Danfoss AB-QM 4.0 Flexo, DN 15-20, PN 25

Description

The Danfoss AB-QM 4.0 Flexo, featuring an AB-QM valve, a 3-way ball valve design, and an 80mm center distance, is a compact and time-saving connection set. It is designed for creating optimal hydronic balance in cooling and heating applications with variable flow, such as those found in fan coil units (FCU) or chilled beams. Flow is controlled by the AB-QM pressure independent control valve to prevent overflow and maintain thermal unit efficiency.

Benefits: Installation

  • Saving time and space
  • Pre-assembled design
  • Reduced installation time
  • Easy setting and sizing, 100% authority and perfect control.

Trouble-free installations

  • Compact and space-saving installation
  • Pressure tested from factory - Nominal pressure PN25

Service

  • Enable fast servicing, maintenance, and trouble shooting
  • Easy flushing ✔️
  • Easy draining ✔️
  • Easy bypass ✔️
  • Easy cleaning of filter ✔️
  • Enables pressure and flow validation ✔️

Energy efficiency

Pressure independent flow control with AB-QM 4.0 offers improved indoor comfort with the best performance and energy savings, ensuring efficient energy transfer and minimal pumping costs.

Applications

The AB-QM 4.0 Flexo is a pre-assembled, pressure-tested set used for terminal units, such as Fan Coil Units (FCU). The Danfoss AB-QM 4.0 Flexo solution includes an H-body (with integrated shut-off valves and the possibility to mount measuring plugs), strainer, drain, and the associated Danfoss AB-QM 4.0 pressure independent control valve.

The AB-QM ensures and controls the required flow at every terminal unit, maintaining hydronic balance within the system. The control valve has 100% authority, ensuring control stability. At partial load, it prevents overflow, unlike conventional solutions, by always limiting the flow to the required amount. Installing the AB-QM divides the entire system into independent control loops.

A wide range of Danfoss actuators are available for the AB-QM 4.0, suitable for all control needs. These actuators are available as On/Off, 0-10 Volt, 4-20 mA, and digital via field bus.

Ordering

AB-QM 4.0 Flexo with AB-QM valve

PictureTypeConnectionCentre (mm)Code No.
Diagram of DN15 LF (strainer) valveDN15 LF (strainer)Internal ½"80003Z1620
Diagram of DN15 (strainer) valveDN15 (strainer)Internal ½"003Z1621
Diagram of DN15 HF (strainer) valveDN15 HF (strainer)Internal ½"003Z1622
Diagram of DN20 (strainer) valveDN20 (strainer)Internal ¾"003Z1623
Diagram of DN20 HF (strainer) valveDN20 HF (strainer)Internal ¾"003Z1624
Diagram of DN15 LF valveDN15 LFInternal ½"80003Z1630
Diagram of DN15 valveDN15Internal ½"003Z1631
Diagram of DN15 HF valveDN15 HFInternal ½"003Z1632
Diagram of DN20 valveDN20Internal ¾"003Z1633
Diagram of DN20 HF valveDN20 HFInternal ¾"003Z1634

AB-QM 4.0 Flexo Accessories

DescriptionDimensionMaterialCommentsCode No.
AB-QM 4.0 Flexo InsulationDN15EPPHeating insulation003Z4751
DN20EPPHeating insulation003Z4752
AB-QM 4.0 Flexo flexible pipeDN15SS300 mm, set of 2 pcs003Z4794
DN20SS300 mm, set of 2 pcs003Z4795
Flexo extended handle (spare part)DN15-DN20AluminumBlack003Z4796
Test plugDN15-DN20DZR Brass-003Z0104
Measuring connector for drainDN15-DN20Brass-003L8143

For a complete range of AB-QM actuators, accessories, and spare parts, please refer to the AB-QM data sheet.

