Product Overview
The Siemens Wet Differential Pressure Sensors, part of the QBE3190UD series, utilize advanced ceramic technology for reliable performance across various industries. These sensors are designed for unidirectional measurements and feature a three-valve manifold for integrated functionality.
Key Features and Specifications
This document details the installation process for models including QBE3190UD25, QBE3190UD50, and QBE3190UD100. It outlines the necessary tools, prerequisites, and step-by-step procedures for safe and effective setup.
Maximum Manifold Pressure Rating: 250 psi. Exceeding this rating may damage the sensor.
Installation Guidance
- Required Tools: Includes thread sealant (Loctite 565 or equivalent), crescent wrenches, and screwdrivers.
- Prerequisites: Proper compression fittings and preparation with thread sealant are essential to prevent leaks.
- Procedure: The instructions cover assembling the sensor/manifold, connecting pressure lines, wiring termination, and mounting the unit. Specific guidance is provided for pressurizing the system and bleeding air.
Safety Information
WARNING: Failure to follow procedures may result in personal injury or loss of life.
CAUTION: Improper installation can lead to equipment damage or data loss.