Danfoss AB-QM 4.0 Flexo, DN 15-20 Operating Guide

Installation

This section details the installation process for the AB-QM 4.0 Flexo. Ensure proper handling and connection as per the diagrams.

Important Symbols:

Installation Steps:

Refer to the diagrams for specific connection and tightening procedures. Ensure correct wrench sizes are used for DN15 (27 mm, 29 mm) and DN20 (30 mm, 32 mm) connections.

Diagram Description: The diagrams illustrate the assembly of the valve, including flexible hoses and the correct orientation of components. Arrows indicate the direction of flow and assembly steps.

Insulation

Instructions for applying insulation to the AB-QM 4.0 Flexo unit. Follow the numbered steps in the provided diagrams.

Diagram Description: The diagrams show how to place insulation components around the valve assembly, ensuring a snug fit for optimal thermal performance.

Filter Cleaning

This section describes the procedure for cleaning the filter. It involves shutting off the flow, removing the filter, cleaning it, and reassembling.

Steps:

  1. Turn the valve to the 'SHUT' position.
  2. Unscrew the filter housing.
  3. Remove and clean the filter element.
  4. Reassemble the unit.

Diagram Description: Visuals demonstrate the process of accessing and cleaning the internal filter, including the use of a wrench (16 mm) and cleaning the filter element.

Operation

Information on the operation of the AB-QM 4.0 Flexo, including setting the flow rate using the adjustment dial.

Flow Rate Adjustment:

The adjustment dial allows setting the flow rate from 10% to 100%. The scale indicates the percentage of maximum flow.

Diagram Description: The diagram shows the adjustment dial with markings from 0 to 10, representing percentage settings. An arrow indicates the direction to turn for adjustment.

Shut-off/Maintenance

Procedures for shutting off the valve for maintenance purposes. This includes locking the valve in a specific position.

Diagram Description: The diagram illustrates how to lock the valve handle using a wire or seal to prevent unauthorized operation.

Flushing of Main Pipe

Instructions for flushing the main pipe connected to the system. This can be done via backward or forward flushing.

Backward Flushing:

The diagram shows the setup for backward flushing, where water is directed against the normal flow to clear the system.

Forward Flushing:

The diagram illustrates forward flushing, where water flows through the system in the normal direction to remove debris. It shows the use of a cup to collect flushed water and the operation of the drain valve.

Diagram Description: The diagrams depict the pipework configuration for both backward and forward flushing, highlighting the flow paths and the components involved, including the fan coil unit.

Technical Specifications and Dimensions

Detailed dimensions for different models (DN15LF, DN15, DN15HF, DN20, DN20HF) are provided in the tables below.

Dimensions Table 1

DN15LFDN15DN15HFDN20DN20HF
A185185185200200
B111.5111.5111.5111.5111.5
C9696969696
D6262626565
E5353535353
FR 1/2R 1/2R 1/2R 1/4R 1/4

Dimensions Table 2

AB
DN15R 1/2307.5
DN20R 1/4319.5

Dimensions Table 3

ABC
DN15120190200
DN20120190215

Diagram Description: The diagrams provide visual representations of the valve assembly with labeled dimensions (A, B, C, D, E, F) corresponding to the tables.

Flow Rate Settings

The following table provides flow rate (L/h, L/s, GPM) settings for various percentages of maximum flow for DN15 and DN20 models, including Low Flow (LF) and High Flow (HF) variants.

