Pixsys PL300 User Manual

Data Acquisition Module

1. Data Acquisition Module PL300

The PL300 is a powerful data acquisition module that serves as an I/O interface for Industrial terminals or SCADA systems. It measures temperature values using various thermocouples and thermoresistances, and acquires normalized signals via a 14-bit converter. The module features 6 digital inputs for alarm notices and 2 linear outputs (isolated 14-bit) capable of driving different types of transducers. Additionally, it offers twelve relay outputs (2 relays rated at 8A and 10 relays rated at 5A / 230VAC resistive).

A key advantage of the PL300, compared to PC boards, is its ability to be placed close to the plant, communicating with the central unit via RS485 or Current Loop 20mA (both galvanic isolated). This configuration enhances immunity to external noise and simplifies wiring. The module is designed and manufactured in compliance with current CE standards, meeting the safety requirements for both light and heavy industry.

General Features

FeatureDescription
Operating Conditions0-45 °C, humidity 35-95% RH
BoxStandard DIN 43880 for DIN rail EN500200
ProtectionSelf-extinguishing Noryl 94V1
Input/Output ProtectionBox IP30, Terminal blocks IP20
WeightApprox. 400 gr.
Size90 x 160 x 53 mm (depth)

Hardware Data

CategoryDetails
Power Supply12-24 Vac/Vdc 10VA (For AC supply, use a separate isolation transformer 20VA per module)
Analog Inputs (selectable via software)AN1-AN4
  • Thermocouples: K, S, T, R, J, E
  • Thermoresistance: PT100, NI100, PT500, PT1000 (accuracy 0.2% ± 1 digit)
  • Voltage: 0-1V, 0-10V, 0-50mV (accuracy 0.2% ± 1 digit)
  • Current: 0-20mA, 4-20mA (accuracy 0.1% ± 1 digit)
Digital InputsI5-I10
  • PNP
Relay OutputsU1-U12
  • U1-U2: Relay 8A-230Vac (Normally Open and Normally Closed contacts)
  • U3-U12: Relay 5A-230Vac
SSR OutputsSSR1-SSR4
  • Supply 10-32 Vdc
  • Max 100mA for single output
Configurable Linear Outputs (selectable via software and internal dip-switch)OUT1, OUT2
  • Logic 0-14V (20mA max.)
  • Voltage 0-10V (12bit/20mA max.)
  • Current 4-20mA (12bit)
  • Galvanic isolated from power and inputs, but not isolated from each other.
Serial PortCOM1: RS485 (terminal block and 8-pole plug connector, galvanic isolated)
COM2: RS232 MODBUS (8-pole plug connector, not isolated)

Software Data

CategoryDescription
PID and ON/OFF AlgorithmsUp to 4 control loops: ON/OFF control or PID with Autotuning function (automatic PID parameter setting).
Motorized Valves ControlUtilizes two coupled relay outputs (e.g., U1-U2, U3-U4) to drive motorized valves. Position control is achieved by measuring the time of opening and closing impulses.
Time Proportioning OutputFor ON/OFF controlled values, outputs can be configured for time-proportioning ON/OFF operation. The period (sec.) and duty-cycle of the output signal are defined, and the PL300 generates it automatically.
Communication ProtocolModbus RTU. Selectable Baud-rate and answer delay.

1.2 Frontal Panel

The front panel of the PL300 features:

1.3 Size and Installation

The PL300 module is designed for DIN rail mounting (EN50022). The dimensions are 160 mm width, 90 mm height, and 53 mm depth. Terminal blocks are clearly labeled for various connections including COM1, COM2, digital inputs, analog inputs (AN1-AN4), and RS-485/Current Loop connections.

