3 phases)
Dual mains systemInput1 x SP3OPT008
Input current limitation (A)81 A (3 phases)
Bypass1 x SP3OPT008
67 A (3 phases)

Easy UPS 3M Compatibility Matrix

UPS ratingEasy UPS 3M 3:3
60 kVA80 kVA100 kVA120 kVA160 kVA200 kVA
Single mains systemInput1 x SP3OPT0091 x SP3OPT0091 x SP3OPT0091 x SP3OPT0101 x SP3OPT0101 x SP3OPT010
Input current limitation (A)155206258309412515(2)
Dual mains systemInput1 x SP3OPT0091 x SP3OPT0091 x SP3OPT0091 x SP3OPT0101 x SP3OPT0101 x SP3OPT010
Input current limitation (A)155206258309412515(2)
Bypass1 x SP3OPT0091 x SP3OPT0091 x SP3OPT0091 x SP3OPT0101 x SP3OPT0101 x SP3OPT010
Bypass current (A)91122152184246307

(2) 515 A at operating temperature of 0 °C to 30 °C. Maximum 450 A at operating temperature of 30 °C to 40 °C.

Power Contactor Specifications

SP3OPT008SP3OPT009SP3OPT010
Power contactor95 A, 3P
LC1D95V7; AC3 duty 95 A
275 A, 3P
LC1G150LSEA, AC1 duty 275 A
550 A, 3P
LC1G400LSEA, AC1 duty 550 A
Rated operational voltageRefer to the UPS installation manual for rated UPS operational voltage.
Coil operating voltage320-440 VAC200-500 VAC200-500 VAC
Frequency (Hz)50/60
Short circuit capacity10 kA Icc conditioned by the upstream protection listed in the UPS installation manuals.
Earthing systemTNS - TT. Not compatible with IT earthing system where 4 pole contactor is required.

Recommended Upstream Protection

Refer to the UPS installation manual for recommended upstream protection.

Recommended Cable Sizes

NOTE: Aluminum cables are not supported.

Refer to the UPS installation manual for recommended cable sizes.

Recommended Bolt and Lug Sizes (Copper)

Cable sizeBolt sizeCable lug type
16 mm²M8KST TLK16-8
25 mm²M8KST TLK25-8
35 mm²M8KST TLK35-8
50 mm²M10KST TLK50-10
70 mm²M10KST TLK70-10
95 mm²M10KST TLK95-10
120 mm²M10KST TLK120-10
150 mm²M10KST TLK150-10

Torque Specifications

Bolt sizeTorque
M41.7 Nm
M52.2 Nm
M65 Nm
M817.5 Nm
M1030 Nm
M1250 Nm

Backfeed Box Weights and Dimensions

Commercial referenceWeight kgHeight mmWidth mmDepth mm
SP3OPT00820300550200
SP3OPT00933600600250
SP3OPT01058800700400

Environment

OperatingStorage
TemperatureSP3OPT008 and SP3OPT009: 0 °C to 40 °C.
SP3OPT010: 0 °C to 30 °C. Operation at 30 °C to 40 °C at maximum 450 A.
-25 °C to 55 °C
Relative humidity0-95% non-condensing0-95% non-condensing
ElevationDesigned for operation in 0-2000 m
Protection classIP20
ColorRAL 9003, 85% gloss

Installation Procedure

Single Mains System Diagram

A diagram shows a UPS connected to a Backfeed box (input), with a load connected to the UPS. A signal cable and a power cable are indicated.

Dual Mains System Diagram

A diagram shows a UPS connected to a Backfeed box (input) and a Backfeed box (bypass). The UPS is connected to the load and bypass. A signal cable and a power cable are indicated.

Installation Steps:

  1. Mount the Backfeed Box to the Wall (page 13).
  2. Prepare the Backfeed Box for Cables (page 15).
  3. Connect the Input Power Cables to the Input Backfeed Box (page 17).
  4. For dual mains systems only: Perform one of the following:
    • Connect the Bypass Power Cables to the Bypass Backfeed Box for 3:1 System (Dual Mains System Only) (page 19).
    • Connect the Bypass Power Cables to the Bypass Backfeed Box for 3:3 System (Dual Mains System Only) (page 21).