SettingDN15 LFDN 15DN 15 HFDN 20DN 20 HF
L/hL/sGPML/hL/sGPML/hL/sGPML/hL/sGPML/hL/sGPM
10%200.0060.09650.0180.291200.0330.531100.030.481900.0530.84
15%300.0080.13980.0270.431800.0500.791650.050.732850.0791.25
20%400.0110.181300.0360.572400.0671.062200.060.973800.1061.67
25%500.0140.221630.0450.723000.0831.322750.081.214750.1322.09
30%600.0170.261950.0540.863600.1001.593300.091.455700.1582.51
35%700.0190.312280.0631.004200.1171.853850.111.706650.1852.93
40%800.0220.352600.0721.144800.1332.114400.121.947600.2113.35
45%900.0250.402930.0811.295400.1502.384950.142.188550.2383.76
50%1000.0280.443250.0901.436000.1672.645500.152.429500.2644.18
55%1100.0310.483580.0991.576600.1832.916050.172.6610450.2904.60
60%1200.0330.533900.1081.727200.2003.176600.182.9111400.3175.02
65%1300.0360.574230.1171.867800.2173.437150.203.1512350.3435.44
70%1400.0390.624550.1262.008400.2333.707700.213.3913300.3705.86
75%1500.0420.664880.1352.159000.2503.968250.233.6314250.3966.27
80%1600.0440.705200.1442.299600.2674.238800.243.8715200.4226.69
85%1700.0470.755530.1542.4310200.2834.499350.264.1216150.4497.11
90%1800.0500.795850.1632.5810800.3004.769900.284.3617100.4757.53
95%1900.0530.846180.1722.7211400.3175.0210450.294.6018050.5027.95
100%2000.0560.886500.1812.8612000.3335.2811000.314.8419000.5288.37

Importer Information

Importer: TOB з іi "Данфосс TOB" 04080, Київ 80, п/с 168, Україна

Manufacturer: Danfoss A/S

Contact: Climate Solutions • danfoss.com • +4574882222

Any information provided, including product selection, application, design, weight, dimensions, capacity, or technical data, is considered informative and only binding if explicitly referenced in a quotation or order confirmation. Danfoss is not responsible for errors in catalogues, brochures, or other materials. Danfoss reserves the right to alter products without prior notice, including ordered products if alterations do not change form, fit, or function. All trademarks are property of Danfoss A/S or its group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Models: AB-QM 4.0 Pressure Independent Control Valves, AB-QM 4.0, Pressure Independent Control Valves, Independent Control Valves, Control Valves, Valves

PDF preview unavailable. Download the PDF instead.

AQ336274304280en-010103 Danfoss A/S Adobe PDF library 15.00

Related Documents

PreviewDanfoss AB-QM 4.0 Flexo DN 15-20 PN 25 Datasheet
Technical datasheet for the Danfoss AB-QM 4.0 Flexo, a pre-assembled, pressure-independent control valve assembly designed for optimal hydronic balancing in HVAC cooling and heating applications. Features include easy installation, precise flow control, and energy efficiency.
PreviewDanfoss AB-QM DN 40-100 Operating Guide
This guide provides operating instructions for the Danfoss AB-QM DN 40-100 automatic balancing and control valve, covering installation, setting, resetting, locking, and measuring procedures.
PreviewDanfoss ASV Automatic Balancing Valves - Technical Catalog
Comprehensive technical catalog detailing Danfoss ASV series automatic balancing valves, including their applications, features, construction, ordering information, technical specifications, and dimensioning guides for HVAC systems.
PreviewDanfoss AB-PM DN 40-100 Operating Guide - Installation and Settings
Comprehensive operating and installation guide for the Danfoss AB-PM DN 40-100 pressure independent control valve, covering handle mounting, impulse tube connection, flow and pressure settings, manual shut-off, measuring, and actuator mounting.
PreviewDanfoss AVQM-2 Flow Rate Controller: Installation and Operation Manual
Comprehensive guide for the Danfoss AVQM-2 flow rate controller, covering installation, operation, settings, troubleshooting, and technical specifications. Includes safety instructions and dimensional data.
PreviewBeaCon Actuator Installation Guide | Danfoss
Installation guide for the Danfoss BeaCon Actuator, including dynamic balancing valves (AB-QM) and control valves (RA-G). Covers manual operation, indicator explanations, and safety notes.
PreviewDanfoss AFP B(-F) 2 / VFQ 2(1) / VFQ 22(1) Operating Guide
Comprehensive operating guide for Danfoss AFP B(-F) 2 and VFQ 2(1) / VFQ 22(1) control valves, detailing safety, application, assembly, installation, operation, maintenance, and technical specifications.
PreviewDanfoss AFPB-F / VFQ 2 (VFQ 21) Differential Pressure Regulator with Flow Limitation - Technical Data
Technical data for the Danfoss AFPB-F / VFQ 2 (VFQ 21) differential pressure regulator with flow limitation. This document details product specifications, ordering codes, technical data, construction, principle of operation, installation, and dimensions for these Danfoss regulators.