Visual Description of Connections:

1.4 Electrical Wirings

Detailed wiring information is provided for various connections:

Terminal No.NameDescription
1, 2+ / GNDSupply 12-24V AC/DC 10VA. Use of a dedicated transformer secondary is recommended for improved noise immunity.
25, 26, 27C, A, BSerial communication port (RS485 / C.L. 20mA). Terminals C are reference signals, A and B are for RS485 communication.
22, 23, 24AN1+, AN1-, AN1CAnalog Input 1: Positive signal, Reference signal, PT100 compensation.
19, 20, 21AN2+, AN2-, AN2CAnalog Input 2: Positive signal, Reference signal, PT100 compensation.
15, 16, 17AN3+, AN3-, AN3CAnalog Input 3: Positive signal, Reference signal, PT100 compensation.
12, 13, 14AN4+, AN4-, AN4CAnalog Input 4: Positive signal, Reference signal, PT100 compensation.
3, 6, 9, 18COM INPUTCommon positive signal for digital inputs. Can be used to activate inputs or power sensors. Input voltage is not stabilized.
11, 10, 8, 7, 5I5, I6, I7, I8, I10Digital Inputs. Short-circuiting the COM INPUT terminal activates the input, indicated by the LED.
28-45Relay Outputs (U1-U12)Various relay contacts (Common, N.O., N.C.) for outputs U1 through U12.
46, 47OUT1+, OUT1-Linear Output 1: Positive and Reference signals for 0-10 Volt or 4-20 mA.
48, 49OUT2+, OUT2-Linear Output 2: Positive and Reference signals for 0-10 Volt or 4-20 mA.

1.4.1 Examples of sensor connections to analog inputs PL300

2-Wire Connection (0-20mA / 4-20mA):

3-Wire Connection (0-10V):

1.4.2 Example of connection to RS485 and to a Master unit

A daisy-chain connection for RS485 communication is shown, connecting multiple PL300 modules to a master unit. Shielded twisted-pair cable is recommended. A 220 ohm termination resistor is used at the end of the bus.

1.5 Select type of linear output

The PL300 has two linear outputs (OUT1, OUT2) configurable via software and dip-switches. To configure:

  1. Disconnect power.
  2. Remove the upper cover.
  3. Set dip-switches SW1 (for OUT1) and SW2 (for OUT2) according to the desired output type:

Replace the cover and restart the PL300. Note: Dip-switches SW1-1 and SW2-1 are used for communication address setting, not output selection.

1.6 Communication address

Two dip-switches (SW1 and SW2) allow setting the module's address for communication with a master device. Up to four modules can be connected directly. For more than four modules, an offset parameter must be configured in Modbus word 5.

Module Address = Address Offset + Combination of DIP-Switches

To set the address:

  1. Disconnect power.
  2. Remove the upper cover.
  3. Set dip-switches SW1-1 and SW2-1 as shown below. The resulting value is added to the offset value for the complete address.

Combinations for DIP=0, DIP=1, DIP=2, DIP=3 are illustrated with diagrams of the dip-switch settings.

Replace the cover and restart the PL300.

1.7 List of configuration parameters

Configuration parameters are stored in EEPROM and are retained after power loss. Each parameter can be written up to 100,000 times. Modifying parameters initiates a 2-second initialization of input reading and output rates.

Parameters are represented using hexadecimal digits, divided into 4 nibbles:

Analog Input Configuration (P-01 to P-04)

These parameters define the type of sensor connected to analog inputs AN1, AN2, AN3, and AN4.

ParameterDescription
P-01Configuration analog input AN1
P-02Configuration analog input AN2
P-03Configuration analog input AN3
P-04Configuration analog input AN4
0No connected sensor (Input used as digital input)
1Type K (-270/1370°C)
2Type S (-50/1760°C)
3Type T (-270/400°C)
4Type R (-50/1760°C)
5Type J (-210/1200°C)
6Type E (-270/1000°C)
7PT100 (-200/800°C)
8NI100 (-60/180°C)
10Voltage 0..1V
11Voltage 0..10V
12Current 0..20mA
13Current 4..20mA
14Voltage 0..50mV
15PT500 with resistor 506 Ohm 0.1% parallel (-200/350°C)
16NI1000 with resistor 470 Ohm 0.1% parallel (-60/150°C)

Scale Limits (P-05 to P-12)

These parameters define the numeric limits for analog conversion for signals connected to AN1-AN4 (for current/voltage inputs).

ParameterDescription
P-05Lower limit scale AN1 (-3000.0 + 3000.0)
P-06Upper limit scale AN1 (-3000.0 + 3000.0)
P-07Lower limit scale AN2 (-3000.0 + 3000.0)
P-08Upper limit scale AN2 (-3000.0 + 3000.0)
P-09Lower limit scale AN3 (-3000.0 + 3000.0)
P-10Upper limit scale AN3 (-3000.0 + 3000.0)
P-11Lower limit scale AN4 (-3000.0 + 3000.0)
P-12Upper limit scale AN4 (-3000.0 + 3000.0)

Calibration (P-13 to P-20)

These parameters define the calibration for converting AN1-AN4 signals to correct reading mistakes. The formula is: Value = Value + (Value * GAIN calibration) / 100.0 + OFFSET Calibration.