Mount the Backfeed Box to the Wall

CAUTION: RISK OF INJURY OR EQUIPMENT DAMAGE

Instructions:

  1. Measure and mark the four mounting hole locations on the wall.

SP3OPT008 Mounting Diagram

A diagram shows the SP3OPT008 backfeed box with dimensions for mounting holes: 400 mm width, 338 mm height, with M10 Ø12 mm mounting holes.

SP3OPT009 Mounting Diagram

A diagram shows the SP3OPT009 backfeed box with dimensions for mounting holes: 450 mm width, 638 mm height, with M10 Ø12 mm mounting holes.

SP3OPT010 Mounting Diagram

A diagram shows the SP3OPT010 backfeed box with dimensions for mounting holes: 550 mm width, 638 mm height, with M10 Ø12 mm mounting holes.

Continued Instructions:

  1. Drill holes in each of the four marked locations.
  2. Mount the backfeed box to the wall.

Prepare the Backfeed Box for Cables

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Illustrations show SP3OPT008. The procedure is the same for SP3OPT009 and SP3OPT010.

  1. Open the front door.
  2. Remove the screws and the front plate.

Diagram: A diagram shows the inside of the backfeed box with arrows indicating the removal of the front plate.

  1. Remove the gland plate.

Diagram: A diagram shows the inside of the backfeed box with arrows indicating the removal of the gland plate.

  1. Drill or punch holes for cables or grommets/conduits (not provided) in the gland plate.
  2. Install grommets/conduits (if applicable) and refit the gland plate.

DANGER: Ensure that there are no sharp edges that can damage the cables.

Diagram: A diagram shows the gland plate with newly punched holes and arrows indicating the refitting of the gland plate.

Connect the Input Power Cables to the Input Backfeed Box

Instructions:

  1. Connect the PE cables.
  2. Connect the UPS input cables (L1, L2, L3, N).
  3. Connect the input cables (L1, L2, L3, N).
  4. Reinstall the front plate with the screws.
  5. Close and lock the front door.

SP3OPT008 (Input Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT008, indicating connections for PE, L1, L2, L3, and N for both UPS input and main input.

SP3OPT009 (Input Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT009, indicating connections for PE, L1, L2, L3, and N for both UPS input and main input.

SP3OPT010 (Input Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT010, indicating connections for PE, L1, L2, L3, and N for both UPS input and main input.

Connect the Bypass Power Cables to the Bypass Backfeed Box for 3:1 System (Dual Mains System Only)

NOTE: Follow the UPS installation manual to remove the single mains busbars in the UPS.

Instructions:

  1. Connect the PE cables.
  2. Connect the UPS bypass cables (L1, N).
  3. Connect the bypass cables (L1, N).

SP3OPT009 for 3:1 System (Bypass Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT009 in a 3:1 bypass configuration, indicating connections for PE, L1, L2, L3, and N for both UPS bypass and main bypass.

  1. Disconnect the signal cable E31 from the L2 busbar of the power contactor. Reconnect the E31 signal cable to the neutral busbar.
  2. Reinstall the front plate with the screws.
  3. Close and lock the front door.

Connect the Bypass Power Cables to the Bypass Backfeed Box for 3:3 System (Dual Mains System Only)

NOTE: Follow the UPS installation manual to remove the single mains busbars in the UPS.

Instructions:

  1. Connect the PE cables.
  2. Connect the UPS bypass cables (L1, L2, L3, N).
  3. Connect the bypass cables (L1, L2, L3, N).
  4. Reinstall the front plate with the screws.
  5. Close and lock the front door.

SP3OPT008 for 3:3 System (Bypass Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT008 in a 3:3 bypass configuration, indicating connections for PE, L1, L2, L3, and N for both UPS bypass and main bypass.

SP3OPT009 for 3:3 System (Bypass Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT009 in a 3:3 bypass configuration, indicating connections for PE, L1, L2, L3, and N for both UPS bypass and main bypass.

SP3OPT010 for 3:3 System (Bypass Only) Wiring Diagram: A diagram shows the internal wiring connections for the SP3OPT010 in a 3:3 bypass configuration, indicating connections for PE, L1, L2, L3, and N for both UPS bypass and main bypass.