Technical Data

AB-QM 4.0 Flexo
Nominal diameterDN15LF1515 HF2020 HF
Flow rangeQnom (100 %)¹⁾l/h2006501.2001.1001.900
Setting range ¹⁾, ²⁾%10-100
Diff. pressure ³⁾Apmin ⁴⁾kPa1616251625
ApmaxkPa600
kvs ⁵⁾5.6
kvs with strainer ⁵⁾m³/h3.55
Pressure stagePN25
Control range1:1000
Control valve's characteristicLinear
Leakage acc. to standard IEC 534No visible leakage (at 100N)
For shut off functionAcc. to ISO 5208 class A - no visible leakage
Flow mediumWater and water mixture for closed heating and cooling systems according to plant type I for DIN EN 14868. When used in plant Type II for DIN EN 14868 appropriate protective measures are taken. The requirements of VDI 2035, part 1 + 2 are observed.
Medium temperature°C(-10°C) +2 ... +95°C
Strokemm4
Connection port fan coil sideInternal Rp ½" (ISO 7/1)
ConnectionConnection port system sideInternal G ½" (ISO228/1)
ActuatorM30 x 1.5
InsulationDensityg/l60
Water absorption%1.2±0.6
Insulation property / thermal conductivity39 mW/m·K
Fire behavior classificationBuilding, Euroclass E
Flex pipeConnection portInternal Rp ½" (ISO 7/1)Internal Rp ¾" (ISO 7/1)
Lengthmm300
Materials in mediumFlexo H-pieceBody and connectionDZR Brass (CW602N)
StrainerPTFE
Drain valveAluminum
Fittings, unionsStainless steel
GasketEPDM
Material out of mediumFlexo H-pieceOperating handlesW.Nr. 1.4310
Handwheel screwPPSU
Materials in mediumPICV (AB-QM)Valve bodiesDZR brass (CW602N)
Membranes and O-ringsPPSU
SpringsDZR brass (CW602N)
Spring supportStainless Steel (A2)
ShutterPA 6
Cone (Cv)DZR brass (CW602N)
Seat (Cv)PPSU
Material out of mediumPICV (AB-QM)ScrewStainless Steel (A2)
Plastic partsPA 6
AccessoriesInsulationEPP
Flexible pipeStainless steel (1.4404)
UnionStainless steel (1.4305)
NutBrass (CW617N)
GasketNBR
Test plugDZR (CW602N)

Notes:

  1. Factory setting of the valve is done at the nominal setting range.
  2. Regardless of the setting, the valve can modulate below 1% of the set flow.
  3. At minimum differential pressure, the valve reaches at least 90% of the nominal flow. Declaration of performance is available upon request.
  4. AB-QM 4.0
  5. Flexo connection set without AB-QM 4.0
  6. If the medium temperature when using AB-QM DN 15-20 is below 2°C, then ice forming on the spindle must be prevented; therefore, the valve should be insulated with dedicated cooling insulation.

According to suitability and usage, especially in not oxygen-tight systems, please mind the instructions given by the coolant producer. Pc - pressure controller part; Cv - Control valve part.

Design

The AB-QM 4.0 Flexo assembly consists of the following components:

  • 1. AB-QM 4.0 valve
  • 2. Strainer
  • 3. Drain connection & measuring station
  • 4. Black handle
  • 5. 3-way return valve
  • 6. 3-way inlet valve
  • 7. Bypass
  • 8. Optional test plug connections
  • 9. Stainless steel pipe

Presetting

The calculated flow can be adjusted easily without using special tools. The change of presetting (factory setting is 100%) can be done by following these steps:

  1. Remove the blue protective cap or the mounted actuator.
  2. Turn the pointer (clockwise to decrease) to the new setting.

Diagram illustrating the AB-QM 4.0 presetting dial for DN 15, 20, showing a scale from 0-10.

Installation

The small installation dimensions allow for easy installation of the Flexo connection set, even in limited spaces. The PICV valve should be installed in the return pipe from the thermal unit, with the flow directed according to the arrow on the AB-QM valve body. Danfoss highly recommends installing the Flexo using flexible pipes.

Diagram showing the installation of the AB-QM 4.0 Flexo in the return pipe from a Fan Coil Unit, connected to an HVAC System, with emphasis on flow direction and flexible pipe usage.

Note: The connection set can be installed in both cooling and heating applications.

Sizing

Example:

Given: Design flow in system 0.2 l/s (0.72m³/h = 720l/h).

Solution: In this case, we can select the AB-QM 4.0 DN15HF (Fig. 2) with Qnom = 1200 l/h for the AB-QM and presetting. The setting on the AB-QM DN 15 HF valve is the design flow divided by the nominal valve capacity: 720 l/h divided by 1200 l/h = 60%.

Flushing

There are three basic modes during flushing:

Forward flushing and draining

System flushing and draining should be done via the drain connection. Use the following procedure to drain (Fig. 3):

  1. Connect a pipe to the drain connection.
  2. Adjust the outlet 3-way valve to open the bypass [bypass symbol ①].
  3. Open the 3-way valve on the inlet side [inlet valve symbol ②].
  4. Open the shut-off valve on the drain [drain valve symbol ③].
  5. Drain the system.

Diagram illustrating the flushing setup with connections and valve operations, including a scale for measuring tool dimensions (5 mm, 3.5-4.5 mm x 0.7 mm) and CLOSE/OPEN indicators.

Flushing (continuous)

Flushing of main pipe (bypass)

High-level cleanliness of the main pipe network flushing is achievable since thermal units are isolated. Use the following procedure for flushing the main pipe via the bypass pipeline (Fig. 4):

  1. Adjust both 3-way valves to open the bypass [bypass symbol ① ②].
  2. Start with the flushing procedure.

Diagram showing the bypass flushing setup for the main pipe, with the Fan Coil Unit isolated and connected to the HVAC System.