ParameterDescription
P-13Calibration OFFSET AN1 (-999.9 + 999.9)
P-14Calibration GAIN AN1 (-999.9 + 999.9%)
P-15Calibration OFFSET AN2 (-999.9 + 999.9)
P-16Calibration GAIN AN2 (-999.9 + 999.9%)
P-17Calibration OFFSET AN3 (-999.9 + 999.9)
P-18Calibration GAIN AN3 (-999.9 + 999.9%)
P-19Calibration OFFSET AN4 (-999.9 + 999.9)
P-20Calibration GAIN AN4 (-999.9 + 999.9%)

Software Filter (P-21)

P-21: Software filter (1-20 sec) for conversion of AN1, AN2, AN3, AN4.

Linear Output Type (P-22, P-23)

These parameters define the type of linear output used. Dip-switches must be set correctly. Time for SSR output is set on P-24 (OUT1) and P-25 (OUT2).

ValueDescription
0Not used
1Logic 0-14V (30mA)
2Voltage 0...10V
3Current 4..20mA
4(Reserved)
5SSR time proportioning (Period set on P-24 / P-25)

Servo-Control Parameters (P-24 to P-31)

These parameters configure the servo-control and operating modes for various outputs (relay and SSR).

ParameterDescription
P-24Time for servo-control 1 (0-600 sec.) for outputs U1, U2, SSR1, OUT1.
P-25Time for servo-control 2 (0-600 sec.) for outputs U3, U4, SSR2, OUT2.
P-26Time for servo-control 3 (0-600 sec.) for outputs U5, U6, SSR3.
P-27Time for servo-control 4 (0-600 sec.) for outputs U7, U8, SSR4.
P-28SERVO-CONTROL1 Operating mode for relay output U1, U2 or SSR1.
P-29SERVO-CONTROL2 Operating mode for relay output U3, U4 or SSR2.
P-30SERVO-CONTROL3 Operating mode for relay output U5, U6 or SSR3.
P-31SERVO-CONTROL4 Operating mode for relay output U7, U8 or SSR4.

Relay State in Off-line Condition (P-32)

P-32: Defines the state of relays during communication failure with the MASTER for over 60 seconds. Each bit corresponds to a relay (Bit0 for U1, Bit1 for U2, etc.). Value 65535 disables this function.

ValueDescription
0Open contact
1Closed contact

1.8 Configuration of alarms for analog inputs

Each analog input can have two alarms configured, with operating modes defined by parameters P-57 to P-76. The following alarm types are available:

Visual diagrams illustrate the behavior of each alarm type relative to the signal, alarm threshold, and hysteresis.

1.9 Tuning (Automatic setting of PID parameters)

Tuning adjusts the controller's characteristics to match the process for optimal performance, aiming for:

Tuning involves calculating and setting parameters such as:

1.10 Protocol Modbus RTU

The PL300 supports Modbus RTU for communication with SCADA systems or terminals. This enables parameter programming, I/O configuration, and reading of analog/digital inputs and outputs control.

Features of Modbus RTU:

A diagram shows the pinout for the PL300's COM1 plug (8-pin) for RS485 communication.

1.11 Addresses WORD/BIT PL300 for Modbus RTU

This section details the Modbus addresses for data handling (words and bits) by the PL300. It specifies read/write features and default starting values.