Backfeed Box One Line Drawing

Instructions to end user:

Single Mains UPS (3:1) Diagram: A one-line diagram illustrates the connection of a primary power source to a backfeed box (SP3OPT009), then to a UPS (Easy UPS 3S 3:1 Single Feed), and finally to the load. It includes notes about contactor and upstream installation ratings and applicability to IT earthing systems.

Dual Mains UPS (3:1) Diagram: A one-line diagram illustrates the connection of a primary power source to a backfeed box (SP3OPT008), then to a UPS (Easy UPS 3S 3:1 Dual Feed), and finally to the load. It also shows a second backfeed box (SP3OPT009) connected to the bypass. It includes notes about contactor and upstream installation ratings and applicability to IT earthing systems.

Single Mains UPS (3:3) Diagram: A one-line diagram illustrates the connection of a primary power source to a backfeed box, then to a UPS (Easy UPS 3S Single Feed), and finally to the load. It includes notes about contactor and upstream installation ratings and applicability to IT earthing systems.

Dual Mains UPS (3:3) Diagram: A one-line diagram illustrates the connection of a primary power source to a backfeed box, then to a UPS (Easy UPS 3S Dual Feed), and finally to the load. It also shows a second backfeed box connected to the bypass. It includes notes about contactor and upstream installation ratings and applicability to IT earthing systems.

Models: SP3OPT0 Series Backfeed Box Power Contactor, SP3OPT0 Series, Backfeed Box Power Contactor, Box Power Contactor, Power Contactor, Contactor

File Info : application/pdf, 28 Pages, 3.34MB

PDF preview unavailable. Download the PDF instead.

990-92223B EN

References

PDFlib PDI 10.0.2p2 (C /Win64)

Related Documents

PreviewSchneider Electric Wall-Mounted Maintenance Bypass Panel Installation Guide
Comprehensive installation guide for Schneider Electric's Wall-Mounted Maintenance Bypass Panel, compatible with Galaxy VS, Easy UPS 3S, Easy UPS 3S Pro, and Easy UPS 3M. Includes safety instructions, specifications, and installation procedures.
PreviewSchneider Electric Parallel Maintenance Bypass Panel Installation Guide for Easy UPS 3S and 3S Pro
This document provides detailed installation instructions for the Schneider Electric Parallel Maintenance Bypass Panel, designed for use with Easy UPS 3S and Easy UPS 3S Pro systems. It covers safety precautions, system overview, specifications, and step-by-step installation procedures.
PreviewSchneider Electric Easy UPS 3M & 3L Battery Breaker Kit Installation Guide
Installation guide for Schneider Electric's Easy UPS 3M and Easy UPS 3L Battery Breaker Kits (models E3MBBK60K80H, E3MBBK100K200H). Covers safety, specifications, trip settings, and wiring.
PreviewEasy UPS 3-Phase Modular 50-250 kW Installation Guide
This document provides installation instructions for the Easy UPS 3-Phase Modular, covering models from 50 kW to 250 kW. It includes safety precautions, electrical specifications, and installation procedures for various configurations.
PreviewSchneider Electric Easy UPS 3S End of Life Instructions & Disassembly Guide
Detailed guide for the end-of-life management and disassembly of Schneider Electric Easy UPS 3S (10-40 kVA, 208V, 400V). Includes component identification, safety precautions, and recyclability information.
PreviewEasy UPS 3S IP40 Kit Installation Guide
Installation instructions for the Schneider Electric Easy UPS 3S IP40 Kit, including safety precautions, specifications, and step-by-step procedures for front, rear, and side protection installation.
PreviewSchneider Electric Easy UPS 3S 208 V UL Earthing Principles
This document outlines the earthing principles for Schneider Electric's Easy UPS 3S 208 V UL models with internal batteries, providing detailed diagrams for various configurations.
PreviewEasy UPS 3S 10-40 kVA Operation Manual
This document provides operational guidance for the Schneider Electric Easy UPS 3S, covering models from 10 to 40 kVA. It details safety instructions, system overviews, user interface, operating procedures, configuration, testing, troubleshooting, and maintenance.