Schneider Electric A9A27005/A9A27006/A9A27008 Rotary Handle Installation Guide
This document provides comprehensive instructions for installing Schneider Electric A9A27005, A9A27006, and A9A27008 rotary handles, compatible with iC60, Vigi iC60, and IID circuit breakers.
Product Variants
The rotary handles are available in the following configurations:
- A9A27005: Black handle (черная ручка, 黑色手柄)
- A9A27006: Red handle (красная ручка, 红色手柄)
- A9A27008: No handle (без ручки, 不带手柄)
Product identification label: S1A44655.
General Installation Procedure
The installation process involves several key stages:
- Mounting the rotary mechanism onto the circuit breaker.
- Installing the breaker and mechanism assembly into an electrical enclosure.
- Attaching the external rotary handle to the shaft.
- Performing operational tests and final checks.
Mounting the Rotary Mechanism (Steps 1a, 1b, 2b)
This section details how to attach the rotary mechanism to the circuit breaker body.
For iC60, iC60 + Vigi iC60, and IID breakers:
- Align the rotary mechanism with the circuit breaker.
- Secure the mechanism by pressing until it clicks into place. This is indicated by prompts like "[Click! Press! Snap!]".
- Ensure all connections are firm and secure.
Specific diagrams show the process for different breaker types (iC60, iC60 + Vigi iC60, IID) and their respective pole configurations (2P, 3P, 4P).
Enclosure Installation (Steps 2a, 3a, 4a, 3b, 4b)
This covers the installation of the assembly into an electrical enclosure.
Panel Preparation and Mounting
- Mount the rotary mechanism assembly onto the enclosure panel.
- Secure the assembly using screws, with a torque specification of 1 N.m for some components.
- Prepare the enclosure door for the shaft, which may involve drilling holes. A Ø50 mm diameter hole is typically required for the shaft.
- Install the shaft guide and support components.
Shaft Installation
- Insert the rotary shaft through the enclosure panel and into the mechanism.
- The required shaft length is specified as 494 mm - A.
- Align the shaft with the mounting points on the enclosure door.
Handle Mechanism Attachment
- Mount the external handle mechanism to the enclosure door.
- Secure this mechanism with screws, often with a torque specification of 1.5 N.m.
Attaching the Rotary Handle (Steps 4a, 5b)
This is the final step for connecting the user-interface handle.
- Attach the rotary handle to the shaft. Ensure the handle is initially set to the [OFF] position.
- The handle is designed for shafts with a diameter range of Ø 5...8 mm.
- Secure the handle onto the shaft.
- A locking feature is available, allowing a padlock to be attached for safety.
Operation and Testing (Steps 5a, 6a, 5b, 6b)
This section describes how to operate the handle and perform required tests.
- The handle can be rotated to the [ON] and [OFF] positions.
- IID Regular TEST / IID периодический испытание / IID 定期测试: Specific testing procedures for IID breakers are outlined, ensuring correct operation.
- Perform several ON/OFF cycles to confirm smooth operation.
- Verify that the locking mechanism functions correctly if engaged.
Technical Data and Dimensions
Detailed dimensions and specifications are provided for various configurations.
Dimensions (mm)
iC60 and IID Series:
| Configuration | Z (mm) | X (mm) | Y (mm) |
|---|---|---|---|
| iC60 2P | 25.3 | 44.5 | 76.8 |
| iC60 2P + Vigi | 25.3 | 44.5 | 76.8 |
| iC60 3P | 25.3 | 44.5 | 76.8 |
| iC60 3P + Vigi | 43 | 62 | 94.5 |
| iC60 4P | 43 | 62 | 94.5 |
| iC60 4P + Vigi | 43 | 62 | 94.5 |
| IID 2P | 25.3 | 44.5 | 76.8 |
| IID 4P | 25.3 | 44.5 | 76.8 |
General Mounting Dimensions:
- Shaft diameter: Ø50 mm
- Shaft angle tolerance: 45° ± 2°
- D = P - 128 mm
- D = L - X
- Condition for P: 166 < P < 500
P vs. F Dimensions:
| P (mm) | F (mm) |
|---|---|
| 300 | 5 |
| 500 | 11 |
Final Checks and Compliance
Final Assembly: Ensure the handle is securely attached and operates smoothly through its full range of motion.
Torque Values: Adhere to specified torque values (e.g., 1 N.m, 1.5 N.m) for secure connections.
Important Information:
This product must be installed, connected, and used in compliance with prevailing standards and/or installation regulations. As standards, specifications, and designs change, always seek confirmation of the information provided in this publication.
The following multilingual statements are included:
English: This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations. As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.
French: Ce produit doit être installé, raccordé et utilisé en respectant les normes et/ou les règlements d'installation en vigueur. En raison de l'évolution des normes et du matériel, les caractéristiques et cotes d'encombrement données ne nous engagent qu'après confirmation par nos services.
Russian: Данное изделие должно устанавливаться, подключаться и использоваться в соответствии с действующими стандартами и/или нормативными требованиями по установке. Поскольку стандарты, спецификации и элементы конструкции могут периодически изменяться, запросите подтверждение актуальности данных, приведенных в этой публикации.
Chinese: 本产品的安装、连接和使用必须遵循现行标准和/或安装法规要求。由于标准、规格和设计的不断调整,请向施耐德电气确认本出版物所提供的信息。