Data Storage Types:

WORD Addresses

MODBUS ADDRESSDescriptionREAD/WRITERESET VALUE
0Type of deviceR20
1Software version PL300R100
5Slave address MODBUS protocolR/WEEP
96Value of linear output OUT1 (Range 0-10000)RP-55
97Value of linear output OUT2 (Range 0-10000)RP-56
98Serial transmission counterR/W0
99Reset monitor (force to "0" at reset)R/W0
100Value analog input AN1R?
101Value analog input AN2R?
102Value analog input AN3R?
103Value analog input AN4R?
104Value digital inputs (bit0 → I1,..., bit9 → I10)R?
105Status relay outputs (bit0 → U1,..., bit11 → U12)R?
106Temperature cold junction PL300R?
107Flag for module status (1 = error/fail)R?
108Alarms status analog inputs (bit0 → alarm no.1 AN1,..., bit7 → alarm no.2 AN4)R?
109-120Timer (minutes) for closing of relays U1-U12/SSR1-SSR4R/WTAMP
150-153Setting of servo control outputs 1-4 (Range 0-10000)R/W0
154Setting of linear output OUT1 (Range 0-10000)R/WP-55
155Setting of linear output OUT2 (Range 0-10000)R/WP-56
156Setting relay outputs (bit0 → U1,..., bit11 → U12)R/W0
157Enable relay modify via serial communication (1=enable, 0=disable)R/W0
158-161Control setpoint AN1-AN4R/WTAMP
162Control Run/Stop AN1÷AN4 (1=RUN, 0=Stop)R/WTAMP
163Start Auto-tuning AN1÷AN4 (only for reverse P.I.D.) (1=START)R/WTAMP
164-167Select source analog input for control loops 1-4R/WTAMP
168-171Select source setpoint for control loops 1-4R/WTAMP
172-175Select PID parameters for control loops 1-4R/WTAMP
176-179Min/Max % output OUT1, OUT2R/WTAMP
200-237Configuration parameters P-01 to P-38R/WEEP
238-275Configuration parameters P-39 to P-76R/WEEP
276-280Configuration parameters P-77 to P-81R/WEEP

BIT Addresses

MODBUS ADDRESSDESCRIPTIONREAD/WRITERESET VALUE
300-309Status digital input I1-I10R?
400-411Status relay output U1-U12R?
420-431Setting relay output U1-U12R/W0
440-451Enable modify relay output U1-U12 via serial comm.R/W0
500-507Status alarm no. 1 and 2 input AN1-AN4R?
600-603Control Run/stop AN1-AN4 (1=Run, 0=Stop)R/WTAMP
700-703Start auto-tune PID control AN1-AN4 (1=Start)R/WTAMP

For detailed information on specific parameters, refer to the parameter descriptions within this manual.

Models: PL-300 Temperature Controller, PL-300, Temperature Controller, Controller

File Info : application/pdf, 38 Pages, 290.66KB

PDF preview unavailable. Download the PDF instead.

pl300-rev-a

References

GPL Ghostscript 8.63

Related Documents

Preview PIXSYS PL260 PLC User Manual
Comprehensive user manual for the PIXSYS PL260 PLC, detailing its features, hardware specifications, electrical wiring, installation, and programming.
Preview PIXSYS PL250A User Manual
User manual for the PIXSYS PL250A, a compact PLC for acquiring analog and digital signals and performing complex mathematical functions. Details features, hardware, wiring, and ladder programming.
Preview Pixsys DRR244 Blue Line PID Controller Datasheet
Datasheet for the Pixsys DRR244 Blue Line PID controller, detailing its features, specifications, and ordering information. This controller is programmable via RFID/NFC and offers a powerful display, interactive text messages, and various input/output options.
Preview Pixsys ETD1644-AD I/O Module User Manual
User manual for the Pixsys ETD1644-AD I/O expansion board, detailing its features, installation, wiring, and configuration for industrial automation.
Preview Pixsys PL500 Modular PLC: Features and Specifications
Discover the Pixsys PL500, a modular, flexible, and powerful PLC. This document details its main features, technical specifications, and ordering codes for various configurations, including digital and analog I/O, Ethernet, and CANopen connectivity.
Preview Pixsys DRR450 Controller User Manual
This user manual provides comprehensive instructions for the Pixsys DRR450 controller, covering its features, installation, wiring, functions, and configuration parameters. Learn about automatic and manual tuning, serial communication, and alarm modes.
Preview Pixsys DRR460 Controller User Manual
This user manual provides comprehensive information on the Pixsys DRR460 controller, covering its features, installation, electrical wiring, and operational functions. It details safety guidelines, technical specifications, and various control and alarm modes for industrial applications.
Preview Pixsys ATR264 Cycle Temperature Controller Datasheet
Datasheet for the Pixsys ATR264, a 1/8 DIN cycle temperature controller designed for precision thermal processing applications. Features PID control, programmable profiles, and multiple output options.