Backward flushing and draining

This offers cleaning of the thermal unit. Backward flushing of the fan coil should be done only with a fully open valve or a fully open actuator mounted on the valve. Use the following procedure for flushing the main pipe via the bypass pipeline (Fig. 5):

  1. Connect a pipe to the drain connection [drain connection symbol ①].
  2. Close the inlet 3-way valve [inlet valve symbol ②].
  3. Open the shut-off valve on the drain [drain valve symbol ③].
  4. Start with the flushing procedure.

Diagram illustrating the backward flushing setup, including a scale for measuring tool dimensions (5 mm, 3.5-4.5 mm x 0.7 mm) and CLOSE/OPEN indicators.

Tender Text

The terminal units shall be connected to the system by way of a valve assembly. This valve assembly shall have the following characteristics:

  • The valve set shall comprise of the following components: PICV, H-piece valve body, measuring points, strainer valve, drain, and operating handles.
  • The assembly shall have a bypass line that, by manipulating the ball valves, will enable insulation of the terminal unit and PICV to allow for forwards- and backward flushing of the system.
  • The valve set shall have extended handles to allow operation with insulation.
  • It shall be possible to shut off the bypass.
  • The set shall be suitable for 25 Bars of static pressure (PN25).
  • The set shall be leak tested.
  • If required, the set shall be insulated by an EPP form-fitting shell.

The PICV shall have the following characteristics:

  • Flow limitation function.
  • Modulating below 1% of set flow, regardless of the setting.
  • Authority of 1 at all settings.
  • Able to close against 16 bars of differential pressure.
  • Linear control characteristic.
  • Setting scale in the percentage of flow.
  • Control ratio 1:1000.
  • Test plugs for pump optimization and flow measuring.
  • Characteristic changed from linear to equal percentage characteristic at all sizes by adjusting actuator settings.
  • Leakage rate Class IV.

Dimensions

Diagram showing the overall dimensions (A through H) of the AB-QM 4.0 Flexo assembly for different models.

DN15LFDN15DN15HFDN20DN20HF
ABCDEFGH
Dimension134.5125807798.5211Internal G½" (ISO 228/1)Internal Rp½" (ISO 7/1)
1441388077102213Internal G¾" (ISO 228/1)Internal Rp¾" (ISO 7/1)

Diagram showing connection port dimensions.

ABC
DN15Internal Rp½" (ISO 7/1)External G½" (ISO 228/1)307.5
DN20Internal Rp¾" (ISO 7/1)External G¾" (ISO 228/1)319.5

Diagram showing additional dimension measurements.

ABC
DN15135175160
DN20135185167

PDF preview unavailable. Download the PDF instead.

AI390954786833en-010103 Danfoss A/S Adobe PDF library 15.00

Related Documents

Preview Danfoss AB-QM 4.0 Flexo DN 15-20 Operating Guide
Comprehensive operating guide for the Danfoss AB-QM 4.0 Flexo, DN 15-20, covering installation, insulation, filter cleaning, operation, shut-off, maintenance, and flushing procedures. Includes technical specifications and dimensions.
Preview Danfoss ASV Automatic Balancing Valves - Technical Catalog
Comprehensive technical catalog detailing Danfoss ASV series automatic balancing valves, including their applications, features, construction, ordering information, technical specifications, and dimensioning guides for HVAC systems.
Preview Danfoss AB-QM DN 40-100 Operating Guide
This guide provides operating instructions for the Danfoss AB-QM DN 40-100 automatic balancing and control valve, covering installation, setting, resetting, locking, and measuring procedures.
Preview Danfoss AFPB-F / VFQ 2 (VFQ 21) Differential Pressure Regulator with Flow Limitation - Technical Data
Technical data for the Danfoss AFPB-F / VFQ 2 (VFQ 21) differential pressure regulator with flow limitation. This document details product specifications, ordering codes, technical data, construction, principle of operation, installation, and dimensions for these Danfoss regulators.
Preview Danfoss AB-PM DN 40-100 Operating Guide - Installation and Settings
Comprehensive operating and installation guide for the Danfoss AB-PM DN 40-100 pressure independent control valve, covering handle mounting, impulse tube connection, flow and pressure settings, manual shut-off, measuring, and actuator mounting.
Preview Danfoss Stellventile VR, VF und VFS: Datenblatt für Zwei- und Dreiwegeventile
Umfassendes Datenblatt von Danfoss für Stellventile der Serien VR, VF und VFS. Enthält technische Spezifikationen, Anwendungsbereiche, Bestellinformationen und Abmessungen für Zwei- und Dreiwegeventile.
Preview Danfoss ASV-D DN 15-50 Operating Guide
Operating guide for the Danfoss ASV-D valve, DN 15-50, covering installation, settings, shut-off, and measurement of flow and pressure drop. Includes technical specifications and dimensions for hydronic balancing.
Preview Danfoss AVQM-2 Flow Rate Controller: Installation and Operation Manual
Comprehensive guide for the Danfoss AVQM-2 flow rate controller, covering installation, operation, settings, troubleshooting, and technical specifications. Includes safety instructions and dimensional data.